The text of a manual · part 6 of 53
DL06 Micro PLC User Manual, Volume 1 of 2, pages 50 to 59
Pages 50 to 59 of 524
The original document is the PDF (6.4 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the AutomationDirect Direct Logic DL06 and Koyo DL06 D0-06DD1
Page 50
Chapter 2: Installation, Wiring, and Specifications
Environmental Specifications
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
The following table lists the environmental specifications that generally apply to DL06 Micro PLCs. The ranges that vary for the Handheld Programmer are noted at the bottom of this chart. Certain output circuit types may have derating curves, depending on the ambient temperature and the number of outputs ON. Please refer to the appropriate section in this chapter pertaining to your particular DL06 PLC. Environmental Specifications Specification
Rating
Storage temperature Ambient operating temperature* Ambient humidity** Vibration resistance Shock resistance Noise immunity Atmosphere Agency approvals
–4° F to 158° F (–20° C to 70° C) 32° F to 131° F (0° C to 55° C) 5% – 95% relative humidity (non–condensing) MIL STD 810C, Method 514.2 MIL STD 810C, Method 516.2 NEMA (ICS3–304) No corrosive gases UL, CE (C1D2), FCC class A
* Operating temperature for the Handheld Programmer and the DV–1000 is 32° to 122° F (0° to 50° C) Storage temperature for the Handheld Programmer and the DV–1000 is –4° to 158° F (–20° to 70° C). **Equipment will operate down to 5% relative humidity. However, static electricity problems occur much more frequently at low humidity levels (below 30%). Make sure you take adequate precautions when you touch the equipment. Consider using ground straps, anti-static floor coverings, etc. if you use the equipment in low-humidity environments.
2–10
Agency Approvals Some applications require agency approvals for particular components. The DL06 Micro PLC agency approvals are listed below: • UL (Underwriters’ Laboratories, Inc.) • CUL (Canadian Underwriters’ Laboratories, Inc.) • CE (European Economic Union)
Marine Use American Bureau of Shipping (ABS) certification requires flame-retarding insulation as per 4-8-3/5.3.6(a). ABS will accept Navy low smoke cables, cable qualified to NEC “Plenum rated” (fire resistant level 4), or other similar flammability resistant rated cables. Use cable specifications for your system that meet a recognized flame retardant standard (i.e. UL, IEEE, etc.), including evidence of cable test certification (i.e. tests certificate, UL file number, etc.). NOTE: Wiring needs to be “low smoke” per the above paragraph. Teflon coated wire is also recommended.
DL06 Micro PLC User Manual, 3rd Edition Rev. A
Page 51
Chapter 2: Installation, Wiring, and Specifications
Wiring Guidelines
1 2 3 4 5 6 7 8 9 WARNING: Once the power wiring is connected, secure the terminal block cover in the closed position. When the cover is open there is a risk of electrical shock if you accidentally touch the connection terminals or power wiring. 10 Fuse Protection for Input Power 11 There are no internal fuses for the input power circuits, so external circuit protection is needed to ensure the safety of service personnel and the safe operation of the equipment itself. 12 To meet UL/CUL specifications, the input power must be fused. Depending on the type of input power being used, follow these fuse protection recommendations: 13 208/240 VAC Operation When operating the unit from 208/240 VAC, whether the voltage source is a step-down transformer or from two phases, fuse both the line (L) and neutral (N) leads. The 14 recommended fuse size is 1.0A (fast blow). 110/125 VAC Operation A When operating the unit from 110/125 VAC, it is only necessary to fuse the line (L) lead; it is not necessary to fuse the neutral (N) lead. The recommended fuse size is 1.0A (fast blow). B C D Connect the power input wiring for the DL06. Observe all precautions stated earlier in this manual. When the wiring is complete, close the connector covers. Do not apply power at this time. 12 - 24 VDC
