Chapter 5: Intelligent Box (IBox) Instructions

NETRX Example (cont’d)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

Rung 2: Using Network# K0, read X0-X7 from Slave K7 and write them to slave K5 as fast as possible. Store them in this local PLC in C200-C207, and write them to C300-C307 in slave K5. Both the NETRX and NETWX work with the Network Config IBox to simplify all networking by handling all of the interlocks and proper resource sharing. They also provide very simplified error reporting. You no longer need to worry about any SP "busy bits" or "error bits", or what port number or slot number a module is in, or have any counters or shift registers or any other interlocks for resource management. In this example, SP1 (always ON) is driving both the NETRX and NETWX IBoxes in the same rung. On the scan that the Network Read completes, the Network Write will start that same scan. As soon as the Network Write completes, any pending operations below it in the program would get a turn. If there are no pending NETRX or NETWX IBoxes below this IBox, then the very next scan the NETRX would start its request again. Using the NETRX and NETWX for all of your serial port, DCM, or original ECOM network reads and writes is the fastest the PLC can do networking. For ECOM100 modules, use the ECOM100 and ECRX/ECWX IBoxes.

5–326

DL06 Micro PLC User Manual, 3rd Edition Rev. A

Page 481

Chapter 5: Intelligent Box (IBox) Instructions

Network WX Write (NETWX) (IB-702) DS5

Used

HPP

N/A

Network WX Write performs the WX instruction with built-in interlocking with all other Network RX (NETRX) and Network WX (NETWX) IBoxes in your program to simplify communications networking. It will perform the WX on the specified Network #, which corresponds to a specific unique Network Configuration (NETCFG) at the top of your program. The Workspace parameter is an internal, private register used by this IBox and MUST BE UNIQUE in this one instruction and MUST NOT be used anywhere else in your program. Whenever this IBox has power, it will write data from the master's V memory buffer to the specified slave starting with the given slave element, giving other Network RX and Network WX IBoxes on that Network # a chance to execute. For example, if you wish to read and write data continuously from 5 different slaves, you can have all of these NETRX and NETWX instructions in ONE RUNG driven by SP1 (Always On). They will execute round-robin style, automatically. NETWX Parameters • Network#: specifies the (CPU port’s, DCM’s, ECOM’s) Network # defined by the NETCFG instruction • Workspace: specifies a V-memory location that will be used by the instruction • Slave ID: specifies the slave PLC that will be targeted by the NETWX instruction • From Master Element (Src): specifies the location in the master PLC where the data will be sourced from • Number of Bytes: specifies the number of bytes to write to the slave PLC • To Slave Element (Dest): specifies the slave address the data will be written to • Success: specifies a bit that will turn on once the request is completed successfully • Error: specifies a bit that will turn on if the instruction is not successfully completed

Parameter

DL06 Range

Network# . . . . . . . . . . . . . . . . . . . . . . . . . . . . . K Workspace . . . . . . . . . . . . . . . . . . . . . . . . . . . . V Slave ID . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . K From Master Element (Src) . . . . . . . . . . . . . . . V Number of Bytes . . . . . . . . . . . . . . . . . . . . . . . K To Slave Element (Dest) X,Y,C,S,T,CT,GX,GY,V,P Success . . . . . . . . . . . . . . . . . . . . X,Y,C,GX,GY,B Error . . . . . . . . . . . . . . . . . . . . . . X,Y,C,GX,GY,B

K0-255 See DL06 V-memory map - Data Words K0-90 See DL06 V-memory map - Data Words K1-128 See DL06 V-memory map See DL06 V-memory map See DL06 V-memory map

DL06 Micro PLC User Manual, 3rd Edition Rev. A

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

5–327

Page 482

Chapter 5: Intelligent Box (IBox) Instructions

NETWX Example

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

Rung 1: The Network Configuration IBox coordinates all of the interaction with other Network IBoxes (NETRX/NETWX). You must have a Network Configuration IBox for each serial port network, DCM module network, or original ECOM module network in your system. Configuration IBoxes must be at the top of your program and must execute every scan. This IBox defines Network# K0 to be for the local CPU serial port #2 (KF2). For local CPU serial ports or DCM/ECOM modules, use the same value you would use in the most significant byte of the first LD instruction in a normal RX/WX rung to reference the port or module. Any NETRX or NETWX IBoxes that need to reference this specific network would enter K0 for their Network# parameter. The Workspace register is used to maintain state information about the port or module, along with proper sharing and interlocking with the other NETRX and NETWX IBoxes in the program. This V memory register must not be used anywhere else in the entire program.

