Page 70
Chapter 2: Installation, Wiring, and Specifications
D0–06DA I/O Wiring Diagram
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
The D0–06DA PLC has twenty DC inputs and sixteen AC outputs. The following diagram shows a typical field wiring example. The AC external power connection uses four terminals as shown. Inputs are organized into five banks of four. Each bank has an isolated common terminal, and may be wired as sinking or sourcing. The wiring example below shows all commons connected together, but separate supplies and common circuits may be used. The equivalent circuit for standard inputs is shown below, and the high-speed input circuit is shown to the left. Outputs are organized into four banks of four triac switches. Each bank has a common terminal. The wiring example below shows all commons connected together, but separate supplies and common circuits may be used. The equivalent output circuit shows one channel of a typical bank. fuse
AC Supply L L L L
L L L L
L L L L
L L L L
G LG Y0 Y2 C1 Y5 Y7 Y10 Y12 C3 Y15 Y17 0V AC(L) AC(N) 24V C0 Y1 Y3 Y4 Y6 C2 Y11 Y13 Y14 Y16 N.C. OUTPUT: 17 - 240V
Y X
0
1
2
3
INPUT: 12 - 24V
50-60Hz
0.5A
5
7
4
6
PWR: 100-240V 10
11
12
13
50-60Hz 40VA 14
15
16
17
20
D0-06DA
21 22
23
3 - 15mA
LOGIC C0
06
K oyo
X1 X0
X3 X2
X4 C1
X6 X5
X7
C2 X11 X13 X14 X16 C4 X21 X23 N.C. X15 X17 X20 X22 N.C. X10 X12 C3
Standard Inputs (X4-X23) +V
+V
DC Supply
Optical Isolator
Input
To LED
+ –
Common
High Speed Inputs (X0-X3) +V
+
Input
Optical Isolator
Equivalent Output Circuit
Derating Chart for AC Outputs Points
Internal module circuitry
16
0.5 A
Y0 - Y7 Y10 - Y17
12
+V OUTPUT L
8
–
Common
Optical Isolator
4 0 0 32
10 50
20 68
30 86
40 104
50 122
55˚C 131˚F
COM
Ambient Temperature ( ˚C/ ˚F)
To LED
2–30
DL06 Micro PLC User Manual, 3rd Edition Rev. A
Page 71
Chapter 2: Installation, Wiring, and Specifications
D0-06DA General Specifications 100 – 240 VAC, 40 VA maximum, External Power Requirements Communication Port 1 9600 baud (Fixed), 8 data K–Sequence (Slave), DirectNET (Slave), MODBUS (Slave) bits, 1 stop bit, odd parity Communication Port 2 9600 baud (default), 8 data K–Sequence (Slave), DirectNET (Master/Slave), MODBUS (Master/Slave), Non-sequence/print, ASCII in/out bits, 1 stop bit, odd parity D2–DSCBL Programming cable type 32 to 131° F (0 to 55° C) Operating Temperature –4 to 158° F (–20 to 70° C) Storage Temperature 5 to 95% (non-condensing) Relative Humidity No corrosive gases permitted Environmental air MIL STD 810C 514.2 Vibration MIL STD 810C 516.2 Shock NEMA ICS3–304 Noise Immunity Removable Terminal Type One 16 AWG or two 18 AWG, 24 AWG minimum Wire Gauge
DC Input Specifications Parameter Input Voltage Range Operating Voltage Range Maximum Voltage Minimum Pulse Width ON Voltage Level OFF Voltage Level Input Impedance Minimum ON Current Maximum OFF Current OFF to ON Response ON to OFF Response Status Indicators Commons
