Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a manual · part 48 of 53

DL06 Micro PLC User Manual, Volume 1 of 2, pages 470 to 479

Pages 470 to 479 of 524

The original document is the PDF (6.4 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the AutomationDirect Direct Logic DL06 and Koyo DL06 D0-06DD1

Page 470

Chapter 5: Intelligent Box (IBox) Instructions

ECOM100 RX Network Read (ECRX) (IB-740)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

DS5

Used

HPP

N/A

5–316

ECOM100 RX Network Read performs the RX instruction with built-in interlocking with all other ECOM100 RX (ECRX) and ECOM100 WX (ECWX) IBoxes in your program to simplify communications networking. It will perform the RX on the specified ECOM100#'s network, which corresponds to a specific unique ECOM100 Configuration (ECOM100) IBox at the top of your program. The Workspace parameter is an internal, private register used by this IBox and MUST BE UNIQUE in this one instruction and MUST NOT be used anywhere else in your program. Whenever this IBox has power, it will read element data from the specified slave into the given destination V memory buffer, giving other ECOM100 RX and ECOM100 WX IBoxes on that ECOM100# network a chance to execute. For example, if you wish to read and write data continuously from 5 different slaves, you can have all of these ECRX and ECWX instructions in ONE RUNG driven by SP1 (Always On). They will execute round-robin style, automatically. ECRX Parameters • ECOM100#: this is a logical number associated with this specific ECOM100 module in the specified slot. All other ECxxxx IBoxes that need to reference this ECOM100 module must reference this logical number • Workspace: specifies a V-memory location that will be used by the instruction • Slave ID: specifies the slave ECOM(100) PLC that will be targeted by the ECRX instruction • From Slave Element (Src): specifies the slave address of the data to be read • Number of Bytes: specifies the number of bytes to read from the slave ECOM(100) PLC • To Master Element (Dest): specifies the location where the slave data will be placed in the master ECOM100 PLC • Success: specifies a bit that will turn on once the request is completed successfully • Error: specifies a bit that will turn on if the instruction is not successfully completed

Parameter ECOM100# . . . . . . . . . . . . . . . . . . . . . . . . . . . . K Workspace . . . . . . . . . . . . . . . . . . . . . . . . . . . . V Slave ID . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . K From Slave Element (Src) X,Y,C,S,T,CT,GX,GY,V,P Number of Bytes . . . . . . . . . . . . . . . . . . . . . . . K To Master Element (Dest) . . . . . . . . . . . . . . . . V Success . . . . . . . . . . . . . . . . . . . . X,Y,C,GX,GY,B Error . . . . . . . . . . . . . . . . . . . . . . X,Y,C,GX,GY,B

DL06 Range K0-255 See DL06 V-memory map - Data Words K0-90 See DL06 V-memory map K1-128 See DL06 V-memory map - Data Words See DL06 V-memory map See DL06 V-memory map

DL06 Micro PLC User Manual, 3rd Edition Rev. A

Page 471

Chapter 5: Intelligent Box (IBox) Instructions

ECRX Example Rung 1: The ECOM100 Config IBox is responsible for coordination/interlocking of all ECOM100 type IBoxes for one specific ECOM100 module. Tag the ECOM100 in slot 1 as ECOM100# K0. All other ECxxxx IBoxes refer to this module # as K0. If you need to move the module in the base to a different slot, then you only need to change this one IBox. V400 is used as a global result status register for the other ECxxxx IBoxes using this specific ECOM100 module.V401 is used to coordinate/interlock the logic in all of the other ECxxxx IBoxes using this specific ECOM100 module. V402-V502 is a common 130 byte buffer available for use by the other ECxxxx IBoxes using this specific ECOM100 module.

