For the AutomationDirect Direct Logic DL06

Page 250

Appendix D: Special Relays

Counter 2 Mode 10 Equal Relays

1 2 3 D 5 6 7 8 9 10 11 12 13 14 A B C D

SP570 SP571 SP572 SP573 SP574 SP575 SP576 SP577 SP600 SP601 SP602 SP603 SP604 SP605 SP606 SP607 SP610 SP611 SP612 SP613 SP614 SP615 SP616 SP617

D–6

Current = target value

On when the counter current value equals the value in V3711/3710

Current = target value

On when the counter current value equals the value in V3713/3712

Current = target value

On when the counter current value equals the value in V3715/3714

Current = target value

On when the counter current value equals the value in V3717/3716

Current = target value

On when the counter current value equals the value in V3721/3720

Current = target value

On when the counter current value equals the value in V3723/3722

Current = target value

On when the counter current value equals the value in V3725/3724

Current = target value

On when the counter current value equals the value in V3727/3726

Current = target value

On when the counter current value equals the value in V3731/3730

Current = target value

On when the counter current value equals the value in V3733/3732

Current = target value

On when the counter current value equals the value in V3735/3734

Current = target value

On when the counter current value equals the value in V3737/3736

Current = target value

On when the counter current value equals the value in V3741/3740

Current = target value

On when the counter current value equals the value in V3743/3742

Current = target value

On when the counter current value equals the value in V3745/3744

Current = target value

On when the counter current value equals the value in V3747/3746

Current = target value

On when the counter current value equals the value in V3751/3750

Current = target value

On when the counter current value equals the value in V3753/3752

Current = target value

On when the counter current value equals the value in V3755/3754

Current = target value

On when the counter current value equals the value in V3757/3756

Current = target value

On when the counter current value equals the value in V3761/3760

Current = target value

On when the counter current value equals the value in V3763/3762

Current = target value

On when the counter current value equals the value in V3765/3764

Current = target value

On when the counter current value equals the value in V3767/3766

DL06 Micro PLC User Manual, 3rd Edition Rev. A

Page 251

HIGH-SPEED INPUT AND PULSE OUTPUT FEATURES

A PPENDIX

E

In This Appendix Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .E–2 Choosing the HSIO Operating Mode . . . . . . . . . . . . . . . . . . . . . . .E–4 Mode 10: High-Speed Counter . . . . . . . . . . . . . . . . . . . . . . . . . . .E–7 Mode 20: Up/Down Counter . . . . . . . . . . . . . . . . . . . . . . . . . . . .E–24 Presets and Special Relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .E–27 Mode 30: Pulse Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .E–38 Mode 40: High-Speed Interrupts . . . . . . . . . . . . . . . . . . . . . . . . .E–64 Mode 50: Pulse Catch Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . .E–69 Mode 60: Discrete Inputs with Filter . . . . . . . . . . . . . . . . . . . . . . .E–73

Page 252

Appendix E: High-speed Input and Pulse Output Features

Introduction

1 2 3 4 E 6 7 8 9 10 11 12 13 14 A B C D

Built-in Motion Control Solution Many machine control applications require various types of simple high-speed monitoring and control. These applications usually involve some type of motion control, or high-speed interrupts for time-critical events. The DL06 Micro PLC solves this traditionally expensive problem with built-in CPU enhancements. Let’s take a closer look at the available high-speed I/O features. The available high-speed input features are: • High Speed Counter (7 kHz max.) with up to 24 counter presets and built-in interrupt subroutine, counts up only, with reset • Quadrature encoder inputs to measure counts and clockwise or counter clockwise direction (7 kHz max.), counts up or down, with reset • High-speed interrupt inputs for immediate response to critical or time-sensitive tasks • Pulse catch feature to monitor one input point, having a pulse width as small as 100µs (0.1ms) • Programmable discrete filtering (both on and off delay up to 99ms) to ensure input signal integrity (this is the default mode for inputs X0–X3)

The available pulse output features are: • Single-axis programmable pulse output (10 kHz max.) with three profile types, including trapezoidal moves, registration, and velocity control

Availability of HSIO Features IMPORTANT: Please note the following restrictions on availability of features: • High-speed input options are available only on DL06s with DC inputs. • Pulse output options are available only on DL06s with DC outputs. • Only one HSIO feature may be in use at one time. You cannot use a high–speed input feature and the pulse output at the same time.