High–Speed Inputs, X0 – X3
Standard DC Inputs X4 – X23
10.8 – 26.4 VDC 10.8 – 26.4 VDC 12 – 24 VDC 12 – 24 VDC 30 VDC (7 kHz maximum frequency) 30 VDC 70 µs N/A > 10 VDC > 10 VDC < 2.0 VDC < 2.0 VDC 1.8 @ 12 – 24 VDC 2.8 @ 12 – 24 VDC >5 mA >4 mA < 0.5 mA <0.5 mA <70 µs 2 – 8 ms, 4 ms typical <70 µs 2 – 8 ms, 4 ms typical Logic side Logic side 4 channels / common x 5 bank (isolated)
AC Output Specifications Output Voltage Range (Min. - Max.) Operating Voltage On Voltage Drop Max Current Max leakage current Max inrush current Minimum Load OFF to ON Response ON to OFF Response Status Indicators Commons Fuses
15 – 264 VAC, 47 – 63 Hz 17 – 240 VAC, 47 – 63 Hz 1.5 VAC @> 50mA, 4 VAC @< 50mA 0.5 A / point, 1.5 A / common < 4 mA @ 264 VAC, 60Hz 10 A for 10 ms 10 mA 1 ms 1 ms +1/2 cycle Logic Side 4 channels / common x 4 banks (isolated) None (external recommended)
DL06 Micro PLC User Manual, 3rd Edition Rev. A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
2–31
Page 72
Chapter 2: Installation, Wiring, and Specifications
D0–06DD1 I/O Wiring Diagram
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
The D0-06DD1 PLC has twenty sinking/sourcing DC inputs and sixteen sinking DC outputs. The following diagram shows a typical field wiring example. The AC external power connection uses four terminals as shown. Inputs are organized into five banks of four. Each bank has an isolated common terminal, and may be wired as either sinking or sourcing inputs. The wiring example below shows all commons connected together, but separate supplies and common circuits may be used. Outputs all share the same common. Note the requirement for external power. - fuse
+24 VDC L L L L
L L L L
L L L L
+
L L L L
0V G LG Y0 Y2 C1 Y5 Y7 Y10 Y12 C3 Y15 Y17 AC(L) AC(N) 24V C0 Y1 Y3 Y4 Y6 C2 Y11 Y13 Y14 Y16 +V OUTPUT: Sinking Output
Y X
0
1
2
3
INPUT: 12 - 24V
6 - 27V 4
5
1.0A 6
7
PWR: 100-240V 10
11
12
13
50-60Hz 40VA 14
15
16
17
20
D0-06DD1
21 22
23
3 - 15mA
LOGIC C0
06
K oyo
X1 X0
X3 X2
X4 C1
X6 X5
X7
C2 X11 X13 X14 X16 C4 X21 X23 N.C. X15 X17 X20 X22 N.C. X10 X12 C3
DC Supply
DC Pulse Outputs (Y0-Y1)
High Speed Inputs (X0-X3)
+V
+V
Input
+
Optical Isolator
Internal module circuitry
To LED
OUTPUT
L
–
Derating Chart for DC Outputs
Common
Optical Isolator
+
Points
To LED
16
0.75A
COM
Y0 - Y17
12
1.0 A
8
DC Standard Inputs (X4-X23) +V
Input +
DC Standard Outputs (Y2-Y17)
4
+V
+V
0 0 32
Optical Isolator
10 50
20 68
30 86
40 104
50 55˚C 122 131˚F
To LED
L
OUTPUT
+
Common COM
DL06 Micro PLC User Manual, 3rd Edition Rev. A
Internal module circuitry
+
Ambient Temperature ( ˚C/ ˚F)
–
2–32
+V
+
Optical Isolator
To LED
Page 73
Chapter 2: Installation, Wiring, and Specifications D0-06DD1 General Specifications External Power Requirements Communication Port 1 9600 baud (Fixed), 8 data bits, 1 stop bit, odd parity Communication Port 2 9600 baud (default), 8 data bits, 1 stop bit, odd parity Programming cable type Operating Temperature Storage Temperature Relative Humidity Environmental air Vibration Shock Noise Immunity Terminal Type Wire Gauge
