Page 40
Chapter 1: Getting Started
Q. Which devices can I connect to the communication ports of the DL06? A. Port 1: The port is RS-232C, fixed at 9600 baud, odd parity, address 1,and uses the proprietary K-sequence protocol. The DL06 can also connect to MODBUS RTU and DirectNET networks as a slave device through port 1. The port communicates with the following devices:
1 2 • DV-1000 Data Access Unit, C-more, DirectTouch, LookoutDirect, DSData or Optimation Operator interface panels 3 • DirectSOFT 5 (running on a personal computer) • D2-HPP handheld programmer 4 • Other devices which communicate via K-sequence, Directnet, MODBUS RTU protocols should work with the DL06 Micro PLC. Contact the vendor for details. 5 A. Port 2: This is a multi-function port. It supports RS-232C, RS422, or RS485, with selective baud rates (300-38,400bps), address and parity. It also supports the proprietary K6 sequence protocol as well as DirectNet and MODBUS RTU, ASCII In/Out and nonsequence/print protocols. 7 Q. Can the DL06 accept 5VDC inputs? A. No, 5 volts is lower than the DC input ON threshold. However, many TTL logic circuits can drive the inputs if they are wired as open collector (sinking) inputs. See Chapter 2 for I/O 8 wiring guidelines. 9 10 11 12 13 14 A B C D DL06 Micro PLC User Manual, 3rd Edition Rev. A
1–13
Page 41
INSTALLATION, WIRING, AND SPECIFICATIONS
CHAPTER
2
In This Chapter... Safety Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2–2 Orientation to DL06 Front Panel . . . . . . . . . . . . . . . . . . . . . . . . . . .2–5 Mounting Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2–7 Wiring Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2–11 System Wiring Strategies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2–14 Wiring Diagrams and Specifications . . . . . . . . . . . . . . . . . . . . . . . .2–26 Glossary of Specification Terms . . . . . . . . . . . . . . . . . . . . . . . . . . .2–44
Page 42
Chapter 2: Installation, Wiring, and Specifications
Safety Guidelines
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 2–2
NOTE: Products with CE marks perform their required functions safely and adhere to relevant standards as specified by CE directives provided they are used according to their intended purpose and that the instructions in this manual are adhered to. The protection provided by the equipment may be impaired if this equipment is used in a manner not specified in this manual. A listing of our international affiliates is available on our Web site: http://www.automationdirect.com WARNING: Providing a safe operating environment for personnel and equipment is your responsibility and should be your primary goal during system planning and installation. Automation systems can fail and may result in situations that can cause serious injury to personnel and/or damage equipment. Do not rely on the automation system alone to provide a safe operating environment. Sufficient emergency circuits should be provided to stop either partially or totally the operation of the PLC or the controlled machine or process. These circuits should be routed outside the PLC in the event of controller failure, so that independent and rapid shutdown are available. Devices, such as “mushroom” switches or end of travel limit switches, should operate motor starter, solenoids, or other devices without being processed by the PLC. These emergency circuits should be designed using simple logic with a minimum number of highly reliable electromechanical compnents. Every automation application is different, so there may be special requirements for your particular application. Make sure all national, state, and local government requirements are followed for the proper installation and use of your equipment.
Plan for Safety The best way to provide a safe operating environment is to make personnel and equipment safety part of the planning process. You should examine every aspect of the system to determine which areas are critical to operator or machine safety. If you are not familiar with PLC system installation practices, or your company does not have established installation guidelines, you should obtain additional information from the following sources. • NEMA, The National Electrical Manufacturers Association, located in Washington, D.C., publishes many different documents that discuss standards for industrial control systems. You can order these publications directly from NEMA. Some of these include: ICS 1, General Standards for Industrial Control and Systems ICS 3, Industrial Systems ICS 6, Enclosures for Industrial Control Systems • NEC, The National Electrical Code provides regulations concerning the installation and use of various types of electrical equipment. Copies of the NEC Handbook can often be obtained from your local electrical equipment distributor or your local library. • Local and State Agencies, many local governments and state governments have additional requirements above and beyond those described in the NEC Handbook. Check with your local Electrical Inspector or Fire Marshall office for information.
