Page 80

Chapter 2: Installation, Wiring, and Specifications

D0–06DD2–D I/O Wiring Diagram

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

These micro PLCs feature twenty DC inputs and sixteen sourcing DC outputs. The following diagram shows a typical field wiring example. The DC external power connection uses four terminals at the left as shown. Inputs are organized into five banks of four. Each bank has an isolated common terminal, and may be wired as either sinking or sourcing inputs. The wiring example below shows all commons connected together, but separate supplies and common circuits may be used. All outputs actually share the same common. Note the requirement for external power. 12 - 24 VDC

-

+

+ +24 VDC

L L L L

G

LG

+

X

0

1

2

3

INPUT: 12 - 24V

L L L L

L L L L

N.C. Y0 Y2 V1 Y5 Y7 Y10 Y12 V3 Y15 Y17 N.C. V0 Y1 Y3 Y4 Y6 V2 Y11 Y13 Y14 Y16 C0

-

6 - 27V

OUTPUT: Sinking Output

Y

L L L L

4

5

1.0A 6

7

PWR: 12-24 10

11

12

13

20W 14

15

16

17

20

D0-06DD2-D 23

21 22

3 - 15mA

LOGIC C0

06

K oyo

X1 X0

X3 X2

X4 C1

X6 X5

X7

C2 X11 X13 X14 X16 C4 X21 X23 N.C. X15 X17 X20 X22 N.C. X10 X12 C3

DC Supply

DC Pulse Outputs (Y0 - Y1)

High Speed Inputs (X0-X3)

Internal module circuitry

+V

Input

+

Optical Isolator

V0 - V3

V0 - V3

To LED

+ -

–

Output

Common

Derating Chart for DC Outputs

To LED

L

Optical Isolator C0

Points 16

+V

Input +

0.75A

12

Standard Input Circuit (X4-X23)

1.0 A

Y0 - Y7 Y10 - Y17

DC Standard Outputs (Y2 - Y17)

8

+V

Internal module circuitry

4 0

Optical Isolator To LED

V0 - V3

+ 0 32

10 50

20 68

30 86

40 104

50 55˚C 122 131˚F

Ambient Temperature ( ˚C/ ˚F)

To LED

Output L

–

C0

Common

Optical Isolator

2–40

DL06 Micro PLC User Manual, 3rd Edition Rev. A

Page 81

Chapter 2: Installation, Wiring, and Specifications D0-06DD2-D General Specifications External Power Requirements Communication Port 1: 9600 baud (Fixed), 8 data bits, 1 stop bit, odd parity Communication Port 2: 9600 baud (default), 8 data bits, 1 stop bit,odd parity Programming cable type Operating Temperature Storage Temperature Relative Humidity Environmental air Vibration Shock Noise Immunity Terminal Type Wire Gauge

12 – 24 VDC, 20 W maximum, K–Sequence (Slave), DirectNET (Slave), MODBUS (Slave) K–Sequence (Slave), DirectNET (Master/Slave), MODBUS (Master/Slave), Non-sequence/print, ASCII in/out D2–DSCBL 32 to 131° F (0 to 55° C) –4 to 158° F (–20 to 70° C) 5 to 95% (non-condensing) No corrosive gases permitted MIL STD 810C 514.2 MIL STD 810C 516.2 NEMA ICS3–304 Removable One 16 AWG or two 18 AWG, 24 AWG minimum

DC Input Specifications Parameter Min. - Max. Voltage Range Operating Voltage Range Peak Voltage Minimum Pulse Width ON Voltage Level OFF Voltage Level Max. Input Current Input Impedance Minimum ON Current Maximum OFF Current OFF to ON Response ON to OFF Response Status Indicators Commons

High–Speed Inputs, X0 – X3

Standard DC Inputs X4 – X23

10.8 – 26.4 VDC 10.8 – 26.4 VDC 12 – 24 VDC 12 – 24 VDC 30 VDC (7 kHz maximum frequency) 30 VDC 70 µs N/A >10.0 VDC > 10.0 VDC < 2.0 VDC < 2.0 VDC 15mA @26.4VDC 11mA @26.4VDC 1.8 @ 12 – 24 VDC 2.8 @ 12 – 24 VDC 5 mA 3 mA 0.5 mA 0.5 mA <70 µs 2 – 8 ms, 4 ms typical <70 µs 2 – 8 ms, 4 ms typical Logic side Logic side 4 channels / common x 5 banks (isolated)

DC Output Specifications Parameter Min. - Max. Voltage Range Operating Voltage Peak Voltage On Voltage Drop Max Current (resistive) Max leakage current Max inrush current External DC power required OFF to ON Response ON to OFF Response Status Indicators Commons Fuses