100 – 240 VAC, 40 VA maximum, K–Sequence (Slave), DirectNET (Slave), MODBUS (Slave) K–Sequence (Slave), DirectNET (Master/Slave), MODBUS (Master/Slave), Non-sequence / print, ASCII in/out D2–DSCBL 32 to 131° F (0 to 55° C) –4 to 158° F (–20 to 70° C) 5 to 95% (non-condensing) No corrosive gases permitted MIL STD 810C 514.2 MIL STD 810C 516.2 NEMA ICS3–304 Removable One 16 AWG or two 18 AWG, 24 AWG minimum
DC Input Specifications Parameter Min. - Max. Voltage Range Operating Voltage Range Peak Voltage Minimum Pulse Width ON Voltage Level OFF Voltage Level Max. Input Current Input Impedance Minimum ON Current Maximum OFF Current OFF to ON Response ON to OFF Response Status Indicators Commons
High–Speed Inputs, X0 – X3
Standard DC Inputs X4 – X23
10.8 – 26.4 VDC 10.8 – 26.4 VDC 12 – 24 VDC 12 – 24 VDC 30 VDC (7 kHz maximum frequency) 30 VDC 100 µs N/A > 10.0 VDC > 10.0 VDC < 2.0 VDC < 2.0 VDC 6mA @12VDC, 13mA @24VDC 4mA @12VDC, 8.5mA @24VDC 1.8 @ 12 – 24 VDC 2.8 @ 12 – 24 VDC >5 mA >4 mA < 0.5 mA <0.5 mA <70 µs 2 – 8 ms, 4 ms typical <70 µs 2 – 8 ms, 4 ms typical Logic side Logic side 4 channels / common x 5 banks isolated
DC Output Specifications Parameter Min. - Max. Voltage Range Operating Voltage Peak Voltage On Voltage Drop Max Current (resistive) Max leakage current Max inrush current External DC power required OFF to ON Response ON to OFF Response Status Indicators Commons Fuses
Pulse Outputs Y0 – Y1
Standard Outputs Y2 – Y17
5 – 30 VDC 6 – 27 VDC < 50 VDC (10 kHz max. frequency) 0.3 VDC @ 1 A 0.5 A / pt., 1A / pt. as standard pt. 15µA @ 30 VDC 2 A for 100 ms
5 – 30 VDC 6 – 27 VDC < 50 VDC 0.3 VDC @ 1 A 1.0 A / point 15µA @ 30 VDC 2 A for 100 ms 20 28 VDC Max 280mA (Aux. 24VDC 20 - 28 VDC Max 150mA powers V+ terminal (sinking outputs) < 10 µs < 10 µs < 20 µs < 60 µs Logic Side Logic Side 4 channels / common x 4 banks non-isolated None (external recommended)
DL06 Micro PLC User Manual, 3rd Edition Rev. A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
2–33
Page 74
Chapter 2: Installation, Wiring, and Specifications
D0–06DD2 I/O Wiring Diagram The D0–06DD2 PLC has twenty sinking/sourcing DC inputs and sixteen sourcing DC outputs. The following diagram shows a typical field wiring example. The AC external power connection uses four terminals as shown. Inputs are organized into four banks of four. Each bank has an isolated common terminal, and may be wired as either sinking or sourcing inputs. The wiring example below shows all commons connected together, but separate supplies and common circuits may be used. All outputs share the same common. Note the requirement for external power. + fuse
+24 VDC
-
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
L L L L