-
Fuse fuse
0V G LG Y0 Y2 C1 Y5 Y7 Y AC(L) AC(N) 24V C0 Y1 Y3 Y4 Y6 C2
OUTPUT: 17-240V
Y
X
0
1
2
INPUT: 90 - 120V
50 - 60Hz
3
4
5
7 - 15mA
0.5A 6
PWR: 100-240V
7
10
11
12
13
50-60
14
1
12/24 VDC Power Input
Fuse
+
110/220 VAC Power Input
G
LG
+
-
6 - 27V
OUTPUT: Sinking Output
Y
X
0
1
2
INPUT: 12 - 24V
3
N.C. Y0 Y2 C1 Y5 Y7 Y10 N.C. C0 Y1 Y3 Y4 Y6 C2 Y
4
5
1.0A
6
7
PWR: 12-24
10
11
12
13
20W
14
15
3 - 15mA
DL06 Micro PLC User Manual, 3rd Edition Rev. A
2–11
Page 52
Chapter 2: Installation, Wiring, and Specifications
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 2–12
12/24 VDC Operation When operating at these lower DC voltages, wire gauge size is just as important as proper fusing techniques. Using large conductors minimizes the voltage drop in the conductor. Each DL06 input power terminal can accommodate one 16 AWG wire or two 18 AWG wires. A DC failure can maintain an arc for much longer time and distance than AC failures. Typically, the main bus is fused at a higher level than the branch device, which in this case is the DL06. The recommended fuse size for the branch circuit to the DL06 is 1.5A, such as AutomationDirect’s AGC 1-5 fast-acting fuse.
External Power Source The power source must be capable of suppling voltage and current complying with individual Micro PLC specifications, according to the following specifications: Power Source Specifications Item Input Voltage Range Maximum Inrush Current Maximum Power Voltage Withstand (dielectric) Insulation Resistance
DL06 VAC Powered Units
DL06 VDC Powered Units
110/220 VAC (95–240 VAC) 12–24 VDC (10.8–26.4 VDC) 13 A, 1ms (95–240 VAC) 10A 15 A, 1ms (240–264 VAC) 30 VA 20 W 1 minute @ 1500 VAC between primary, secondary, field ground > 10 at 500 VDC
NOTE: The rating between all internal circuits is BASIC INSULATION ONLY.
Planning the Wiring Routes The following guidelines provide general information on how to wire the I/O connections to DL06 Micro PLCs. For specific information on wiring a particular PLC refer to the corresponding specification sheet which appears later in this chapter. 1. Each terminal connection of the DL06 PLC can accept one 16 AWG wire or two 18 AWG size wires. Do not exceed this recommended capacity. NOTE: Recommended wire size for field devices is 16 - 22 AWG solid/stranded. Tighten terminal screws to 7.81 lb-in (0.882 N*m) to 9.03 lb-in (1.02 N*m). 2. Always use a continuous length of wire. Do not splice wires to attain a needed length. 3. Use the shortest possible wire length. 4. Use wire trays for routing where possible. 5. Avoid running wires near high energy wiring. 6. Avoid running input wiring close to output wiring where possible. 7. To minimize voltage drops when wires must run a long distance, consider using multiple wires for the return line. 8. Avoid running DC wiring in close proximity to AC wiring where possible. 9. Avoid creating sharp bends in the wires. 10. Install the recommended powerline filter to reduce power surges and EMI/RFI noise.
DL06 Micro PLC User Manual, 3rd Edition Rev. A
Page 53
Chapter 2: Installation, Wiring, and Specifications
Fuse Protection for Input and Output Circuits Input and Output circuits on DL06 Micro PLCs do not have internal fuses. In order to protect your Micro PLC, we suggest you add external fuses to your I/O wiring. A fast-blow fuse, with a lower current rating than the I/O bank’s common current rating can be wired to each common. Or, a fuse with a rating of slightly less than the maximum current per output point can be added to each output. Refer to the Micro PLC specification sheets further in this chapter to find the maximum current per output point or per output common. Adding the external fuse does not guarantee the prevention of Micro PLC damage, but it will provide added protection.
