Page 60

Chapter 2: Installation, Wiring, and Specifications

Relay Output Wiring Methods

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 2–20

The D0–06AR and the D0–06DR models feature relay outputs. Relays are best for the following applications: • Loads that require higher currents than the solid-state DL06 outputs can deliver • Cost-sensitive applications • Some output channels need isolation from other outputs (such as when some loads require AC while others require DC)

Some applications in which NOT to use relays: • Loads that require currents under 10 mA • Loads which must be switched at high speed and duty cycle

This section presents various ways to wire relay outputs to the loads. The relay output DL06s have sixteen normally-open SPST relays available. They are organized with four relays per common. The figure below shows the relays and the internal wiring of the PLC. Note that each group is isolated from the other group of outputs. Y0 Common Y1

Y2

Y4 Common Y5

Y3

Y6

Y7

In the circuit below, all loads use the same AC power supply which powers the DL06 PLC. In this example, all commons are connected together. fuse

L L L L

L L L L

L L L L

L L L L

G 0V LG Y0 Y2 C1 Y5 Y7 Y10 Y12 C3 Y15 Y17 AC(L) AC(N) 24V C0 Y1 Y3 Y4 Y6 C2 Y11 Y13 Y14 Y16 N.C. OUTPUT: 6-240V

50 - 60Hz

2.0A, 6 - 27V

2.0A

PWR: 100-240V

50-60Hz 40VA

Y 0

1

2

3

4

5

6

7

10

11

12

13

14

15

16

17

20

D0-06AR

21 22

23

X INPUT: 90 - 120V

7 - 15mA

In the circuit on the following page, loads for Y0 – Y3 use the same AC power supply which powers the DL06 PLC. Loads for Y4 – Y7 use a separate DC supply. In this example, the commons are separated according to which supply powers the associated load.

DL06 Micro PLC User Manual, 3rd Edition Rev. A

Page 61

Chapter 2: Installation, Wiring, and Specifications +24 VDC L

N

- fuse

+ fuse

L L L L

L L L L

1 2 3 06 4 5 Surge Suppression For Inductive Loads 6 Inductive load devices (devices with a coil) generate transient voltages when de-energized with a relay contact. When a relay contact is closed it “bounces”, which energizes and de7 energizes the coil until the “bouncing” stops. The transient voltages generated are much larger in amplitude than the supply voltage, especially with a DC supply voltage. 8 When switching a DC-supplied inductive load the full supply voltage is always present when the relay contact opens (or “bounces”). When switching an AC-supplied inductive load there is one chance in 60 (60 Hz) or 50 (50 Hz) that the relay contact will open (or 9 “bounce”) when the AC sine wave is zero crossing. If the voltage is not zero when the relay contact opens there is energy stored in the inductor that is released when the voltage 10 to the inductor is suddenly removed. This release of energy is the cause of the transient voltages. When inductive load devices (motors, motor starters, interposing relays, solenoids, valves, 11 etc.) are controlled with relay contacts, it is recommended that a surge suppression device be connected directly across the coil of the field device. If the inductive device has plug12 type connectors, the suppression device can be installed on the terminal block of the relay output. 13 Transient Voltage Suppressors (TVS or transorb) provide the best surge and transient suppression of AC and DC powered coils, providing the fastest response with the smallest 14 overshoot. Metal Oxide Varistors (MOV) provide the next best surge and transient suppression of AC and DC powered coils. A For example, the waveform in the figure below shows the energy released when opening a contact switching a 24 VDC solenoid. Notice the large voltage spike. B C D G 0V LG Y0 Y2 C1 Y5 Y7 Y10 Y12 C3 Y15 Y17 AC(L) AC(N) 24V C0 Y1 Y3 Y4 Y6 C2 Y11 Y13 Y14 Y16 N.C.