L L L L
L L L L
L L L L
0V G LG Y0 Y2 V1 Y5 Y7 Y10 Y12 V3 Y15 Y17 AC(L) AC(N) 24V V0 Y1 Y3 Y4 Y6 V2 Y11 Y13 Y14 Y16 CO OUTPUT: Sourcing Output 12 - 24V
Y X
0
1
2
3
INPUT: 12 - 24V
4
5
1.0A
6
7
PWR: 100-240V 10
11
12
13
50-60Hz 40VA 14
15
16
17
20
D0-06DD2
21 22
23
3 - 15mA
LOGIC C0
06
K oyo
X1 X0
X3 X2
X4 C1
X6 X5
X7
C2 X11 X13 X14 X16 C4 X21 X23 N.C. X15 X17 X20 X22 N.C. X10 X12 C3
DC Supply
DC Pulse Outputs (Y0-Y1)
High Speed Inputs (X0-X3)
Internal module circuitry
V0 - V3
+V Optical Isolator
Input
+
V0 - V3
To LED
+ -
–
Derating Chart for DC Outputs
Common
Output
16
+V
Input +
0.75A
12
1.0 A
Y0 - Y7 Y10 - Y17
DC Standard Outputs (Y2-Y17)
8
+V
Optical Isolator
Internal module circuitry
4 0
To LED
Optical Isolator C0
Points
DC Standard Inputs (X4-X23)
To LED
L
0 32
10 50
20 68
30 86
40 104
50 55˚C 122 131˚F
Ambient Temperature ( ˚C/ ˚F)
V0 - V3
+
To LED
Output L
–
Common
C0 Optical Isolator
2–34
DL06 Micro PLC User Manual, 3rd Edition Rev. A
Page 75
Chapter 2: Installation, Wiring, and Specifications D0-06DD2 General Specifications External Power Requirements Communication Port 1 9600 baud (Fixed), 8 data bits, 1 stop bit, odd parity Communication Port 2 9600 baud (default), 8 data bits, 1 stop bit, odd parity Programming cable type Operating Temperature Storage Temperature Relative Humidity Environmental air Vibration Shock Noise Immunity Terminal Type Wire Gauge
100 – 240 VAC, 40 VA maximum, K–Sequence (Slave), DirectNET (Slave), MODBUS (Slave) K–Sequence (Slave), DirectNET (Master/Slave), MODBUS (Master/Slave), Non-sequence / print, ASCII in/out D2–DSCBL 32 to 131° F (0 to 55° C) –4 to 158° F (–20 to 70° C) 5 to 95% (non-condensing) No corrosive gases permitted MIL STD 810C 514.2 MIL STD 810C 516.2 NEMA ICS3–304 Removable One 16 AWG or two 18 AWG, 24 AWG minimum
DC Input Specifications Parameter Min. - Max. Voltage Range Operating Voltage Range Peak Voltage Minimum Pulse Width ON Voltage Level OFF Voltage Level Max. Input Current Input Impedance Minimum ON Current Maximum OFF Current OFF to ON Response ON to OFF Response Status Indicators Commons
High–Speed Inputs, X0 – X3
Standard DC Inputs X4 – X23
10.8 – 26.4 VDC 10.8 – 26.4 VDC 12 – 24 VDC 12 – 24 VDC 30 VDC (7 kHz maximum frequency) 30 VDC 70 µs N/A > 10.0 VDC > 10.0 VDC < 2.0 VDC < 2.0 VDC 6mA @12VDC, 13mA @24VDC 4mA @12VDC, 8.5mA @24VDC 1.8 @ 12 – 24 VDC 2.8 @ 12 – 24 VDC >5 mA >4 mA < 0.5 mA <0.5 mA <70 µs 2 – 8 ms, 4 ms typical <70 µs 2 – 8 ms, 4 ms typical Logic side Logic side 4 channels/common x 5 banks (isolated)
DC Output Specifications Parameter Min. - Max. Voltage Range Operating Voltage Peak Voltage On Voltage Drop Max Current (resistive) Max leakage current Max inrush current External DC power required OFF to ON Response ON to OFF Response Status Indicators Commons Fuses
Pulse Outputs Y0 – Y1
Standard Outputs Y2 – Y17
