Page 490
Chapter 5: Intelligent Box (IBox) Instructions
CTRCLRT Example
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
Rung 1: This sets up the CTRIO card in slot 2 of the local base. Each CTRIO in the system will need a separate CTRIO I-box before any CTRxxxx I-boxes can be used for them. The CTRIO has been configured to use V2000 through V2025 for its input data, and V2030 through V2061 for its output data.
5–336
DL06 Micro PLC User Manual, 3rd Edition Rev. A
Rung 2: This rung is a sample method for enabling the CTRCLRT command. A C-bit is used to allow the programmer to control the command from Data View for testing purposes. Turning on C0 will cause the CTRCLRT instruction to clear the preset table for output #0 on the CTRIO in slot 2. Operating procedure for this example code is to load the CTRCLRT_ex1.cwb file to your CTRIO, then enter the code shown here, change to RUN mode, enable output #0 by turning on C2 in Data View, turn encoder on CTRIO to value above 10 and output #0 light will come on and stay on until a count of 20 is reached, where it will turn off. Now reset the counter with C1, enable C0 to execute CTRCLRT command to clear the preset table, turn on C2 to enable output #0, then turn encoder to value of 10+ (output #0 should NOT turn on).
(example continued on next page)
Page 491
Chapter 5: Intelligent Box (IBox) Instructions
CTRCLRT Example (cont’d) Rung 3: This rung allows the programmer to reset the counter from the ladder logic.
Rung 4: This rung allows the operator to enable output #0 from the ladder code.
DL06 Micro PLC User Manual, 3rd Edition Rev. A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 5–337
Page 492
Chapter 5: Intelligent Box (IBox) Instructions
CTRIO Edit Preset Table Entry (CTREDPT) (IB-1003)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
DS5
Used
HPP
N/A
5–338
CTRIO Edit Preset Table Entry, on a leading edge transition to this IBox, will edit a single entry in a Preset Table on a specific CTRIO Output resource. This IBox is good if you are editing more than one entry in a file at a time. If you wish to do just one edit and then reload the table immediately, see the CTRIO Edit and Reload Preset Table Entry (CTREDRL) IBox. This IBox will take more than 1 PLC scan to execute. Either the Success or Error bit will turn on when the command is complete. If the Error Bit is on, you can use the CTRIO Read Error Code (CTRRDER) IBox to get extended error information. Entry Type: K0: Set K1: Reset K2: Pulse On (uses Pulse Time) K3: Pulse Off (uses Pulse Time) K4: Toggle K5: Reset Count Note that the Pulse Time parameter is ignored by some Entry Types. The Workspace register is for internal use by this IBox instruction and MUST NOT be used anywhere else in your program. CTREDPT Parameters • CTRIO#: specifies a specific CTRIO module based on a user defined number (see CTRIO Config Ibox) • Output#: specifies a CTRIO output to be used by the instruction • Table#: specifies the Table number of which an Entry is to be edited • Entry#: specifies the Entry location in the Preset Table to be edited • Entry Type: specifies the Entry Type to add during the edit • Pulse Time: specifies a pulse time for the Pulse On and Pulse Off Entry Types • Preset Count: specifies an initial count value to begin at after Reset • Workspace: specifies a V-memory location that will be used by the instruction • Success: specifies a bit that will turn on once the instruction has successfully completed • Error: specifies a bit that will turn on if the instruction does not complete successfully
DL06 Micro PLC User Manual, 3rd Edition Rev. A
Page 493
Chapter 5: Intelligent Box (IBox) Instructions
Parameter
DL06 Range
CTRIO# . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . K Output# . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . K Table# . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V,K Entry# . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V,K Entry Type . . . . . . . . . . . . . . . . . . . . . . . . . . . V,K Pulse Time . . . . . . . . . . . . . . . . . . . . . . . . . . V,K Preset Count . . . . . . . . . . . . . . . . . . . . . . . . . V,K Workspace . . . . . . . . . . . . . . . . . . . . . . . . . . . . V Success . . . . . . . . . . . . . . . . . . . . X,Y,C,GX,GY,B Error . . . . . . . . . . . . . . . . . . . . . . X,Y,C,GX,GY,B
K0-255 K0-3 K0-255; See DL06 V-memory map - Data Words K0-255; See DL06 V-memory map - Data Words K0-5; See DL06 V-memory map - Data Words K0-65535; See DL06 V-memory map - Data Words K0-2147434528; See DL06 V-memory map See DL06 V-memory map - Data Words See DL06 V-memory map See DL06 V-memory map
CTREDPT Example Rung 1: This sets up the CTRIO card in slot 2 of the local base. Each CTRIO in the system will need a separate CTRIO I-box before any CTRxxxx I-boxes can be used for them. The CTRIO has been configured to use V2000 through V2025 for its input data, and V2030 through V2061 for its output data.
(example continued on next page)
DL06 Micro PLC User Manual, 3rd Edition Rev. A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
5–339
Page 494
Chapter 5: Intelligent Box (IBox) Instructions
CTREDPT Example (cont’d)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
Rung 2: This rung is a sample method for enabling the CTREDPT command. A C-bit is used to allow the programmer to control the command from Data View for testing purposes. Turning on C0 will cause the CTREDPT instruction to change the second preset from a reset at a count of 20 to a reset at a count of 30 for output #0 on the CTRIO in slot 2. Operating procedure for this example code is to load the CTREDPT_ex1.cwb file to your CTRIO, then enter the code shown here, change to RUN mode, enable output #0 by turning on C2 in Data View, turn encoder on CTRIO to value above 10 and output #0 light will come on and stay on until a count of 20 is reached, where it will turn off. Now reset the counter with C1, enable C0 to execute CTREDPT command to change the second preset, turn on C2 to enable output #0, then turn encoder to value of 10+ (output #0 should turn on) and then continue past a count of 30 (output #0 should turn off ). Note that we must also reload the profile after changing the preset(s), this is why the CTRLDPR command follows the CTREDPT command in this example.