(example continued on next page)

DL06 Micro PLC User Manual, 3rd Edition Rev. A

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

5–317

Page 472

Chapter 5: Intelligent Box (IBox) Instructions

ECRX Example (cont’d)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

Rung 2: Using ECOM100# K0, read X0-X7 from Slave K7 and write them to slave K5 as fast as possible. Store them in this local PLC in C200-C207, and write them to C300-C307 in slave K5. Both the ECRX and ECWX work with the ECOM100 Config IBox to simplify all networking by handling all of the interlocks and proper resource sharing. They also provide very simplified error reporting. You no longer need to worry about any SP "busy bits" or "error bits", or what slot number a module is in, or have any counters or shift registers or any other interlocks for resource management. In this example, SP1 (always ON) is driving both the ECRX and ECWX IBoxes in the same rung. On the scan that the Network Read completes, the Network Write will start that same scan. As soon as the Network Write completes, any pending operations below it in the program would get a turn. If there are no pending ECOM100 IBoxes below the ECWX, then the very next scan the ECRX would start its request again. Using the ECRX and ECWX for all of your ECOM100 network reads and writes is the fastest the PLC can do networking. For local Serial Ports, DCM modules, or the original ECOM modules, use the NETCFG and NETRX/NETWX IBoxes.

5–318

DL06 Micro PLC User Manual, 3rd Edition Rev. A

Page 473

Chapter 5: Intelligent Box (IBox) Instructions

ECOM100 WX Network Write(ECWX) (IB-741) DS5

Used

HPP

N/A

ECOM100 WX Network Write performs the WX instruction with built-in interlocking with all other ECOM100 RX (ECRX) and ECOM100 WX (ECWX) IBoxes in your program to simplify communications networking. It will perform the WX on the specified ECOM100#'s network, which corresponds to a specific unique ECOM100 Configuration (ECOM100) IBox at the top of your program. The Workspace parameter is an internal, private register used by this IBox and MUST BE UNIQUE in this one instruction and MUST NOT be used anywhere else in your program. Whenever this IBox has power, it will write data from the master's V memory buffer to the specified slave starting with the given slave element, giving other ECOM100 RX and ECOM100 WX IBoxes on that ECOM100# network a chance to execute. For example, if you wish to read and write data continuously from 5 different slaves, you can have all of these ECRX and ECWX instructions in ONE RUNG driven by SP1 (Always On). They will execute round-robin style, automatically. ECWX Parameters • ECOM100#: this is a logical number associated with this specific ECOM100 module in the specified slot. All other ECxxxx IBoxes that need to reference this ECOM100 module must reference this logical number • Workspace: specifies a V-memory location that will be used by the instruction • Slave ID: specifies the slave ECOM(100) PLC that will be targeted by the ECWX instruction • From Master Element (Src): specifies the location in the master ECOM100 PLC where the data will be sourced from • Number of Bytes: specifies the number of bytes to write to the slave ECOM(100) PLC • To Slave Element (Dest): specifies the slave address the data will be written to • Success: specifies a bit that will turn on once the request is completed successfully • Error: specifies a bit that will turn on if the instruction is not successfully completed

Parameter

DL06 Range

ECOM100# . . . . . . . . . . . . . . . . . . . . . . . . . . . . K Workspace . . . . . . . . . . . . . . . . . . . . . . . . . . . . V Slave ID . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . K From Master Element (Src) . . . . . . . . . . . . . . . V Number of Bytes . . . . . . . . . . . . . . . . . . . . . . . K To Slave Element (Dest) X,Y,C,S,T,CT,GX,GY,V,P Success . . . . . . . . . . . . . . . . . . . . X,Y,C,GX,GY,B Error . . . . . . . . . . . . . . . . . . . . . . X,Y,C,GX,GY,B

K0-255 See DL06 V-memory map - Data Words K0-90 See DL06 V-memory map - Data Words K1-128 See DL06 V-memory map See DL06 V-memory map See DL06 V-memory map

DL06 Micro PLC User Manual, 3rd Edition Rev. A

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

5–319

Page 474

Chapter 5: Intelligent Box (IBox) Instructions

ECWX Example

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

Rung 1: The ECOM100 Config IBox is responsible for coordination/interlocking of all ECOM100 type IBoxes for one specific ECOM100 module. Tag the ECOM100 in slot 1 as ECOM100# K0. All other ECxxxx IBoxes refer to this module # as K0. If you need to move the module in the base to a different slot, then you only need to change this one IBox. V400 is used as a global result status register for the other ECxxxx IBoxes using this specific ECOM100 module.V401 is used to coordinate/interlock the logic in all of the other ECxxxx IBoxes using this specific ECOM100 module. V402-V502 is a common 130 byte buffer available for use by the other ECxxxx IBoxes using this specific ECOM100 module.