10.8 -26.4 VDC 10.8 -26.4 VDC 12-24 VDC 12-24 VDC < 50 VDC (10 kHz max. frequency) < 50 VDC 0.5VDC @ 1 A 1.2 VDC @ 1 A 0.5 A / pt., 1A / pt. as standard pt. 1.0 A / point 15 µA @ 30 VDC 15 µA @ 30 VDC 2 A for 100 ms 2 A for 100 ms 12 - 24 VDC 12 -24 VDC < 10µs < 10 µs < 20 µs < 0.5 µs Logic Side Logic Side 4 channels / common x 4 banks (non-isolated) None (external recommended)
DL06 Micro PLC User Manual, 3rd Edition Rev. A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
2–35
Page 76
Chapter 2: Installation, Wiring, and Specifications
D0–06DR I/O Wiring Diagram
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
The D0–06DR PLCs feature twenty DC inputs and sixteen relay contact outputs. The following diagram shows a typical field wiring example. The AC external power connection uses four terminals as shown. Inputs are organized into five banks of four. Each bank has an isolated common terminal, and may be wired as either sinking or sourcing inputs. The wiring example below shows all commons connected together, but separate supplies and common circuits may be used. The equivalent circuit for standard inputs is shown below, and the high-speed input circuit is shown to the left. Outputs are organized into four banks of four normally-open relay contacts. Each bank has a common terminal. The wiring example below shows all commons connected together, but separate supplies and common circuits may be used. The equivalent output circuit shows one channel of a typical bank. The relay contacts can switch AC or DC voltages. Typical Relay Life (Operations) at Room Temperature
Voltage & Load Type fuse
AC or DC Supply L L L L
L L L L
L L L L
Load Current At 1A At 2A
24VDC Resistive 24VDC Inductive 110VAC Resistive 110VAC Inductive 220VAC Resistive 220VAC Inductive
500K 100K 500K 200K 350K 100K
250K 50K 250K 100K 200K 50K
G 0V LG Y0 Y2 C1 Y5 Y7 Y10 Y12 C3 Y15 Y17 AC(L) AC(N) 24V C0 Y1 Y3 Y4 Y6 C2 Y11 Y13 Y14 Y16 N.C. OUTPUT: 6-240V
Y X
0
1
2
50 - 60Hz 3
INPUT: 12 - 24V
Equivalent Circuit, High-speed Inputs (X0-X3)
4
5
2.0A, 6 - 27V 6
7
10
2.0A 11
12
PWR: 100-240V 13
14
15
16
50-60Hz 40VA 17
20
D0-06DR
21 22
23
3 - 15mA
LOGIC C0
+V
+
L L L L
06
K oyo
X1 X0
X3 X2
X4 C1
X6 X5
X7
C2 X11 X13 X14 X16 C4 X21 X23 N.C. X15 X17 X20 X22 N.C. X10 X12 C3
Optical Isolator
Input
To LED
–
Common DC Supply
Equivalent Circuit, Standard Inputs (X4-X23) +V
Input +
Equivalent Output Circuit +V
Internal module circuitry
Derating Chart for Relay Outputs
Optical Isolator
+V
L
Output
To LED
–
Common
Common
F
2–36
DL06 Micro PLC User Manual, 3rd Edition Rev. A
To LED
Page 77
Chapter 2: Installation, Wiring, and Specifications