Specifications DL06 Part Number D0–06AA D0–06AR D0–06DA D0–06DD1 D0–06DD2 D0–06DR D0–06DD1–D D0–06DD2–D D0–06DR–D

E–2

Discrete Input Type Discrete Output Type AC AC DC DC DC DC DC DC DC

AC Relay AC DC DC Relay DC DC Relay

DL06 Micro PLC User Manual, 3rd Edition Rev. A

High-Speed Input

Pulse Output

No No Yes Yes Yes Yes Yes Yes Yes

No No No Yes Yes No Yes Yes No

Page 253

Appendix E: High-speed Input and Pulse Output Features

Dedicated High- Speed I/O Circuit The internal CPU’s main task is to execute the ladder program and read/write all I/O points during each scan. In order to service high-speed I/O events, the DL06 includes a special circuit which is dedicated to a portion of the I/O points. Refer to the DL06 block diagram in the figure below.

1 2 3 4 E 6 7 The high-speed I/O circuit (HSIO) is dedicated to the first four inputs (X0 – X3) and the 8 first two outputs (Y0 – Y1). We might think of this as a “CPU helper”. In the default operation (called “Mode 60”) the HSIO circuit just passes through the I/O signals to or from 9 the CPU, so that all twenty inputs behave equally and all sixteen outputs behave equally. When the CPU is configured in any other HSIO Mode, the HSIO circuit imposes a specialized function on the portion of inputs and outputs shown. The HSIO circuit operates 10 independently of the CPU program scan. This provides accurate measurement and capturing of high-speed I/O activity while the CPU is busy with ladder program execution. 11 Wiring Diagrams for Each HSIO Mode After choosing the appropriate HSIO mode for your application, you’ll need to refer to the section in this appendix for that specific mode. Each section includes wiring diagrams to help 12 you connect the High-Speed I/O points correctly to field devices. An example of a High Speed Counter mode diagram is shown below. 13 14 A B C D 16 Discrete Outputs

DL06 PLC

Output Circuit

Y0, Y1

High-Speed I/O Circuit

X0 - X3

Y2 - Y17

CPU

X4 - X23

Input Circuit

20 Discrete Inputs

C0

X1

X0

X3

X2

X4

C1

X6

X5

X7

C2 X11 X13 X14 X16 C4 X21 X23 N.C. X15 X17 X20 X22 N.C. X10 X12 C3

TERM

PORT1

PORT2

RUN STOP

Counter Input Wiring Signal

–

+

Signal Common

12-24 VDC Supply

DL06 Micro PLC User Manual, 3rd Edition Rev. A

E–3

Page 254

Appendix E: High-speed Input and Pulse Output Features

Choosing the HSIO Operating Mode

1 2 3 4 E 6 7 8 9 10 11 12 13 14 A B C D E–4

Understanding the Six Modes The High-Speed I/O circuit operates in one of 6 basic modes as listed in the table below. The number in the left column is the mode number (later, we’ll use these numbers to configure the PLC). Choose one of the following modes according to the primary function you want from the dedicated High-Speed I/O circuit. You can simply use all twenty inputs and sixteen outputs as regular I/O points with Mode 60. High Speed I/O Basic Modes Mode 10

High-Speed Counter

20

Up/Down Counter

Mode Features Two 7 kHz counters with 24 presets and reset input, counts up only, cause interrupt on preset 7 kHz up/down counter with 24 presets and reset, causes interrupt on preset Channel A / Channel B 7 kHz quadrature input, counts up and down

30

Pulse Output

40 50 60

High-Speed Interrupt Pulse Catch Filtered Input

Stepper control – pulse and direction signals, programmable motion profile (10kHz max.) Generates an interrupt based on input transition or time Captures narrow pulses on a selected input Rejects narrow pulses on selected inputs

In choosing one of the six high-speed I/O modes, the I/O points listed in the table below operate only as the function listed. If an input point is not specifically used to support a particular mode, it usually operates as a filtered input by default. Similarly, output points operate normally unless Pulse Output mode is selected.