5–320

DL06 Micro PLC User Manual, 3rd Edition Rev. A

(example continued on next page)

Page 475

Chapter 5: Intelligent Box (IBox) Instructions

ECWX Example (cont’d) Rung 2: Using ECOM100# K0, read X0-X7 from Slave K7 and write them to slave K5 as fast as possible. Store them in this local PLC in C200-C207, and write them to C300-C307 in slave K5. Both the ECRX and ECWX work with the ECOM100 Config IBox to simplify all networking by handling all of the interlocks and proper resource sharing. They also provide very simplified error reporting. You no longer need to worry about any SP "busy bits" or "error bits", or what slot number a module is in, or have any counters or shift registers or any other interlocks for resource management. In this example, SP1 (always ON) is driving both the ECRX and ECWX IBoxes in the same rung. On the scan that the Network Read completes, the Network Write will start that same scan. As soon as the Network Write completes, any pending operations below it in the program would get a turn. If there are no pending ECOM100 IBoxes below the ECWX, then the very next scan the ECRX would start its request again. Using the ECRX and ECWX for all of your ECOM100 network reads and writes is the fastest the PLC can do networking. For local Serial Ports, DCM modules, or the original ECOM modules, use the NETCFG and NETRX/NETWX IBoxes.

DL06 Micro PLC User Manual, 3rd Edition Rev. A

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

5–321

Page 476

Chapter 5: Intelligent Box (IBox) Instructions

NETCFG Network Configuration (NETCFG) (IB-700)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

DS5

Used

HPP

N/A

5–322

Network Config defines all the common information necessary for performing RX/WX Networking using the NETRX and NETWX IBox instructions via a local CPU serial port, DCM or ECOM module. You must have the Network Config instruction at the top of your ladder/stage program with any other configuration IBoxes. If you use more than one local serial port, DCM or ECOM in your PLC for RX/WX Networking, you must have a different Network Config instruction for EACH RX/WX network in your system that utilizes any NETRX/NETWX IBox instructions. The Workspace parameter is an internal, private register used by the Network Config IBox and MUST BE UNIQUE in this one instruction and MUST NOT be used anywhere else in your program. The 2nd parameter "CPU Port or Slot" is the same value as in the high byte of the first LD instruction if you were coding the RX or WX rung yourself. This value is CPU and port specific (check your PLC manual), but possible values include KF2 for local CPU serial port 2 of an 06, K3 for a DCM or ECOM in slot 3 of a local 205 base, or K37 for a DCM in a 405 expansion base 3, slot 7. Since this logic only executes on the first scan, this IBox cannot have any input logic. NETCFG Parameters • Network#: specifies a unique # for each ECOM(100) or DCM network to use • CPU Port or Slot: specifies the CPU port number or slot number of DCM/ECOM(100) used • Workspace: specifies a V-memory location that will be used by the instruction

Parameter Network# . . . . . . . . . . . . . . . . . . . . . . . . . . . . . K CPU Port or Slot . . . . . . . . . . . . . . . . . . . . . . . K Workspace . . . . . . . . . . . . . . . . . . . . . . . . . . . . V

DL06 Range K0-255 K0-FF See DL06 V-memory map - Data Words

DL06 Micro PLC User Manual, 3rd Edition Rev. A

Page 477

Chapter 5: Intelligent Box (IBox) Instructions

NETCFG Example The Network Configuration IBox coordinates all of the interaction with other Network IBoxes (NETRX/NETWX). You must have a Network Configuration IBox for each serial port network, DCM module network, or original ECOM module network in your system. Configuration IBoxes must be at the top of your program and must execute every scan. This IBox defines Network# K0 to be for the local CPU serial port #2 (KF2). For local CPU serial ports or DCM/ECOM modules, use the same value you would use in the most significant byte of the first LD instruction in a normal RX/WX rung to reference the port or module. Any NETRX or NETWX IBoxes that need to reference this specific network would enter K0 for their Network# parameter. The Workspace register is used to maintain state information about the port or module, along with proper sharing and interlocking with the other NETRX and NETWX IBoxes in the program. This V memory register must not be used anywhere else in the entire program.