D0-06DR General Specifications 100 – 240 VAC, 40 VA maximum, External Power Requirements Communication Port 1 9600 baud (Fixed), 8 data K–Sequence (Slave), DirectNET (Slave), MODBUS (Slave) bits, 1 stop bit, odd parity Communication Port 2 9600 baud (default), 8 data K–Sequence (Slave), DirectNET (Master/Slave), MODBUS (Master/Slave), Non-sequence /print, ASCII in/out bits, 1 stop bit,odd parity D2–DSCBL Programming cable type 32 to 131° F (0 to 55° C) Operating Temperature –4 to 158° F (–20 to 70° C) Storage Temperature 5 to 95% (non-condensing) Relative Humidity No corrosive gases permitted Environmental air MIL STD 810C 514.2 Vibration MIL STD 810C 516.2 Shock NEMA ICS3–304 Noise Immunity Removable Terminal Type One 16 AWG or two 18 AWG, 24 AWG minimum Wire Gauge
DC Input Specifications Parameter Min. - Max. Voltage Range Operating Voltage Range Peak Voltage Minimum Pulse Width ON Voltage Level OFF Voltage Level Input Impedance Max. Input Current Minimum ON Current Maximum OFF Current OFF to ON Response ON to OFF Response Status Indicators Commons
High–Speed Inputs, X0 – X3
Standard DC Inputs X4 – X23
10.8 – 26.4 VDC 10.8 – 26.4 VDC 12 -24 VDC 12 -24 VDC 30 VDC (7 kHz maximum frequency) 30 VDC 70 µs N/A > 10 VDC > 10 VDC < 2.0 VDC < 2.0 VDC 1.8 @ 12 – 24 VDC 2.8 @ 12 – 24 VDC 6mA @12VDC 13mA @24VDC 4mA @12VDC 8.5mA @24VDC >5 mA >4 mA < 0.5 mA <0.5 mA <70 µs 2 – 8 ms, 4 ms typical <70 µs 2 – 8 ms, 4 ms typical Logic side Logic side 4 channels / common x 5 banks (isolated)
Relay Output Specifications Output Voltage Range (Min. - Max.) Operating Voltage Output Current Maximum Voltage Max leakage current Smallest Recommended Load OFF to ON Response ON to OFF Response Status Indicators Commons Fuses
5 -264 VAC (47 -63 Hz), 5 - 30 VDC 6 -240 VAC (47 -63 Hz), 6 - 27 VDC 2A / point 6A / common 264 VAC, 30 VDC 0.1 mA @264 VAC 5 mA < 15 ms < 10 ms Logic Side 4 channels / common x 4 banks (isolated) None (external recommended)
DL06 Micro PLC User Manual, 3rd Edition Rev. A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
2–37
Page 78
Chapter 2: Installation, Wiring, and Specifications
D0–06DD1–D I/O Wiring Diagram
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
These micro PLCs feature twenty DC inputs and sixteen sinking DC outputs. The following diagram shows a typical field wiring example. The DC external power connection uses four terminals at the left as shown. Inputs are organized into five banks of four. Each bank has an isolated common terminal, and may be wired as either sinking or sourcing inputs. The wiring example below shows all commons connected together, but separate supplies and common circuits may be used. All outputs actually share the same common. Note the requirement for external power. 12 - 24 VDC
-
+
+24 VDC L L L L
G
LG
+
-
OUTPUT: Sinking Output
Y X
0
1
2
3
INPUT: 12 - 24V
L L L L
L L L L
+
L L L L
N.C. Y0 Y2 C1 Y5 Y7 Y10 Y12 C3 Y15 Y17 N.C. C0 Y1 Y3 Y4 Y6 C2 Y11 Y13 Y14 Y16 +V 6 - 27V
4
5
1.0A 6
7
PWR: 12-24 10
11
12
13
20W 14
15
16
17
20
D0-06DD1-D 21 22
23
3 - 15mA
LOGIC C0
06
K oyo
X1 X0
X3 X2
X4 C1
X6 X5
X7
C2 X11 X13 X14 X16 C4 X21 X23 N.C. X15 X17 X20 X22 N.C. X10 X12 C3
DC Supply
DC Pulse Outputs (Y0 - Y1)