LG Y0 Y2 C1 Y5 Y7 Y10 Y12 C3 Y15 Y17 G 0V AC(L) AC(N) 24V C0 Y1 Y3 Y4 Y6 C2 Y11 Y13 Y14 Y16 N.C. OUTPUT: 6-240V
Y X
0
1
2
50 - 60Hz 3
INPUT: 12 - 24V
4
5
2.0A, 6 - 27V 6
7
10
2.0A 11
12
PWR: 100-240V 13
14
15
16
PWR RUN CPU TX1 RX1 TX2 RX2
50-60Hz 40VA 17
20
D0-06DR
21 22
23
3 - 15mA
LOGIC C0
06
K oyo
X1 X0
X3 X2
X4 C1
X6 X5
X7
C2 X11 X13 X14 X16 C4 X21 X23 N.C. X15 X17 X20 X22 N.C. X10 X12 C3
TERM PORT1
PORT2
RUN STOP
I/O Point Numbering All DL06 Micro PLCs have a fixed I/O configuration. It follows the same octal numbering system used on other DirectLogic family PLCs, starting at X0 and Y0. The letter X is always used to indicate inputs and the letter Y is always used for outputs. The I/O numbering always starts at zero and does not include the digits 8 or 9. The addresses are typically assigned in groups of 8 or 16, depending on the number of points in an I/O group. For the DL06 the twenty inputs use reference numbers X0 – X23. The sixteen output points use references Y0 – Y17. Additional I/O modules can be installed in the four option slots. See the DL05/06 Option Modules User Manual, D0-OPTIONS-M, for a complete selection of modules and how to addresss them in the DL06. This manual can either be ordered from Automatindirect or downloaded from our website.
DL06 Micro PLC User Manual, 3rd Edition Rev. A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
2–13
Page 54
Chapter 2: Installation, Wiring, and Specifications
System Wiring Strategies
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
The DL06 Micro PLC is very flexible and will work in many different wiring configurations. By studying this section before actual installation, you can probably find the best wiring strategy for your application. This will help to lower system cost, wiring errors, and avoid safety problems.
PLC Isolation Boundaries PLC circuitry is divided into three main regions separated by isolation boundaries, shown in the drawing below. Electrical isolation provides safety, so that a fault in one area does not damage another. A powerline filter will provide isolation between the power source and the power supply. A transformer in the power supply provides magnetic isolation between the primary and secondary sides. Opto-couplers provide optical isolation in Input and Output circuits. This isolates logic circuitry from the field side, where factory machinery connects. Note that the discrete inputs are isolated from the discrete outputs, because each is isolated from the logic side. Isolation boundaries protect the operator interface (and the operator) from power input faults or field wiring faults. When wiring a PLC, it is extremely important to avoid making external connections that connect logic side circuits to any other. Power Input
16 Discrete Outputs
Output circuit
Power Supply
CPU
4 Optional card slots
Isolation boundary
Input circuit
20 discrete Inputs
2 comm. ports
To programming device or Operator interface
The next figure shows the internal layout of DL06 PLCs, as viewed from the front panel. Power Input
Filter 16 Discrete Outputs Commons
Output Circuit Main Power Supply
CPU
DL06 PLC
Input Circuit
20 Discrete Inputs
2–14
LCD monitor
Commons
DL06 Micro PLC User Manual, 3rd Edition Rev. A
Optional Card Slots LCD Monitor 2 Comm. Ports
To Programming Device, Operator Interface or networking
Page 55
Chapter 2: Installation, Wiring, and Specifications
Connecting Operator Interface Devices Operator interfaces require data and power connections. Some operator interfaces usually require separate AC power. However, other operator interface devices like the popular DV1000 Data Access Unit may be powered directly from the DL06 Micro PLC. Connect the DV-1000 to communication port 1 on the DL06 Micro PLC using the cable shown below. A single cable contains transmit/receive data wires and +5V power. DL06 Micro PLC