DL06 Micro PLC User Manual, 3rd Edition Rev. A
Page 43
Chapter 2: Installation, Wiring, and Specifications
Three Levels of Protection The publications mentioned provide many ideas and requirements for system safety. At a minimum, you should follow these regulations. Also, you should use the following techniques, which provide three levels of system control. • Emergency stop switch for disconnecting system power • Mechanical disconnect for output module power • Orderly system shutdown sequence in the PLC control program
Emergency Stops It is recommended that emergency stop circuits be incorporated into the system for every machine controlled by a PLC. For maximum safety in a PLC system, these circuits must not be wired into the controller, but should be hardwired external to the PLC. The emergency stop switches should be easily accessed by the operator and are generally wired into a master control relay (MCR) or a safety control relay (SCR) that will remove power from the PLC I/O system in an emergency. MCRs and SCRs provide a convenient means for removing power from the I/O system during an emergency situation. By de-energizing an MCR (or SCR) coil, power to the input (optional) and output devices is removed. This event occurs when any emergency stop switch opens. However, the PLC continues to receive power and operate even though all its inputs and outputs are disabled. The MCR circuit could be extended by placing a PLC fault relay (closed during normal PLC operation) in series with any other emergency stop conditions. This would cause the MCR circuit to drop the PLC I/O power in case of a PLC failure (memory error, I/O communications error, etc.). HOT
NEUTRAL
Use E-Stop and Master Relay Power On
E STOP
Master Control Relay
Guard Link
MCR L1 to Output Supply Guard?Line Switch
Saw Arbor
Emergency Stop
G LG 0V Y0 Y2 C1 Y5 Y7 Y10 Y12 C3 Y15 Y17 AC(L) AC(N) 24V C0 Y1 Y3 Y4 Y6 C2 Y11 Y13 Y14 Y16 N.C. OUTPUT: 6-240V
Y X
0
1
2
50 - 60Hz 3
INPUT: 12 - 24V
4
5
2.0A, 6 - 27V 6
7
10
2.0A 11
12
PWR: 100-240V 13
14
15
16
PWR RUN CPU TX1 RX1 TX2 RX2
50-60Hz 40VA 17
20
D0-06DR
21 22
23
3 - 15mA
LOGIC C0
06
K oyo
X1 X0
X3 X2
X4 C1
X6 X5
X7
C2 X11 X13 X14 X16 C4 X21 X23 N.C. X10 X12 C3 X15 X17 X20 X22 N.C.
TERM PORT1
PORT2
RUN STOP
MCR L1 to Input Supply (optional)
DL06 Micro PLC User Manual, 3rd Edition Rev. A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
2–3
Page 44
Chapter 2: Installation, Wiring, and Specifications
Emergency Power Disconnect
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 2–4
A properly rated emergency power disconnect should be used to power the PLC controlled system as a means of removing the power from the entire control system. It may be necessary to install a capacitor across the disconnect to protect against a condition known as “outrush”. This condition occurs when the output Triacs are turned off by powering off the disconnect, thus causing the energy stored in the inductive loads to seek the shortest distance to ground, which is often through the Triacs. After an emergency shutdown or any other type of power interruption, there may be requirements that must be met before the PLC control program can be restarted. For example, there may be specific register values that must be established (or maintained from the state prior to the shutdown) before operations can resume. In this case, you may want to use retentive memory locations, or include constants in the control program to insure a known starting point.
Orderly System Shutdown Ideally, the first level of fault detection is the PLC control program, which can identify machine problems. Certain shutdown sequences should be performed. The types of problems are usually things such as jammed parts, etc. that do not pose a risk of personal injury or equipment damage. WARNING: The control program must not be the only form of protection for any problems that may result in a risk of personal injury or equipment damage.
Jam Detect
Turn off Saw RST RST Retract
Class 1, Division 2 Approval This equipment is suitable for use in Class 1, Division 2, groups A, B, C and D or nonhazardous locations only. WARNING: Explosion Hazard! Substitution of components may impair suitability for Class 1, Division 2. Do not disconnect equipment unless power has been switched off or area is known to be nonhazardous.