Pulse Outputs, Y0 – Y1

Standard Outputs, Y2 – Y17

10.8 – 26.4 VDC 10.8 – 26.4 VDC 12 – 24 VDC 12 – 24 VDC 30 VDC (10 kHz max. frequency) 30 VDC 0.5 VDC @ 1 A 1.2 VDC @ 1 A 0.5 A / pt., 1A / pt. as standard pt. 1.0 A / point 15 µA @ 30 VDC 15 µA @ 30 VDC 2 A for 100 ms 2 A for 100 ms 12 – 24 VDC N/A < 10 µs < 10 µs < 20 µs < 0.5 ms Logic Side Logic Side 4 channels / common x 4 banks (non-isolated) None (external recommended)

DL06 Micro PLC User Manual, 3rd Edition Rev. A

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

2–41

Page 82

Chapter 2: Installation, Wiring, and Specifications

D0–06DR–D I/O Wiring Diagram

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

The D0–06DR–D PLC has twenty DC inputs and sixteen relay contact outputs. The following diagram shows a typical field wiring example. The DC external power connection uses three terminals as shown. Inputs are organized into five banks of four. Each bank has an isolated common terminal, and may be wired as either sinking or sourcing inputs. The wiring example above shows all commons connected together, but separate supplies and common circuits may be used. Outputs are organized into four banks of four normally-open relay contacts. Each bank has a common terminal. The wiring example above shows all commons connected together, but separate supplies and common circuits may be used. The equivalent output circuit shows one channel of a typical bank. The relay contacts can switch AC or DC voltages. 12 - 24 VDC

-

+

Typical Relay Life (Operations) at Room Temperature

AC or DC Supply L L L L

Voltage & Load Type 24VDC Resistive 24VDC Inductive 110VAC Resistive 110VAC Inductive 220VAC Resistive 220VAC Inductive

500K 100K 500K 200K 350K 100K

250K 50K 250K 100K 200K 50K

+

G

LG

-

OUTPUT: 6-240V

Y

X

0

1

2

L L L L

L L L L

Y0 - Y7 Y10 - Y17

12

C0

5

2.0A, 6 - 27V 6

7

10

2.0A

11

12

13

PWR: 12-24 14

15

16

20W 17

20

D0-06DR-D

21 22

23

06

K oyo

X1 X0

8

4

3 - 15mA

LOGIC 2.0A

N.C. Y0 Y2 C1 Y5 Y7 Y10 Y12 C3 Y15 Y17 N.C. C0 Y1 Y3 Y4 Y6 C2 Y11 Y13 Y14 Y16 N.C.

50 - 60Hz 3

INPUT: 12 - 24V

Points 16

L L L L

Load Current At 1A At 2A

X3 X2

X4 C1

X6 X5

X7

C2 X11 X13 X14 X16 C4 X21 X23 N.C. X15 X17 X20 X22 N.C. X10 X12 C3

4 0 0 32

10 50

20 68

30 86

40 104

50 122

55˚C 131˚F

Ambient Temperature ( ˚C/ ˚F)

Derating Chart for Relay Outputs

DC Supply

+V +V

Input

+

Optical Isolator

Input

–

Optical Isolator

+ To LED

+V

Internal module circuitry +V

L

To LED

Output

–

Common Common

Common

High-speed Input Circuit (X0-X3)

2–42

Standard Input Circuit (X4-X23)

DL06 Micro PLC User Manual, 3rd Edition Rev. A

To LED

Standard Output Circuit

Page 83

Chapter 2: Installation, Wiring, and Specifications D0-06DR-D General Specifications External Power Requirements Communication Port 1 9600 baud (Fixed), 8 data bits, 1 stop bit, odd parity Communication Port 2 9600 baud (default), 8 data bits, 1 stop bit, odd parity Programming cable type Operating Temperature Storage Temperature Relative Humidity Environmental air Vibration Shock Noise Immunity Terminal Type Wire Gauge

12 – 24 VDC, 20 W maximum, K–Sequence (Slave), DirectNET (Slave), MODBUS (Slave) K–Sequence (Slave), DirectNET (Master/Slave), MODBUS (Master/Slave),Non-sequence/print, ASCII in/out D2–DSCBL 32 to 131° F (0 to 55° C) –4 to 158° F (–20 to 70° C) 5 to 95% (non-condensing) No corrosive gases permitted MIL STD 810C 514.2 MIL STD 810C 516.2 NEMA ICS3–304 Removable One 16 AWG or two 18AWG, 24AWG minimum