0V LG Y0 Y2 C1 Y5 Y7 Y10 Y12 C3 Y15 Y17 G AC(L) AC(N) 24V C0 Y1 Y3 Y4 Y6 C2 Y11 Y13 Y14 Y16 N.C. OUTPUT: 6-240V
Y
0
X
1
50 - 60Hz
2
3
INPUT: 12 - 24V
4
2.0A, 6 - 27V
5
6
7
10
2.0A 11
12
PWR: 100-240V 13
14
15
PWR RUN CPU TX1 RX1 TX2 RX2
50-60Hz 40VA
16
17
D0-06DR
20
21 22
23
3 - 15mA
RJ12 phone style
DV-1000
06
LOGIC C0
RJ12 phone style
K oyo
X1 X0
X3 X2
X4 C1
X6 X5
X7
C2 X11 X13 X14 X16 C4 X21 X23 N.C. X15 X17 X20 X22 N.C. X10 X12 C3
Use cable part no. DV–1000CBL
TERM PORT1
PORT2
RUN STOP
C-more operator interface touch panels uses a provided 24 VDC plug-in power supply. Connect the DL06 to the serial connector on the rear of the C-more panel using the cable shown below. DL06 Micro PLC
G LG 0V Y0 Y2 C1 Y5 Y7 Y10 Y12 C3 Y15 Y17 AC(L) AC(N) 24V C0 Y1 Y3 Y4 Y6 C2 Y11 Y13 Y14 Y16 N.C. OUTPUT: 6-240V
Y X
0
1
50 - 60Hz
2
3
INPUT: 12 - 24V
4
2.0A, 6 - 27V
5
6
7
10
2.0A 11
12
PWR: 100-240V 13
14
15
16
PWR RUN CPU TX1 RX1 TX2 RX2
50-60Hz 40VA 17
20
21
D0-06DR
22
23
3 - 15mA
15-pin D-shell male
06
LOGIC C0
15-pin VGA male
K oyo
X1 X0
X3 X2
X4 C1
X6 X5
X7
C2 X11 X13 X14 X16 C4 X21 X23 N.C. X15 X17 X20 X22 N.C. X10 X12 C3
Use cable part no. EA-2CBL-1
TERM PORT1
PORT2
RUN STOP
Connecting Programming Devices DL06 Micro PLCs can be programmed with either a handheld programmer or with DirectSOFT 5 on a PC. Connect the DL06 to a PC using the cable shown below. DL06 Micro PLC RJ12 phone style 0V LG Y0 Y2 C1 Y5 Y7 Y10 Y12 C3 Y15 Y17 G AC(L) AC(N) 24V C0 Y1 Y3 Y4 Y6 C2 Y11 Y13 Y14 Y16 N.C. OUTPUT: 6-240V
Y
X
0
1
50 - 60Hz
2
3
INPUT: 12 - 24V
4
5
2.0A, 6 - 27V 6
7
10
2.0A 11
12
PWR: 100-240V 13
14
15
16
50-60Hz 40VA 17
20
D0-06DR
21 22
23
3 - 15mA
LOGIC C0
06
Use cable part no. D2–DSCBL
K oyo
X1 X0
X3 X2
X4 C1
X6 X5
X7
9-pin D-shell female
PWR RUN CPU TX1 RX1 TX2 RX2
C2 X11 X13 X14 X16 C4 X21 X23 N.C. X15 X17 X20 X22 N.C. X10 X12 C3
TERM PORT1
PORT2
RUN STOP
The D2-HPP Handheld Programmer comes with a communications cable. For a replacement part, use the cable shown below. DL06 Micro PLC
LG Y0 Y2 C1 Y5 Y7 Y10 Y12 C3 Y15 Y17 0V G AC(L) AC(N) 24V C0 Y1 Y3 Y4 Y6 C2 Y11 Y13 Y14 Y16 N.C. OUTPUT: 6-240V
Y
X
0
1
2
50 - 60Hz 3
INPUT: 12 - 24V
4
5
2.0A, 6 - 27V 6
7
10
2.0A 11
12
PWR: 100-240V 13
14
15
16
PWR RUN CPU TX1 RX1 TX2 RX2
50-60Hz 40VA 17
20
D0-06DR
21 22
23
3 - 15mA
LOGIC C0
X3 X2
X4 C1
RJ12 phone style
D2–HPP
(cable comes with HPP)
06
K oyo
X1 X0
RJ12 phone style
X6 X5
X7
C2 X11 X13 X14 X16 C4 X21 X23 N.C. X15 X17 X20 X22 N.C. X10 X12 C3
TERM PORT1
PORT2
RUN STOP
For replacement cable, use part no. DV–1000CBL
DL06 Micro PLC User Manual, 3rd Edition Rev. A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
2–15
Page 56
Chapter 2: Installation, Wiring, and Specifications
Sinking / Sourcing Concepts
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 2–16
Before going further in our presentation of wiring strategies, we need to introduce the concepts of “sinking” and “sourcing.” These terms apply to typical input or output circuits. It is the goal of this section to make these concepts easy to understand. First we give the following short definitions, followed by practical applications. Sinking = Path to supply ground (–) Sourcing = Path to supply source (+) Notice the reference to (+) and (–) polarities. Sinking and sourcing terminology applies only to DC input and output circuits. Input and output points that are either sinking or sourcing can conduct current in only one direction. This means it is possible to connect the external supply and field device to the I/O point with current trying to flow in the wrong direction, and the circuit will not operate. However, we can successfully connect the supply and field device every time by understanding “sourcing” and “sinking.” For example, the figure to the right depicts a “sinking” input. To properly connect the external supply, we just have to connect it so the the input provides a path to ground (–). So, we start at the PLC input