DL06 Micro PLC User Manual, 3rd Edition Rev. A
Page 45
Chapter 2: Installation, Wiring, and Specifications
Orientation to DL06 Front Panel Most connections, indicators, and labels on the DL06 Micro PLCs are located on its front panel. The communication ports are located on front of the PLC as are the option card slots and the mode selector switch. Please refer to the drawing below. The output and power connector accepts external power and logic and chassis ground connections on the indicated terminals. The remaining terminals are for connecting commons and output connections Y0 through Y17. The sixteen output terminals are numbered in octal, Y0-Y7 and Y10-Y17. On DC output units, the end terminal on the right accepts power for the output stage. The input side connector provides the location for connecting the inputs X0 and X23 and the associated commons. Power Inputs Mounting Tab
Discrete Outputs
Output Status Indicators
Output Circuit Power Input (for DC output versions only)
Status Indicators
G LG Y0 Y2 C1 Y5 Y7 Y10 Y12 C3 Y15 Y17 0V AC(L) AC(N) 24V C0 Y1 Y3 Y4 Y6 C2 Y11 Y13 Y14 Y16 N.C. OUTPUT: 6-240V
Y X
0
1
2
50 - 60Hz 3
INPUT: 12 - 24V
4
5
2.0A, 6 - 27V 6
7
10
2.0A 11
12
PWR: 100-240V 13
14
15
16
17
20
21
D0-06DR
22
23
Communication Ports
3 - 15mA
LOGIC C0
06
K oyo
X1 X0
PWR RUN CPU TX1 RX1 TX2 RX2
50-60Hz 40VA
X3 X2
X4 C1
X6 X5
X7
C2 X11 X13 X14 X16 C4 X21 X23 N.C. X15 X17 X20 X22 N.C. X10 X12 C3
TERM PORT1
Discrete Inputs
Input Status Indicators
Option Slots
PORT2
RUN STOP
Mode Switch Mounting Tab
WARNING: For some applications, field device power may still be present on the terminal block even though the Micro PLC is turned off. To minimize the risk of electrical shock, check all field device power before you expose or remove either connector
DL06 Micro PLC User Manual, 3rd Edition Rev. A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
2–5
Page 46
Chapter 2: Installation, Wiring, and Specifications
Terminal Block Removal
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 2–6
The DL06 terminals are divided into two groups. Each group has its own terminal block. The outputs and power wiring are on one block, and the input wiring is on the other. In some instances, it may be desirable to remove the terminal block for easy wiring. The terminal block is designed for easy removal with just a small screwdriver. The drawing below shows the procedure for removing one of the terminal blocks. 1. Loosen the retention screws on each end of the connector block.
2. From the center of the connector block, pry upward with the screwdriver until the connector is loose. The terminal blocks on DL06 PLCs have regular (m3 size) screw terminals, which will accept either standard blade-type or #1 Philips screwdriver tips. Use No. 16 to 22 AWG solid/stranded wire. Be careful not to over-tighten; maximum torque is 0.882 to 1.020 Nm (7.806 to 9.028 inch-lbs). Spare terminal blocks are available in an accessory kit. Please refer to part number D0-ACC-2. You can find this and other accessories on our web site.
DL06 Micro PLC User Manual, 3rd Edition Rev. A
Page 47
Chapter 2: Installation, Wiring, and Specifications
Mounting Guidelines In addition to the panel layout guidelines, other specifications can affect the installation of a PLC system. Always consider the following: • Environmental Specifications • Power Requirements • Agency Approvals • Enclosure Selection and Component Dimensions
Unit Dimensions The following diagram shows the outside dimensions and mounting hole locations for all versions of the DL06. Make sure you follow the installation guidelines to allow proper spacing from other components.