DL06 Micro PLC User Manual, 3rd Edition Rev. A

Page 255

Appendix E: High-speed Input and Pulse Output Features

Physical I/O Point Usage Mode

10

20

30 40

X0

High-Speed Counter Counter #1

DC Input Points X1 X2

X3

DC Output Points Y0 Y1

Counter #2, Reset #1, Reset #2, Regular Interrupt, Interrupt, Interrupt, Pulse Input or Pulse Input or Pulse Input or Output Filtered Input Filtered Input Filtered Input

Up/Down counter Down (Standard counting) Up Counting Counting Up/Down counter Phase A (Quadrature counting) Input Pulse Output

Pulse Input Pulse Input or Pulse Input or Pulse Input or Pulse or or Filtered Filtered Input Filtered Input Filtered Input CW Pulse Input

Pulse Catch

60

Filtered Input

Regular Output

Direction or CCW Pulse

Interrupt, Interrupt, Interrupt, Pulse Input or Pulse Input or Pulse Input or Regular Filtered Input Filtered Input Filtered Input Output

Regular Output

Pulse Input, Pulse Input, Pulse Input, Pulse Input Interrupt or Interrupt or Interrupt or Regular Filtered Input Filtered Input Filtered Input Output Filtered Input Filtered Input Filtered Input Filtered Input Regular Output

Regular Output

High-Speed Interrupt Interrupt

50

Reset, Input or Regular Pulse Input or Pulse Filtered Input Output Filtered Input Phase B Input

Regular Output

Regular Output

Default Mode Mode 60 (Filtered Inputs) is the default mode. The DL06 is initialized to this mode at the factory, and any time you initialize the scratchpad memory. In the default condition, X0–X3 are filtered inputs (10 ms delay) and Y0–Y1 are standard outputs.

DL06 Micro PLC User Manual, 3rd Edition Rev. A

1 2 3 4 E 6 7 8 9 10 11 12 13 14 A B C D

E–5

Page 256

Appendix E: High-speed Input and Pulse Output Features

Configuring the HSIO Mode

1 2 3 4 E 6 7 8 9 10 11 12 13 14 A B C D E–6

If you have chosen a mode suited to the high-speed I/O needs of your application, we’re ready to proceed to configure the PLC to operate accordingly. In the block diagram below, notice the V-memory detail in the expanded CPU block. V-memory location V7633 determines the functional mode of the high-speed I/O circuit. This is the most important V-memory configuration value for HSIO functions! Output Circuit

DL06 PLC

Y0 - Y1

Y2 - Y17

CPU

I/O Data

High-Speed I/O Circuit

V-Memory

Mode Select

V7633

X0 - X3 xxxx

X4 - X23

Input Circuit

The contents of V7633 is a 16-bit word, to be entered in binary–coded decimal. The figure below defines what each 4-bit BCD digit of the word represents. Memory Location V7633 Bits

15

14

13

12 11

10

9

8

7

6

5

4

3

2

1

0

0

0

0

0

0

0

0

0

1

0

1

0

0

0

0

0

0

0

5

0

Miscellaneous Setup (BCD)

HSIO Mode Setup (BCD)

00 = Not Used (default) 10 = Battery Enabled 20 = Power-up in RUN 30 = Battery Enabled and Power-up in RUN

00 = Not Used 10 = High-Speed Counter 20 = Up/Down Counter 30 = Pulse Output 40 = High-Speed Interrupts 50 = Pulse Catch 60 = Filtered Inputs (default)

Bits 0 – 7 define the mode number 00, 10.. 60 previously referenced in this appendix. The example data “0050” shown selects Mode 50 – Pulse Catch (BCD = 50).

Configuring Inputs X0 – X3 In addition to configuring V7633 for the HSIO mode, you’ll need to program the next four locations in certain modes according to the desired function of input points X0 – X3. Other memory locations may require configuring, depending on the HSIO mode (see the corresponding section for particular HSIO modes).