OUTPUT: 6-240V

50 - 60Hz

2.0A,

6 - 27V

2.0A

PWR: 100-240V

50-60Hz 40VA

Y

0

1

2

3

4

5

6

7

10

11

12

13

14

15

16

17

20

21

D0-06AR

22

23

X

INPUT: 90 - 120V

7 - 15mA

LOGIC

K oyo

C0

X1

X0

X3

X2

X4

C1

X6

X5

X7

C2 X11 X13 X14 X16 C4 X21 X23 N.C. X15 X17 X20 X22 N.C. X10 X12 C3

AC Supply

+24 VDC

0 VDC

+24 VDC

Module Relay Contact –324 VDC

DL06 Micro PLC User Manual, 3rd Edition Rev. A

2–21

Page 62

Chapter 2: Installation, Wiring, and Specifications

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

This figure shows the same circuit with a transorb (TVS) across the coil. Notice that the voltage spike is significantly reduced. +24 VDC 0 VDC

+24 VDC –42 VDC

Module Relay Contact

Use the following table to help select a TVS or MOV suppressor for your application based on the inductive load voltage. Surge Suppressors Vendor / Catalog

Type

Inductive Load Voltage

Part Number

AutomationDirect Transient Voltage Suppressors, LiteOn Diodes; from Digi-Key Catalog: Phone: 1-800-344-4539

TVS TVS TVS TVS Diode

110/120 VAC 24 VDC 220/240 VAC 12/24 VDC 12/24 VDC

ZL-TD8-120 ZL-TD8-24 P6KE350CA Contact Digi-Key, Corp.

Digi-key www.digikey.com

MOV MOV

110/120 VAC 220/240 VAC

Contact Digi-Key, Corp.

Prolonging Relay Contact Life Relay contacts wear according to the amount of relay switching, amount of spark created at the time of open or closure, and presence of airborne contaminants. There are some steps you can take to help prolong the life of relay contacts, such as switching the relay on or off only when it is necessary, and if possible, switching the load on or off at a time when it will draw the least current. Also, take measures to suppress inductive voltage spikes from inductive DC loads such as contactors and solenoids. For inductive loads in DC circuits we recommend using a suppression diode as shown in the following diagram (DO NOT use this circuit with an AC power supply). When the load is energized the diode is reverse-biased (high impedance). When the load is turned off, energy stored in its coil is released in the form of a negative-going voltage spike. At this moment the diode is forward-biased (low impedance) and shunts the energy to ground. This protects the relay contacts from the high voltage arc that would occur just as the contacts are opening. Place the diode as close to the inductive field device as possible. Use a diode with a peak inverse voltage rating (PIV) at least 100 PIV, 3A forward current or larger. Use a fast-recovery type (such as Schottky type). DO NOT use a small-signal diode such as 1N914, 1N941, etc. Be sure the diode is in the circuit correctly before operation. If installed backwards, it shortcircuits the supply when the relay energizes. Inductive Field Device

PLC Relay Output

Common

2–22

Input

Output

+

–

DL06 Micro PLC User Manual, 3rd Edition Rev. A

Common

Page 63

Chapter 2: Installation, Wiring, and Specifications

DC Input Wiring Methods

PLC DC Input

Input DL06 Micro PLCs with DC inputs are particularly flexible because they can be wired as either sinking or sourcing. The dual diodes (shown to the right) allow 10.8 – 26.4 VDC. The target applications are +12 VDC and +24 VDC. Common You can actually wire each group of inputs associated common group of inputs as DC sinking and the other half as DC sourcing. Inputs grouped by a common must be all sinking or all sourcing. In the first and simplest example below, all commons are connected together and all inputs are sinking. C0

X1 X0

X3 X2

X4 C1

X6 X5

X7

C2 X11 X13 X14 X16 C4 X21 X23 N.C. X15 X17 X20 X22 N.C. X10 X12 C3

+24 VDC

+

In the next example, the first eight inputs are sinking, and the last twelve are sourcing. C0

X1 X0

+12 VDC

+

X3 X2

X4 C1

X6 X5

X7

C2 X11 X13 X14 X16 C4 X21 X23 N.C. X15 X17 X20 X22 N.C. X10 X12 C3

+24 VDC

+ -

DL06 Micro PLC User Manual, 3rd Edition Rev. A

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

2–23

Page 64

Chapter 2: Installation, Wiring, and Specifications

DC Output Wiring Methods

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 2–24

DL06 DC output circuits are high-performance transistor switches with low on-resistance and fast switching times. Please note the following characteristics which are unique to the DC output type: • There is only one electrical common for all sixteen outputs. All sixteen outputs belong to one bank. • The output switches are current-sinking only or current sourcing only. Refer to the detailed specifications in this manual to determine which type output is present on a particular model. • The output circuit inside the PLC requires external power. The supply (–) must be connected to a common terminal, and the supply (+) connects the the right-most terminal on the upper connector (+V).