DC Input Specifications Parameter Min. - Max. Voltage Range Operating Voltage Range Peak Voltage Minimum Pulse Width ON Voltage Level OFF Voltage Level Input Impedance Max. Input Current Minimum ON Current Maximum OFF Current OFF to ON Response ON to OFF Response Status Indicators Commons

High–Speed Inputs, X0 – X3

Standard DC Inputs X4 – X23

10.8 – 26.4 VDC 10.8 – 26.4 VDC 12 -24 VDC 12 -24 VDC 30 VDC (7 kHz maximum frequency) 30 VDC 70 µs N/A > 10 VDC > 10 VDC < 2.0 VDC < 2.0 VDC 1.8 @ 12 – 24 VDC 2.8 @ 12 – 24 VDC 6mA @12VDC 13mA @24VDC 4mA @12VDC 8.5mA @24VDC >5 mA >4 mA < 0.5 mA <0.5 mA <70 µs 2 – 8 ms, 4 ms typical < 70 µs 2 – 8 ms, 4 ms typical Logic side Logic side 4 channels / common x 5 banks (isolated)

Relay Output Specifications Output Voltage Range (Min. - Max.) Operating Voltage Output Current Maximum Voltage Max leakage current Smallest Recommended Load OFF to ON Response ON to OFF Response Status Indicators Commons Fuses

5 -264 VAC (47 -63 Hz), 5 - 30 VDC 6 -240 VAC (47 -63 Hz), 6 - 27 VDC 2A / point 6A / common 264 VAC, 30 VDC 0.1 mA @264 VAC 5 mA < 15 ms < 10 ms Logic Side 4 channels / common x 4 banks isolated commons None (external recommended)

DL06 Micro PLC User Manual, 3rd Edition Rev. A

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

2–43

Page 84

Chapter 2: Installation, Wiring, and Specifications

Glossary of Specification Terms

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 2–44

Discrete Input One of twenty input connections to the PLC which converts an electrical signal from a field device to a binary status (off or on), which is read by the internal CPU each PLC scan.

Discrete Output One of sixteen output connections from the PLC which converts an internal ladder program result (0 or 1) to turn On or Off an output switching device. This enables the program to turn on and off large field loads.

I/O Common A connection in the input or output terminals which is shared by multiple I/O circuits. It usually is in the return path to the power supply of the I/O circuit.

Input Voltage Range The operating voltage range of the input circuit.

Maximum Voltage Maximum voltage allowed for the input circuit.

ON Voltage Level The minimum voltage level at which the input point will turn ON.

OFF Voltage Level The maximum voltage level at which the input point will turn OFF

Input Impedance Input impedance can be used to calculate input current for a particular operating voltage.

Input Current Typical operating current for an active (ON) input.

Minimum ON Current The minimum current for the input circuit to operate reliably in the ON state.

Maximum OFF Current The maximum current for the input circuit to operate reliably in the OFF state.

OFF to ON Response The time the module requires to process an OFF to ON state transition.

ON to OFF Response The time the module requires to process an ON to OFF state transition.

Status Indicators The LEDs that indicate the ON/OFF status of an input or output point. All LEDs on DL06 Micro PLCs are electrically located on the logic side of the input or output circuit.

DL06 Micro PLC User Manual, 3rd Edition Rev. A

Page 85

CPU SPECIFICATIONS AND OPERATION

CHAPTER

3

In This Chapter Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3–2 CPU Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3–3 CPU Hardware Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3–4 Using Battery Backup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3–8 CPU Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3–12 I/O Response Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3–17 CPU Scan Time Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . .3–20 Memory Map . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3–25 DL06 System V-memory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3–29 DL06 Aliases . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3–31 DL06 Memory Map . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3–32 X Input/Y Output Bit Map . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3–33 Stage Control/Status Bit Map . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3–34 Control Relay Bit Map . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3–36 Timer Status Bit Map . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3–38 Counter Status Bit Map . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3–38 GX and GY I/O Bit Map . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3–39

Page 86

Chapter 3: CPU Specifications and Operation

Introduction

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 3–2

The Central Processing Unit (CPU) is the heart of the Micro PLC. Almost all PLC operations are controlled by the CPU, so it is important that it is set up correctly. This chapter provides the information needed to understand: • Steps required to set up the CPU • Operation of ladder programs • Organization of Variable Memory Power Input

16 Discrete Outputs

Output circuit

Power Supply

CPU

LCD monitor

4 Optional card slots

Isolation boundary

Input circuit

20 discrete Inputs

2 comm. ports

To programming device or Operator interface

NOTE: The High-Speed I/O function (HSIO) consists of dedicated but configurable hardware in the DL06. It is not considered part of the CPU, because it does not execute the ladder program. For more on HSIO operation, see Appendix E.