terminal, follow through the input sensing circuit, exit at the common PLC Input terminal, and connect the supply (–) to the (sinking) common terminal. By adding the switch, between the supply (+) and the input, we have completed + Input the circuit. Current flows in the direction of the Sensing – arrow when the switch is closed. Common By applying the circuit principle above to the four possible combinations of input/output sinking/sourcing types, we have the four circuits as shown below. The DC-powered DL06 Micro PLCs have selectable sinking or sourcing inputs and either sinking or sourcing outputs. Any pair of input/output circuits shown below is possible with one of the DL06 models.
Sinking Input
Sinking Output Input
PLC
PLC
Output
Load
+ –
+ Common
Input Sensing
Sourcing Input
–
Common
Sourcing Output
Common + –
Output Switch
Input
PLC Input Sensing
PLC
Common +
Output Switch
DL06 Micro PLC User Manual, 3rd Edition Rev. A
Output
– Load
Page 57
Chapter 2: Installation, Wiring, and Specifications
I/O “Common” Terminal Concepts In order for a PLC I/O circuit to operate, current must enter at one terminal and exit at another. This means at least two terminals are associated with every I/O point. In the figure to the right, the input or output terminal is the main path for the current. One additional terminal must provide the return path to the power supply. Most input or output point groups on PLCs share the return path among two or more I/O points. The figure to the right shows a group (or bank) of 4 input points which share a common return path. In this way, the four inputs require only five terminals instead of eight. NOTE: In the circuit to the right, the current in the common path is 4 times any channel’s input current when all inputs are energized. This is especially important in output circuits, where heavier gauge wire is sometimes necessary on commons.
PLC Field Device
Main Path (I/O point)
+
I/O Circuit
– Return Path
PLC Input Sensing Input 1 Input 2 Input 3 Input 4 + –
Common
Most DL06 input and output circuits are grouped into banks that share a common return path. The best indication of I/O common grouping is on the wiring label. The I/O common groups are separated by a bold line. A thinner line separates the inputs associated with that common. To the right, notice that X0, X1, X2, and X3 share the common terminal C0, located to the left of X1. The following complete set of labels shows five banks of four inputs and four banks of four outputs. One common is provided for each bank. 0V G LG Y0 Y2 C1 Y5 Y7 Y10 Y12 C3 Y15 Y17 AC(L) AC(N) 24V C0 Y1 Y3 Y4 Y6 C2 Y11 Y13 Y14 Y16 N.C. C0
X1 X0
X3 X2
X4 C1
X6 X5
X7
C2 X11 X13 X14 X16 C4 X21 X23 N.C. X15 X17 X20 X22 N.C. X10 X12 C3
This set of labels is for DC (sinking) output versions such as the D0-06DD1 and D0-06DD1-D. One common is provided for each group of four outputs, and one designated terminal on the output side accepts power for the output stage. G 0V LG Y0 Y2 C1 Y5 Y7 Y10 Y12 C3 Y15 Y17 AC(L) AC(N) 24V C0 Y1 Y3 Y4 Y6 C2 Y11 Y13 Y14 Y16 +V
C0
X1 X0
X3 X2
X4 C1
X6 X5
X7
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
C2 X11 X13 X14 X16 C4 X21 X23 N.C. X15 X17 X20 X22 N.C. X10 X12 C3
DL06 Micro PLC User Manual, 3rd Edition Rev. A
2–17
Page 58
Chapter 2: Installation, Wiring, and Specifications
Connecting DC I/O to “Solid State” Field Devices
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 2–18
In the previous section on sinking and sourcing concepts, we discussed DC I/O circuits that only allow current to flow one way. This is also true for many of the field devices which have solid-state (transistor) interfaces. In other words, field devices can also be sourcing or sinking. When connecting two devices in a series DC circuit (as is the case when wiring a field device to a PLC DC input or output), one must be wired as sourcing and the other as sinking.