In the example below, all sixteen outputs share a common supply. - fuse

+24 VDC L L L L

L L L L

L L L L

L L L L

+

G LG 0V Y0 Y2 C1 Y5 Y7 Y10 Y12 C3 Y15 Y17 AC(L) AC(N) 24V C0 Y1 Y3 Y4 Y6 C2 Y11 Y13 Y14 Y16 +V

In the next example below, the outputs have “split” supplies. The first eight outputs are using a +12 VDC supply, and the last eight are using a +24 VDC supply. However, you can split the outputs among any number of supplies, as long as: • all supply voltages are within the specified range • all output points are wired as sinking • all source (–) terminals are connected together +12 VDC fuse

+24 VDC

+

L L L L

L L L L

L L L L

L L L L

+

LG 0V Y0 Y2 C1 Y5 Y7 Y10 Y12 C3 Y15 Y17 G Y1 Y3 Y4 Y6 C2 Y11 Y13 Y14 Y16 +V AC(L) AC(N) 24V C0

Warning: The maximum output current from the Auxiliary 24VDC power depends on the I/O configuration. Refer to Chapter 4, page 4-6, to determine how much current can be drawn from the Auxiliary 24VDC power for your particular I/O configuration.

DL06 Micro PLC User Manual, 3rd Edition Rev. A

Page 65

Chapter 2: Installation, Wiring, and Specifications

High-Speed I/O Wiring Methods DL06 versions with DC type input or output points contain a dedicated High-Speed I/O circuit (HSIO). The circuit configuration is programmable, and it processes specific I/O points independently from the CPU scan. Appendix E discusses the programming options for HSIO. While the HSIO circuit has six modes, we show wiring diagrams for two of the most popular modes in this chapter. The high-speed input interfaces to points X0 – X3. Properly configured, the DL06 can count quadrature pulses at up to 7 kHz from an incremental encoder as shown below. C0

X1 X0

X3 X2

X4 C1

X6 X5

X7

C2 X11 X13 X14 X16 C4 X21 X23 N.C. X15 X17 X20 X22 N.C. X10 X12 C3

Phase A = X0 Phase B = X1

DL06 versions with DC type output points can use the High Speed I/O Pulse Output feature. It can generate high-speed pulses at up to 10 kHz for specialized control such as stepper motor / intelligent drive systems. Output Y0 and Y1 can generate pulse and direction signals, or it can generate CCW and CW pulse signals respectively. See Appendix E on highspeed input and pulse output options. Motor

Amplifier +

Power Input

+24 VDC

Signal Common Pulse Direction

G LG 0V Y0 Y2 C1 Y5 Y7 Y10 Y12 C3 Y15 Y17 AC(L) AC(N) 24V C0 Y1 Y3 Y4 Y6 C2 Y11 Y13 Y14 Y16 +V

DL06 Micro PLC User Manual, 3rd Edition Rev. A

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

2–25

Page 66

Chapter 2: Installation, Wiring, and Specifications

1 Wiring Diagrams and Specifications The remainder of this chapter provides detailed technical information for the DL06 PLCs. A basic wiring diagram, equivalent I/O circuits, and specification tables are laid out for each PLC. 2 D0–06AA I/O Wiring Diagram 3 The D0–06AA PLC has twenty AC inputs and sixteen AC outputs. The following diagram shows a typical field wiring example. The AC external power connection uses four terminals as shown. Inputs are organized into five banks of four. Each bank has an isolated common terminal. The 4 wiring example below shows all commons connected together, but separate supplies and common circuits may be used. The equivalent input circuit shows one channel of a typical bank. 5 Outputs are organized into four banks of four triac switches. Each bank has a common terminal. The wiring example below shows all commons connected together, but separate supplies and 6 common circuits may be used. The equivalent output circuit shows one channel of a typical bank. 7 8 9 10 11 06 12 13 14 A B C D fuse

AC Supply

L L L L

L L L L

L L L L

L L L L

G 0V LG Y0 Y2 C1 Y5 Y7 Y10 Y12 C3 Y15 Y17 AC(L) AC(N) 24V C0 Y1 Y3 Y4 Y6 C2 Y11 Y13 Y14 Y16 N.C.