DL06 CPU Features The DL06 Micro PLC has 14.8K words of memory comprised of 7.6K of ladder memory and 7.6K words of V-memory (data registers). Program storage is in the FLASH memory which is a part of the CPU board in the PLC. In addition, there is RAM with the CPU which will store system parameters, V-memory, and other data which is not in the application program. The RAM is backed up by a “super-capacitor”, storing the data for several hours in the event of a power outage. The capacitor automatically charges during powered operation of the PLC. The DL06 supports fixed I/O which includes twenty discrete input points and sixteen output points. Over 220 different instructions are available for program development as well as extensive internal diagnostics that can be monitored from the application program or from an operator interface. Chapters 5, 6, and 7 provide detailed descriptions of the instructions. The DL06 provides two built-in communication ports, so you can easily connect a handheld programmer, operator interface, or a personal computer without needing any additional hardware.

DL06 Micro PLC User Manual, 3rd Edition Rev. A

Page 87

Chapter 3: CPU Specifications and Operation

CPU Specifications Specifications Feature Total Program memory (words) Ladder memory (words) Total V-memory (words) User V-memory (words) Non-volatile V Memory (words) Contact execution (boolean) Typical scan (1k boolean) RLL Ladder style Programming RLL and RLLPLUS Programming Run Time Edits Scan Handheld programmer Direct SOFT 5 programming for Windows Built-in communication ports (RS232C) FLASH Memory Local Discrete I/O points available Local Analog input / output channels maximum High-Speed I/O (quad., pulse out, interrupt, pulse catch, etc.) I/O Point Density Number of instructions available (see Chapter 5 for details) Control relays Special relays (system defined) Stages in RLLPLUS Timers Counters Immediate I/O Interrupt input (external / timed) Subroutines For/Next Loops Math (Integer and floating point) Drum Sequencer Instruction Time of Day Clock/Calendar Internal diagnostics Password security System error log User error log Battery backup

DL06 14.8K 7680 7616 7488 128 <0.6us 1-2ms Yes Yes Yes Variable / fixed Yes Yes Yes Standard on CPU 36 None Yes, 2 20 inputs, 16 outputs 229 1024 512 1024 256 128 Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Optional D2-BAT-1 available (not included with unit)

DL06 Micro PLC User Manual, 3rd Edition Rev. A

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 3–3

Page 88

Chapter 3: CPU Specifications and Operation

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

CPU Hardware Setup

3–4

Communication Port Pinout Diagrams Cables are available that allow you to quickly and easily connect a Handheld Programmer or a personal computer to the DL06 PLCs. However, if you need to build your a cable(s), use the pinout descriptions shown below, or use the Tech Support/Cable Wiring Diagrams located on our website. The DL06 PLCs require an RJ-12 phone plug for port 1 (D2-DSCBL) and a 15pin SVGA DSub for port 2 (D2-DSCBL-1). The DL06 PLC has two built-in serial communication ports. Port 1 (RS232C only) is generally used for connecting to a D2-HPP, Direct SOFT 5, operator interface, MODBUS slave only, or a Direct NET slave only. The baud rate is fixed at 9600 baud for port 1. Port 2 (RS232C/RS422/RS485) can be used to connect to a D2-HPP, Direct SOFT 5, operator interface, MODBUS master/slave, Direct NET master/slave or ASCII in/out. Port 2 has a range of speeds from 300 baud to 38.4K baud. Port 1 Pin Descriptions 1 2 3 4 5 6

Port 2 Pin Descriptions

0V Power (-) connection (GND) 5V Power (+) 200 mA max RXD Receive data (RS-232C) TXD Transmit data (RS-232C) 5V Power (+) connection 0V Power (-) connection (GND) TERM PORT1

6

5 4 3 2

PORT2

1

RUN STOP

5

1 10

6

15

PORT1

11

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

PORT2

Communications Port 1 Connects to HPP, DirectSOFT 5, operator interfaces, etc. 6-pin, RS232C Communication speed (baud): 9600 (fixed) Parity: odd (fixed) Com 1 Station Address: 1 (fixed) 8 data bits 1 start, 1 stop bit Asynchronous, half-duplex, DTE Protocol (auto-select): K-sequence (slave only), DirectNET (slave only), MODBUS (slave only)