0.71" 18mm
1.46" 37mm
Enclosures Your selection of a proper enclosure is important to ensure safe and proper operation of your DL06 system. Applications of DL06 systems vary and may require additional features. The minimum considerations for enclosures include: • Conformance to electrical standards • Protection from the elements in an industrial environment • Common ground reference • Maintenance of specified ambient temperature • Access to equipment • Security or restricted access • Sufficient space for proper installation and maintenance of equipment
DL06 Micro PLC User Manual, 3rd Edition Rev. A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
2–7
Page 48
Chapter 2: Installation, Wiring, and Specifications
Panel Layout & Clearances
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 2–8
There are many things to consider when designing the panel layout. The following items correspond to the diagram shown. Note: there may be additional requirements, depending on your application and use of other components in the cabinet. 1. Mount the PLCs horizontally as shown below to provide proper ventilation. You cannot mount the DL06 units vertically, upside down, or on a flat horizontal surface. If you place more than one unit in a cabinet, there must be a minimum of 7.2” (183 mm) between the units. 2. Provide a minimum clearance of 1.5” (39 mm) between the unit and all sides of the cabinet. Remember to allow for any operator panels or other items mounted in the door. 3. There should also be at least 3” (78 mm) of clearance between the unit and any wiring ducts that run parallel to the terminals. 4. The ground terminal on the DL06 base must be connected to a single point ground. Use copper NOTE: There is a minimum clearance requirement of 1.5” (38 mm) between the panel door (or any devices mounted in the panel door) and the nearest DL06 component.
Temperature Probe
Ground braid copper lugs Panel
Star Washers
Star Washers
Panel or single point ground
1.5" 38mm min
Power Source stranded wire to achieve a low impedance. Copper eye lugs should be crimped and soldered to the ends of the stranded wire to ensure good surface contact.
1.5" 38mm min
Pan el G roun d Te rmin al
Eart 5. There must be a single point ground h Gr oun d (i.e., copper bus bar) for all devices in the panel requiring an earth ground return. The single point of ground must be connected to the panel ground termination. The panel ground termination must be connected to earth ground. Minimum wire sizes, color coding, and general safety practices should comply with appropriate electrical codes and standards for your area.
DL06 Micro PLC User Manual, 3rd Edition, Rev. A
1.5" 38mm min
Page 49
Chapter 2: Installation, Wiring, and Specifications 6. A good common ground reference (Earth ground) is essential for proper operation of the DL06. One side of all control and power circuits and the ground lead on flexible shielded cable must be properly connected to Earth ground. There are several methods of providing an adequate common ground reference, including: a) Installing a ground rod as close to the panel as possible. b) Connection to incoming power system ground.
1 2 7. Evaluate any installations where the ambient temperature may approach the lower or upper limits of the specifications. If you suspect the ambient temperature will not be within the operating 3 specification for the DL06 system, measures such as installing a cooling/heating source must be taken to get the ambient temperature within the range of specifications. 4 8. The DL06 systems are designed to be powered by 95-240 VAC or 12–24 VDC normally available throughout an industrial environment. Electrical power in some areas where the PLCs are installed is not always stable and storms can cause power surges. Due to this, powerline filters are recommended 5 for protecting the DL06 PLCs from power surges and EMI/RFI noise. The Automation Powerline Filter, for use with 120 VAC and 240 VAC, 1–5 Amps, is an excellent choice (locate at 6 www.automationdirect.com), however, you can use a filter of your choice. These units install easily between the power source and the PLC. 7 NOTE: If you are using other components in your system, make sure you refer to the appropriate manual to determine how those units can affect mounting dimensions. 8 Using Mounting Rails DL06 Micro PLCs can be secured to a panel by using mounting rails. We recommend rails 9 that conform to DIN EN standard 50 022. They are approximately 35mm high, with a depth of 7mm. If you mount the Micro PLC on a rail, do consider using end brackets on each side 10 of the PLC. The end bracket helps keep the PLC from sliding horizontally along the rail, reducing the possibility of accidentally pulling the wiring loose. On the bottom of the PLC are two small retaining clips. To secure the PLC to a DIN rail, place it onto the rail and gently 11 push up on the clips to lock it onto the rail. To remove the PLC, pull down on the retaining clips, lift up on the PLC slightly, then pull it away from the rail. 12 13 14 A B C D NOTE: Refer to our catalog or web site for a complete listing of DINnector connection systems. DIN Rail Dimensions
DIN rail slot is designed for 35mm X 7mm rail conforming to DIN EN 50022
7mm
35mm
Retaining Clip
DL06 Micro PLC User Manual, 3rd Edition Rev. A
2–9