OUTPUT: 17-240V

Y

X

0

1

2

50 - 60Hz

3

INPUT: 90 - 120V

4

0.5A

5

6

7

PWR: 100-240V

50-60Hz 40VA

10

14

11

12

13

15

16

17

20

21

D0-06AA

22

23

7 - 15mA

LOGIC C0

K oyo

X1

X0

X3

X2

X4

C1

X6

X5

X7

C2 X11 X13 X14 X16 C4 X21 X23 N.C. N.C. X15 X17 X20 X22 X10 X12 C3

AC Supply

Equivalent Input Circuit

+V

Input

Optical Isolator

Equivalent Output Circuit

Derating Chart for AC Outputs

Internal module circuitry

Points

+V

16

0.5 A

Y0 - Y7 Y10 - Y17

12

OUTPUT

L

Optical Isolator

8

Common

4

COM

0

0 32

10 50

20 68

30 86

40 104

50 122

55˚C 131˚F

Ambient Temperature ( ˚C/ ˚F)

2–26

DL06 Micro PLC User Manual, 3rd Edition Rev. A

To

Page 67

Chapter 2: Installation, Wiring, and Specifications

D0-06AA General Specifications External Power Requirements Communication Port 1 9600 baud (Fixed), 8 data bits, 1 stop bit odd parity Communication Port 2 9600 baud (default) 8 data bits, 1 stop bit odd parity Programming cable type Operating Temperature Storage Temperature Relative Humidity Environmental air Vibration Shock Noise Immunity Terminal Type Wire Gauge

100– 240 VAC, 40 VA maximum, K–Sequence (Slave), DirectNET (Slave), MODBUS (Slave) K–Sequence (Slave),DirectNET (Master/Slave), MODBUS (Master/Slave), Non-sequence / print, ASCII in/out D2–DSCBL 32 to 131° F (0 to 55° C) –4 to 158° F (–20 to 70° C) 5 to 95% (non-condensing) No corrosive gases permitted MIL STD 810C 514.2 MIL STD 810C 516.2 NEMA ICS3–304 Removable One 16 AWG or two 18 AWG, 24 AWG minimum

AC Input Specifications Input Voltage Range (Min. - Max.) Operating Voltage Range

80 – 132 VAC, 47 - 63 Hz 90 – 120 VAC, 47 - 63 Hz 8 mA @100 VAC at 50 Hz 10 mA @100 VAC at 60 Hz

Input Current

12 mA @132 VAC at 50 Hz 15 mA @132 VAC at 60 Hz @50 Hz, @60Hz > 6 mA @ 75 VAC < 2 mA @ 20 VAC < 40 ms < 40 ms Logic Side 4 channels / common x 5 banks (isolated)

Max. Input Current Input Impedance ON Current/Voltage OFF Current/Voltage OFF to ON Response ON to OFF Response Status Indicators Commons

AC Output Specifications Output Voltage Range (Min. - Max.) Operating Voltage On Voltage Drop Max Current Max leakage current Max inrush current Minimum Load OFF to ON Response ON to OFF Response Status Indicators Commons Fuses

15 – 264 VAC, 47 – 63 Hz 17 – 240 VAC, 47 – 63 Hz 1.5 VAC (>50mA) 4.0 VAC (<50mA) 0.5 A / point, 1.5 A / common <4 mA @ 264 VAC 10 A for 10 ms 10 mA 1 ms 1 ms +1/2 cycle Logic Side 4 channels / common x 4 banks (isolated) None (external recommended)

DL06 Micro PLC User Manual, 3rd Edition Rev. A

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 2–27

Page 68

Chapter 2: Installation, Wiring, and Specifications

D0–06AR I/O Wiring Diagram

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

The D0–06AR PLC has twenty AC inputs and sixteen relay contact outputs. The following diagram shows a typical field wiring example. The AC external power connection uses four terminals at the left as shown. The twenty AC input channels use terminals on the bottom of the connector. Inputs are organized into five banks of four. Each bank has a common terminal. The wiring example below shows all commons connected together, but separate supplies and common circuits may be used. The equivalent input circuit shows one channel of a typical bank. fuse AC or DC Supply L L L L