5V Power (+) connection TXD Transmit data (RS-232C) RXD Receive data (RS-232C) RTS Ready to send CTS Clear to send RXD- Receive data (-) (RS-422/485) 0V Power (-) connection (GND) 0V Power (-) connection (GND) TXD+ Transmit data (+) (RS-422/485) TXD- Transmit data (-) (RS-422/485) RTS+ Ready to send (+) (RS-422/485) RTS- Ready to send (-) (RS-422/485) RXD+ Receive data (+) (RS-422/485) CTS+ Clear to send (+) (RS-422/485) CTS- Clear to send (-) (RS-422/485)

Communications Port 2 Connects to HPP, DirectSOFT 5, operator interfaces, etc. 15-pin, multifunction port, RS232C, RS422, RS485 (RS485 with 2-wire is only available for MODBUS and Non-sequence.) Communication speed (baud): 300, 600, 1200, 2400, 4800, 9600, 19200, 38400 Parity: odd (default), even, none Com 2 Station Address: 1 (default) 8 data bits 1 start, 1 stop bit Asynchronous, half-duplex, DTE Protocol (auto-select): K-sequence (slave only), DirectNET (master/slave), MODBUS (master/slave), non-sequence/print/ASCII in/out

DL06 Micro PLC User Manual, 3rd Edition Rev. A

Page 89

Chapter 3: CPU Specifications and Operation

Connecting the Programming Devices If you’re using a Personal Computer with the DirectSOFT 5 programming package, you can connect the computer to either of the DL06’s serial ports. For an engineering office environment (typical during program development), this is the preferred method of programming.

1 2 3 4 5 6 The Handheld programmer D2-HPP is connected to the CPU with a handheld programmer cable. This device is ideal for maintaining existing installations or making small program 7 changes. The handheld programmer is shipped with a cable, which is approximately 6.5 feet (200 cm) long. 8 9 10 11 12 CPU Setup Information Even if you have years of experience using PLCs, there are a few things you need to do before 13 you can start entering programs. This section includes some basic things, such as changing the CPU mode, but it also includes some things that you may never have to use. Here’s a brief list of the items that are discussed: 14 • Using Auxiliary Functions • Clearing the program (and other memory areas) A • How to initialize system memory • Setting retentive memory ranges B The following paragraphs provide the setup information necessary to get the CPU ready for programming. They include setup instructions for either type of programming device you are C using. The D2–HPP Handheld Programmer Manual provides the Handheld keystrokes required to perform all of these operations. The DirectSOFT 5 Manual provides a description D of the menus and keystrokes required to perform the setup procedures via DirectSOFT 5. G LG Y0 Y2 C1 Y5 Y7 Y10 Y12 C3 Y15 Y17 0V AC(L) AC(N) 24V C0 Y1 Y3 Y4 Y6 C2 Y11 Y13 Y14 Y16 N.C.

OUTPUT: 6-240V

Y

X

0

1

2

50 - 60Hz

3

INPUT: 12 - 24V

4

5

2.0A, 6 - 27V 6

7

10

2.0A

11

12

PWR: 100-240V

13

14

15

16

PWR RUN CPU TX1 RX1 TX2 RX2

50-60Hz 40VA

17

20

D0-06DR

21 22

23

3 - 15mA

LOGIC C0

06

K oyo

X1

X0

X3

X2

X4

C1

X6

X5

X7

C2 X11 X13 X14 X16 C4 X21 X23 N.C. X10 X12 C3 X15 X17 X20 X22 N.C.

TERM

PORT1

PORT2

RUN STOP

Use cable part no. D2–DSCBL

0V G LG Y0 Y2 C1 Y5 Y7 Y10 Y12 C3 Y15 Y17 AC(L) AC(N) 24V C0 Y1 Y3 Y4 Y6 C2 Y11 Y13 Y14 Y16 N.C.

OUTPUT: 6-240V

Y

X

0

1

2

50 - 60Hz

3

INPUT: 12 - 24V

4

5

2.0A, 6 - 27V 6

7

10

2.0A

11

12

PWR: 100-240V

13

14

15

16

PWR RUN CPU TX1 RX1 TX2 RX2

50-60Hz 40VA

17

20

D0-06DR

21 22

23

3 - 15mA

LOGIC C0

06

K oyo

X1

X0

X3

X2

X4

C1

X6

X5

X7

C2 X11 X13 X14 X16 C4 X21 X23 N.C. X15 X17 X20 X22 N.C. X10 X12 C3

TERM

PORT1

PORT2

RUN STOP

For replacement cable, use part no. DV–1000CBL

DL06 Micro PLC User Manual, 3rd Edition Rev. A

3–5