Permissive contacts or input logic cannot be used with this instruction

DL06 Micro PLC User Manual, 3rd Edition Rev. A

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

5–323

Page 478

Chapter 5: Intelligent Box (IBox) Instructions

Network RX Read (NETRX) (IB-701)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

DS5

Used

HPP

N/A

5–324

Network RX Read performs the RX instruction with built-in interlocking with all other Network RX (NETRX) and Network WX (NETWX) IBoxes in your program to simplify communications networking. It will perform the RX on the specified Network #, which corresponds to a specific unique Network Configuration (NETCFG) at the top of your program. The Workspace parameter is an internal, private register used by this IBox and MUST BE UNIQUE in this one instruction and MUST NOT be used anywhere else in your program. Whenever this IBox has power, it will read element data from the specified slave into the given destination V memory buffer, giving other Network RX and Network WX IBoxes on that Network # a chance to execute. For example, if you wish to read and write data continuously from 5 different slaves, you can have all of these NETRX and NETWX instructions in ONE RUNG driven by SP1 (Always On). They will execute round-robin style, automatically. NETRX Parameters • Network#: specifies the (CPU port’s, DCM’s, ECOM’s) Network # defined by the NETCFG instruction • Workspace: specifies a V-memory location that will be used by the instruction • Slave ID: specifies the slave PLC that will be targeted by the NETRX instruction • From Slave Element (Src): specifies the slave address of the data to be read • Number of Bytes: specifies the number of bytes to read from the slave device • To Master Element (Dest): specifies the location where the slave data will be placed in the master PLC • Success: specifies a bit that will turn on once the request is completed successfully • Error: specifies a bit that will turn on if the instruction is not successfully completed

Parameter Network# . . . . . . . . . . . . . . . . . . . . . . . . . . . . . K Workspace . . . . . . . . . . . . . . . . . . . . . . . . . . . . V Slave ID . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . K From Slave Element (Src) X,Y,C,S,T,CT,GX,GY,V,P Number of Bytes . . . . . . . . . . . . . . . . . . . . . . . K To Master Element (Dest) . . . . . . . . . . . . . . . . V Success . . . . . . . . . . . . . . . . . . . . X,Y,C,GX,GY,B Error . . . . . . . . . . . . . . . . . . . . . . X,Y,C,GX,GY,B

DL06 Range K0-255 See DL06 V-memory map - Data Words K0-90 See DL06 V-memory map K1-128 See DL06 V-memory map - Data Words See DL06 V-memory map See DL06 V-memory map

DL06 Micro PLC User Manual, 3rd Edition Rev. A

Page 479

Chapter 5: Intelligent Box (IBox) Instructions

NETRX Example Rung 1: The Network Configuration IBox coordinates all of the interaction with other Network IBoxes (NETRX/NETWX). You must have a Network Configuration IBox for each serial port network, DCM module network, or original ECOM module network in your system. Configuration IBoxes must be at the top of your program and must execute every scan. This IBox defines Network# K0 to be for the local CPU serial port #2 (KF2). For local CPU serial ports or DCM/ECOM modules, use the same value you would use in the most significant byte of the first LD instruction in a normal RX/WX rung to reference the port or module. Any NETRX or NETWX IBoxes that need to reference this specific network would enter K0 for their Network# parameter. The Workspace register is used to maintain state information about the port or module, along with proper sharing and interlocking with the other NETRX and NETWX IBoxes in the program. This V memory register must not be used anywhere else in the entire program.

(example continued on next page)

DL06 Micro PLC User Manual, 3rd Edition Rev. A

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

5–325