L L L L

L L L L

L L L L

G LG Y0 Y2 C1 Y5 Y7 Y10 Y12 C3 Y15 Y17 0V AC(L) AC(N) 24V C0 Y1 Y3 Y4 Y6 C2 Y11 Y13 Y14 Y16 N.C. OUTPUT: 6-240V

50 - 60Hz

2.0A, 6 - 27V

2.0A

PWR: 100-240V

50-60Hz 40VA

Y 0

1

2

3

4

5

6

7

10

11

12

13

14

15

16

17

20

D0-06AR

21 22

23

X INPUT: 90 - 120V

Typical Relay Life (Operations) at Room Temperature

Voltage & Load Type 24VDC Resistive 24VDC Inductive 110VAC Resistive 110VAC Inductive 220VAC Resistive 220VAC Inductive

06

K oyo C0

X1 X0

250K 50K 250K 100K 200K 50K

Equivalent Input Circuit

X3 X2

X4 C1

X6 X5

X7

C2 X11 X13 X14 X16 C4 X21 X23 N.C. X10 X12 C3 X15 X17 X20 X22 N.C.

AC Supply

Derating Chart for Relay Outputs +V

Input

LOGIC

Load Current At 1A At 2A 500K 100K 500K 200K 350K 100K

7 - 15mA

+V

Internal module circuitry

Points 16

Optical Isolator

2.0A

Y0 - Y7 Y10 - Y17

12

To LED

Equivalent Output Circuit

8

+V

L

Output

4

Common

2–28

0 0 32

10 50

20 68

30 86

40 104

50 122

55˚C 131˚F

Ambient Temperature ( ˚C/ ˚F)

DL06 Micro PLC User Manual, 3rd Edition Rev. A

Common

To LED

Page 69

Chapter 2: Installation, Wiring, and Specifications The sixteen relay output channels use terminals on the right side top connector. Outputs are organized into four banks of four normally-open relay contacts. Each bank has a common terminal. The wiring example on the last page shows all commons connected together, but separate supplies and common circuits may be used. The equivalent output circuit shows one channel of a typical bank. The relay contacts can switch AC or DC voltages. D0-06AR General Specifications 100 – 240 VAC, 40 VA maximum, External Power Requirements Communication Port 1 9600 baud (Fixed), 8 data K–Sequence (Slave), DirectNET (Slave), MODBUS (Slave) bits, 1 stop bit, odd parity Communication Port 2 9600 baud (default), 8 data K–Sequence (Slave), DirectNET (Master/Slave), MODBUS (Master/Slave), Non-sequence / print, ASCII in/out bits, 1 stop bit, odd parity D2–DSCBL Programming cable type 32 to 131° F (0 to 55° C) Operating Temperature –4 to 158° F (–20 to 70° C) Storage Temperature 5 to 95% (non-condensing) Relative Humidity No corrosive gases permitted Environmental air MIL STD 810C 514.2 Vibration MIL STD 810C 516.2 Shock NEMA ICS3–304 Noise Immunity Removable Terminal Type One 16 AWG or two 18 AWG, 24 AWG minimum Wire Gauge

AC Input Specifications X0-X23 Input Voltage Range (Min. - Max.) Operating Voltage Range Input Current Max. Input Current Input Impedance ON Current/Voltage OFF Current/Voltage OFF to ON Response ON to OFF Response Status Indicators Commons

80 – 132 VAC, 47 - 63 Hz 90 – 120 VAC, 47 -63 Hz 8 mA @ 100 VAC at 50 Hz 10 mA @ 100 VAC at 60 Hz 12 mA @ 132 VAC at 50 Hz 15 mA @ 132 VAC at 60 Hz @50 Hz, @60 Hz >6 mA @ 75 VAC <2 mA @ 20 VAC < 40 ms < 40 ms Logic Side 4 channels / common x 5 banks (isolated)

Relay Output Specifications Y0-Y17 Output Voltage Range Operating Voltage Range Output Current Max. leakage current Smallest Recommended Load OFF to ON Response ON to OFF Response Status Indicators Commons Fuses

(Min. – Max.) 5 – 264 VAC (47 -63 Hz), 5 – 30 VDC 6 – 240 VAC (47 -63 Hz), 6 – 27 VDC 2A / point, 6A / common 0.1 mA @264VAC 5 mA @5 VDC < 15 ms < 10 ms Logic Side 4 channels / common x 4 banks (isolated) None (external recommended)

DL06 Micro PLC User Manual, 3rd Edition Rev. A

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

2–29