5–340
DL06 Micro PLC User Manual, 3rd Edition Rev. A
(example continued on next page)
Page 495
Chapter 5: Intelligent Box (IBox) Instructions
CTREDPT Example (cont’d) Rung 3: This rung allows the programmer to reset the counter from the ladder logic.
Rung 4: This rung allows the operator to enable output #0 from the ladder code.
DL06 Micro PLC User Manual, 3rd Edition Rev. A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 5–341
Page 496
Chapter 5: Intelligent Box (IBox) Instructions
CTRIO Edit Preset Table Entry and Reload (CTREDRL) (IB-1002)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
DS5
Used
HPP
N/A
5–342
CTRIO Edit Preset Table Entry and Reload, on a leading edge transition to this IBox, will perform this dual operation to a CTRIO Output resource in one CTRIO command. This IBox will take more than 1 PLC scan to execute. Either the Success or Error bit will turn on when the command is complete. If the Error Bit is on, you can use the CTRIO Read Error Code (CTRRDER) IBox to get extended error information. Entry Type: K0: Set K1: Reset K2: Pulse On (uses Pulse Time) K3: Pulse Off (uses Pulse Time) K4: Toggle K5: Reset Count Note that the Pulse Time parameter is ignored by some Entry Types. The Workspace register is for internal use by this IBox instruction and MUST NOT be used anywhere else in your program. CTREDRL Parameters • CTRIO#: specifies a specific CTRIO module based on a user defined number (see CTRIO Config Ibox) • Output#: specifies a CTRIO output to be used by the instruction • Table#: specifies the Table number of which an Entry is to be edited • Entry#: specifies the Entry location in the Preset Table to be edited • Entry Type: specifies the Entry Type to add during the edit • Pulse Time: specifies a pulse time for the Pulse On and Pulse Off Entry Types • Preset Count: specifies an initial count value to begin at after Reset • Workspace: specifies a V-memory location that will be used by the instruction • Success: specifies a bit that will turn on once the instruction has successfully completed • Error: specifies a bit that will turn on if the instruction does not complete successfully
DL06 Micro PLC User Manual, 3rd Edition Rev. A
Page 497
Chapter 5: Intelligent Box (IBox) Instructions
Parameter
DL06 Range
CTRIO# . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . K Output# . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . K Table# . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V,K Entry# . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V,K Entry Type . . . . . . . . . . . . . . . . . . . . . . . . . . . V,K Pulse Time . . . . . . . . . . . . . . . . . . . . . . . . . . V,K Preset Count . . . . . . . . . . . . . . . . . . . . . . . . . V,K Workspace . . . . . . . . . . . . . . . . . . . . . . . . . . . . V Success . . . . . . . . . . . . . . . . . . . . X,Y,C,GX,GY,B Error . . . . . . . . . . . . . . . . . . . . . . X,Y,C,GX,GY,B
K0-255 K0-3 K0-255; See DL06 V-memory map - Data Words K0-255; See DL06 V-memory map - Data Words K0-5; See DL06 V-memory map - Data Words K0-65535; See DL06 V-memory map - Data Words K0-2147434528; See DL06 V-memory map See DL06 V-memory map - Data Words See DL06 V-memory map See DL06 V-memory map
CTREDRL Example Rung 1: This sets up the CTRIO card in slot 2 of the local base. Each CTRIO in the system will need a separate CTRIO I-box before any CTRxxxx I-boxes can be used for them. The CTRIO has been configured to use V2000 through V2025 for its input data, and V2030 through V2061 for its output data.
(example continued on next page)
DL06 Micro PLC User Manual, 3rd Edition Rev. A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
5–343
Page 498
Chapter 5: Intelligent Box (IBox) Instructions
CTREDRL Example (cont’d)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
Rung 2: This rung is a sample method for enabling the CTREDRL command. A C-bit is used to allow the programmer to control the command from Data View for testing purposes. Turning on C0 will cause the CTREDRL instruction to change the second preset in file 1 from a reset at a value of 20 to a reset at a value of 30. Operating procedure for this example code is to load the CTREDRL_ex1.cwb file to your CTRIO, then enter the code shown here, change to RUN mode, enable output #0 by turning on C2 in Data View, turn encoder on CTRIO to value above 10 and output #0 light will come on, continue to a count above 20 and the output #0 light will turn off. Now reset the counter with C1, enable C0 to execute CTREDRL command to change the second preset count value to 30, then turn encoder to value of 10+ (output #0 should turn on) and continue on to a value of 30+ and the output #0 light will turn off. Note that it is not necessary to reload this file separately, however, the command can only change one value at a time.
5–344
DL06 Micro PLC User Manual, 3rd Edition Rev. A
(example continued on next page)
Page 499
Chapter 5: Intelligent Box (IBox) Instructions
CTREDRL Example (cont’d) Rung 3: This rung allows the programmer to reset the counter from the ladder logic.
Rung 4: This rung allows the operator to enable output #0 from the ladder code.
DL06 Micro PLC User Manual, 3rd Edition Rev. A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 5–345