Solid State Input Sensors The DL06’s DC inputs are flexible in that they detect current flow in either direction, so they can be wired as either sourcing or sinking. In the following circuit, a field device has an opencollector NPN transistor output. It sinks current from the PLC input point, which sources current. The power supply can be the included auxiliary 24 VDC power supply or another supply (+12 VDC or +24VDC), as long as the input specifications are met. Field Device
PLC DC Input Input (sourcing)
Output (sinking) Supply Ground
–
+
Common
In the next circuit, a field device has an open-emitter PNP transistor output. It sources current to the PLC input point, which sinks the current back to ground. Since the field device is sourcing current, no additional power supply is required between the device and the PLC DC Input. Field Device =>
PLC DC Input Input (sinking) Output (sourcing) Common
Ground
Solid State Output Loads Sometimes an application requires connecting a PLC output point to a solid state input on a device. This type of connection is usually made to carry a low-level signal, not to send DC power to an actuator. The DL06 PLC family offers DC outputs that are sinking only or DC outputs that are sourcing. All sixteen outputs have the same electrical common, even though there are four common terminal screws. In the following circuit, the PLC output point sinks current to the output common when energized. It is connected to a sourcing input of a field device input. PLC DC Output +DC Power
Field Device
Power
=> Input
Output (sinking) Common
(sourcing)
+ –
2 .25 >
DL06 Micro PLC User Manual, 3rd Edition Rev. A
Ground
Page 59
Chapter 2: Installation, Wiring, and Specifications In the next example we connect a PLC DC output point to the sinking input of a field device. This is a bit tricky, because both the PLC output and field device input are sinking type. Since the circuit must have one sourcing and one sinking device, we add sourcing capability to the PLC output by using a pull-up resistor. In the circuit below, we connect Rpull-up from the output to the DC output circuit power input. PLC DC Output +DC pwr
Power Field Device
R pull-up (sourcing) (sinking)
Output +
Input (sinking)
–
Ground
R input
Supply Common
NOTE 1: DO NOT attempt to drive a heavy load (>25 mA) with this pull-up method. NOTE 2: Using the pull-up resistor to implement a sourcing output has the effect of inverting the output point logic. In other words, the field device input is energized when the PLC output is OFF, from a ladder logic point-of-view. Your ladder program must comprehend this and generate an inverted output. Or, you may choose to cancel the effect of the inversion elsewhere, such as in the field device.
It is important to choose the correct value of Rpull-up. In order to do so, we need to know the nominal input current to the field device (Iinput) when the input is energized. If this value is not known, it can be calculated as shown (a typical value is 15 mA). Then use Iinput and the voltage of the external supply to compute Rpull-up. Then calculate the power Ppull-up (in watts), in order to size Rpull-up properly. I input
=
R pull-up =
V input (turn–on) R input V supply – 0.7 I input
– R input
P pull-up =
V supply
2
R pullup
DL06 Micro PLC User Manual, 3rd Edition Rev. A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
2–19