5–328

DL06 Micro PLC User Manual, 3rd Edition Rev. A

(example continued on next page)

Page 483

Chapter 5: Intelligent Box (IBox) Instructions

NETWX Example (cont’d) Rung 2: Using Network# K0, read X0-X7 from Slave K7 and write them to slave K5 as fast as possible. Store them in this local PLC in C200-C207, and write them to C300-C307 in slave K5. Both the NETRX and NETWX work with the Network Config IBox to simplify all networking by handling all of the interlocks and proper resource sharing. They also provide very simplified error reporting. You no longer need to worry about any SP "busy bits" or "error bits", or what port number or slot number a module is in, or have any counters or shift registers or any other interlocks for resource management. In this example, SP1 (always ON) is driving both the NETRX and NETWX IBoxes in the same rung. On the scan that the Network Read completes, the Network Write will start that same scan. As soon as the Network Write completes, any pending operations below it in the program would get a turn. If there are no pending NETRX or NETWX IBoxes below this IBox, then the very next scan the NETRX would start its request again. Using the NETRX and NETWX for all of your serial port, DCM, or original ECOM network reads and writes is the fastest the PLC can do networking. For ECOM100 modules, use the ECOM100 and ECRX/ECWX IBoxes.

DL06 Micro PLC User Manual, 3rd Edition Rev. A

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

5–329

Page 484

Chapter 5: Intelligent Box (IBox) Instructions

CTRIO Configuration (CTRIO) (IB-1000)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

DS5

Used

HPP

N/A

5–330

CTRIO Config defines all the common information for one specific CTRIO module which is used by the other CTRIO IBox instructions (for example, CTRLDPR - CTRIO Load Profile, CTREDRL - CTRIO Edit and Reload Preset Table, CTRRTLM - CTRIO Run to Limit Mode, ...). The Input/Output parameters for this instruction can be copied directly from the CTRIO Workbench configuration for this CTRIO module. Since the behavior is slightly different when the CTRIO module is in an EBC Base via an ERM, you must specify whether the CTRIO module is in a local base or in an EBC base. The DL06 PLC only supports local base operation at this time. You must have the CTRIO Config IBox at the top of your ladder/stage program along with any other configuration IBoxes. If you have more than one CTRIO in your PLC, you must have a different CTRIO Config IBox for EACH CTRIO module in your system that utilizes any CTRIO IBox instructions. Each CTRIO Config IBox must have a UNIQUE CTRIO# value. This is how the CTRIO IBoxes differentiate between the different CTRIO modules in your system. The Workspace parameter is an internal, private register used by the CTRIO Config IBox and MUST BE UNIQUE in this one instruction and MUST NOT be used anywhere else in your program. Since this logic only executes on the first scan, this IBox cannot have any input logic. CTRIO Parameters • CTRIO#: specifies a specific CTRIO module based on a user defined number • Slot: specifies which PLC option slot the CTRIO module occupies • Workspace: specifies a V-memory location that will be used by the instruction • CTRIO Location: specifies where the module is located (local base only for DL06) • Input: This needs to be set to the same V-memory register as is specified in CTRIO Workbench as ‘Starting V address for inputs’ for this unique CTRIO. • Output: This needs to be set to the same V-memory register as is specified in CTRIO Workbench as ‘Starting V address for outputs’ for this unique CTRIO.

DL06 Micro PLC User Manual, 3rd Edition Rev. A

Page 485

Chapter 5: Intelligent Box (IBox) Instructions

Parameter

DL06 Range

CTRIO# . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . K Slot . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . K Workspace . . . . . . . . . . . . . . . . . . . . . . . . . . . . V Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V

K0-255 K1-4 See DL06 V-memory map - Data Words See DL06 V-memory map - Data Words See DL06 V-memory map - Data Words

CTRIO Example Rung 1: This sets up the CTRIO card in slot 2 of the local base. Each CTRIO in the system will need a separate CTRIO I-box before any CTRxxxx I-boxes can be used for them. The CTRIO has been configured to use V2000 through V2025 for its input data, and V2030 through V2061 for its output data.

Permissive contacts or input logic cannot be used with this instruction

DL06 Micro PLC User Manual, 3rd Edition Rev. A

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

5–331

Page 486

Chapter 5: Intelligent Box (IBox) Instructions

CTRIO Add Entry to End of Preset Table (CTRADPT) (IB-1005)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

DS5

Used

HPP

N/A

5–332

CTRIO Add Entry to End of Preset Table, on a leading edge transition to this IBox, will append an entry to the end of a memory based Preset Table on a specific CTRIO Output resource. This IBox will take more than 1 PLC scan to execute. Either the Success or Error bit will turn on when the command is complete. If the Error Bit is on, you can use the CTRIO Read Error Code (CTRRDER) IBox to get extended error information. Entry Type: K0: Set K1: Reset K2: Pulse On (uses Pulse Time) K3: Pulse Off (uses Pulse Time) K4: Toggle K5: Reset Count Note that the Pulse Time parameter is ignored by some Entry Types. The Workspace register is for internal use by this IBox instruction and MUST NOT be used anywhere else in your program. CTRAPT Parameters • CTRIO#: specifies a specific CTRIO module based on a user defined number (see CTRIO Config) • Output#: specifies a CTRIO output to be used by the instruction • Entry Type: specifies the Entry Type to be added to the end of a Preset Table • Pulse Time: specifies a pulse time for the Pulse On and Pulse Off Entry Types • Preset Count: specifies an initial count value to begin at after Reset • Workspace: specifies a V-memory location that will be used by the instruction • Success: specifies a bit that will turn on once the instruction has successfully completed • Error: specifies a bit that will turn on if the instruction does not complete successfully