High Speed Inputs (X0-X3)
Input
+
Internal module circuitry +V
+V
+V +
Optical Isolator
Derating Chart for DC Outputs
To LED
L
–
Optical Isolator
+
Points
Common
OUTPUT
To LED
16
0.75A
COM
Y0 - Y17
12
1.0 A
8
Standard Input Circuit (X4-X23) +V
Input +
+V
Optical Isolator
DC Standard Outputs (Y2 - Y17)
4 0
+V 0 32
10 50
20 68
30 86
40 104
50 55˚C 122 131˚F
Ambient Temperature ( ˚C/ ˚F) L
To LED
OUTPUT
+
–
Common COM
2–38
Internal module circuitry
+
DL06 Micro PLC User Manual, 3rd Edition Rev. A
Optical Isolator
To LED
Page 79
Chapter 2: Installation, Wiring, and Specifications D0-06DD1-D General Specifications External Power Requirements Communication Port 1: 9600 baud (Fixed), 8 data bits, 1 stop bit, odd parity Communication Port 2: 9600 baud (default), 8 data bits, 1 stop bit,odd parity Programming cable type Operating Temperature Storage Temperature Relative Humidity Environmental air Vibration Shock Noise Immunity Terminal Type Wire Gauge
12 – 24 VDC, 20 W maximum, K–Sequence (Slave), DirectNET (Slave), MODBUS (Slave) K–Sequence (Slave), DirectNET (Master/Slave), MODBUS (Master/Slave), Non-sequence/print, ASCII in/out D2–DSCBL 32 to 131° F (0 to 55° C) –4 to 158° F (–20 to 70° C) 5 to 95% (non-condensing) No corrosive gases permitted MIL STD 810C 514.2 MIL STD 810C 516.2 NEMA ICS3–304 Removable One 16 AWG or two 18 AWG, 24 AWG minimum
DC Input Specifications Parameter Min. - Max. Voltage Range Operating Voltage Range Peak Voltage Minimum Pulse Width ON Voltage Level OFF Voltage Level Max. Input Current Input Impedance Minimum ON Current Maximum OFF Current OFF to ON Response ON to OFF Response Status Indicators Commons
High–Speed Inputs, X0 – X3
Standard DC Inputs X4 – X23
10.8 – 26.4 VDC 10.8 – 26.4 VDC 12 – 24 VDC 12 – 24 VDC 30 VDC (7 kHz maximum frequency) 30 VDC 70 µs N/A >10.0 VDC > 10.0 VDC < 2.0 VDC < 2.0 VDC 6mA @12VDC, 13mA @24VDC 4mA @12VDC, 8.5mA @24VDC 1.8 @ 12 – 24 VDC 2.8 @ 12 – 24 VDC >5 mA >4 mA < 0.5 mA <0.5 mA <70 µs 2 – 8 ms, 4 ms typical <70 µs 2 – 8 ms, 4 ms typical Logic side Logic side 4 channels / common x 5 banks (isolated)
DC Output Specifications Parameter Min. - Max. Voltage Range Operating Voltage Peak Voltage On Voltage Drop Max Current (resistive) Max leakage current Max inrush current External DC power required OFF to ON Response ON to OFF Response Status Indicators Commons Fuses
Pulse Outputs, Y0 – Y1
Standard Outputs, Y2 – Y17
5 – 30 VDC 5 – 30 VDC 6 – 27 VDC 6 – 27 VDC < 50 VDC (10 kHz max. frequency) < 50 VDC 0.3 VDC @ 1 A 0.3 VDC @ 1 A 0.5 A / pt., 1A / pt. as standard pt. 1.0 A / point 15 µA @ 30 VDC 15 µA @ 30 VDC 2 A for 100 ms 2 A for 100 ms 20 - 28 VDC Max 150mA 20 - 28 VDC Max 150mA < 10 µs < 10 µs < 20 µs < 60 µs Logic Side Logic Side 4 channels / common x 4 banks (non-isolated) None (external recommended)
DL06 Micro PLC User Manual, 3rd Edition Rev. A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
2–39