Parameter CTRIO# . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . K Output# . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . K Entry Type . . . . . . . . . . . . . . . . . . . . . . . . . . . V,K Pulse Time . . . . . . . . . . . . . . . . . . . . . . . . . . V,K Preset Count . . . . . . . . . . . . . . . . . . . . . . . . . V,K Workspace . . . . . . . . . . . . . . . . . . . . . . . . . . . . V Success . . . . . . . . . . . . . . . . . . . . X,Y,C,GX,GY,B Error . . . . . . . . . . . . . . . . . . . . . . X,Y,C,GX,GY,B

DL06 Range K0-255 K0-3 K0-5; See DL06 V-memory map - Data Words K0-65535; See DL06 V-memory map - Data Words K0-2147434528; See DL06 V-memory map See DL06 V-memory map - Data Words See DL06 V-memory map See DL06 V-memory map

DL06 Micro PLC User Manual, 3rd Edition Rev. A

Page 487

Chapter 5: Intelligent Box (IBox) Instructions

CTRADPT Example Rung 1: This sets up the CTRIO card in slot 2 of the local base. Each CTRIO in the system will need a separate CTRIO I-box before any CTRxxxx I-boxes can be used for them. The CTRIO has been configured to use V2000 through V2025 for its input data, and V2030 through V2061 for its output data.

1 2 3 4 5 6 Rung 2: This rung is a sample method for enabling the CTRADPT command. A C-bit is 7 used to allow the programmer to control the command from Data View for testing purposes. Turning on C0 will cause the CTRADPT instruction to add a new preset to the preset table 8 for output #0 on the CTRIO in slot 2. The new preset will be a command to RESET (entry type K1=reset), pulse time is left at zero as the reset type does not use this, and the count at 9 which it will reset will be 20. Operating procedure for this example code is to load the CTRADPT_ex1.cwb file to your CTRIO, then enter the code shown here, change to RUN mode, enable output #0 by turning 10 on C2 in Data View, turn encoder on CTRIO to value above 10 and output #0 light will come on and stay on for all counts past 10. Now reset the counter with C1, enable C0 to 11 execute CTRADPT command to add a reset for output #0 at a count of 20, turn on C2 to enable output #0, then turn encoder to value of 10+ (output #0 should turn on) and then 12 continue on to count of 20+ (output #0 should turn off ). 13 14 A B C D (example continued on next page)

DL06 Micro PLC User Manual, 3rd Edition Rev. A

5–333

Page 488

Chapter 5: Intelligent Box (IBox) Instructions

CTRADPT Example (cont’d)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

Rung 3: This rung allows the programmer to reset the counter from the ladder logic.

5–334

DL06 Micro PLC User Manual, 3rd Edition Rev. A

Rung 4: This rung allows the operator to enable output #0 from the ladder code.

Page 489

Chapter 5: Intelligent Box (IBox) Instructions

CTRIO Clear Preset Table (CTRCLRT) (IB-1007) DS5

Used

HPP

N/A

CTRIO Clear Preset Table will clear the RAM based Preset Table on a leading edge transition to this IBox. This IBox will take more than 1 PLC scan to execute. Either the Success or Error bit will turn on when the command is complete. If the Error Bit is on, you can use the CTRIO Read Error Code (CTRRDER) IBox to get extended error information. The Workspace register is for internal use by this IBox instruction and MUST NOT be used anywhere else in your program.

1 2 3 4 5 CTRCLRT Parameters 6 • CTRIO#: specifies a specific CTRIO module based on a user defined number (see CTRIO Config) • Output#: specifies a CTRIO output to be used by the instruction 7 • Workspace: specifies a V-memory location that will be used by the instruction • Success: specifies a bit that will turn on once the instruction has successfully completed 8 • Error: specifies a bit that will turn on if the instruction does not complete successfully 9 Parameter DL06 Range 10 11 12 13 14 A B C D CTRIO# . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . K Output# . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . K Workspace . . . . . . . . . . . . . . . . . . . . . . . . . . . . V Success . . . . . . . . . . . . . . . . . . . . X,Y,C,GX,GY,B Error . . . . . . . . . . . . . . . . . . . . . . X,Y,C,GX,GY,B

K0-255 K0-3 See DL06 V-memory map - Data Words See DL06 V-memory map See DL06 V-memory map

DL06 Micro PLC User Manual, 3rd Edition Rev. A

5–335