DL06 Micro PLC User Manual, 3rd Edition Rev. A

V-Memory Mode X0 X1 X2 X3

V7633 V7634 V7635 V7636 V7637 xxxx xxxx xxxx xxxx xxxx

Page 257

Appendix E: High-speed Input and Pulse Output Features

Mode 10: High-Speed Counter

1 The HSIO circuit contains two high-speed counters. A single pulse train from an external 2 source (X0) clocks the counter on each signal leading edge. The counter counts only upwards, from 0 to 99999999. The counter compares the current count with up to 24 preset values, 3 which you define. The purpose of the presets is to quickly cause an action upon arrival at specific counts, making it ideal for such applications as cut-to-length. It uses counter registers CT174 to CT177 in the CPU. 4 Functional Block Diagram Refer to the block diagram below. When the lower byte of HSIO Mode register V7633 E contains a BCD “10”, the high-speed up counter in the HSIO circuit is enabled. X0 and X1 automatically become the “clock” inputs for the high-speed counters, incrementing them 6 upon each off-to-on transition. The external reset input on X2 and X3 are the default configuration for Mode 10. 7 8 9 10 11 12 Instead of using X2 and X3 as dedicated reset inputs, you can configure X2 and X3 as normal filtered inputs. In this way, the counter reset must be generated in ladder logic. 13 14 A B C D Purpose

Output Circuit

DL06 PLC

Y2 - Y17

Y0 - Y1

HSIO

Counter 1

Counter 2

CLK Reset X0

I/O data

X2

CLK Reset X1

Mode Select

Filter

CPU

V-memory

V7633

0010

X4 - X23

X3

Input Circuit

Output Circuit

DL06 PLC

Y2 - Y17

Y0 - Y1

HSIO

Counter 1

CLK Reset X0

I/O data

Counter 2

CLK Reset X1

Filter

Mode Select

X2 - X3

CPU

V-memory

V7633

0010

X4 - X23

Input Circuit

DL06 Micro PLC User Manual, 3rd Edition Rev. A

E–7

Page 258

Appendix E: High-speed Input and Pulse Output Features

Wiring Diagram

1 2 3 4 E 6 7 8 9 10 11 12 13 14 A B C D

A general wiring diagram for counters/encoders to the DL06 in HSIO Mode 10 is shown below. Many types of pulse-generating devices may be used, such as proximity switches, singlechannel encoders, magnetic or optical sensors, etc. Devices with sinking outputs (NPN open collector) are probably the best choice for interfacing. If the counter sources to the inputs, it must output 12 to 24 VDC. Note that devices with 5V sourcing outputs will not work with DL06 inputs. C0

X1 X0

X3 X2

X4 C1

X6 X5

X7

C2 X11 X13 X14 X16 C4 X21 X23 N.C. X15 X17 X20 X22 N.C. X10 X12 C3

TERM PORT1

PORT2

RUN STOP

Counter Input Wiring Signal

–

+

Signal Common

12-24 VDC Supply

Interfacing to Counter Inputs

E–8

The DL06’s DC inputs are flexible in that they detect current flow in either direction, so they can be wired to a sensor with either sourcing or sinking outputs. In the following circuit, a sensor has an open-collector NPN transistor output. It sinks current from the PLC input point, which sources current. The power supply can be the FA–24PS or another supply (+12VDC or +24VDC), as long as the input specifications are met. Sensor Output

X0 - X3 Input Input (sourcing)

Output (sinking) 12-24 VDC Supply Ground

–

+

Common

In the circuit diagram below, an encoder has open-emitter PNP transistor outputs. It sources current to the PLC input point, which sinks the current back to ground. Since the encoder sources current, no additional power supply is required. However, note that the encoder output must be 12 to 24 volts (5V encoder outputs will not work). Encoder Output X0 - X3 Input

+12 to 24 VDC

Input Output (sourcing) Ground

(sinking) Common

DL06 Micro PLC User Manual, 3rd Edition Rev. A

Page 259

Appendix E: High-speed Input and Pulse Output Features

Setup for Mode 10 V7633 is the HSIO Mode Select register. Refer to the diagram below. Use BCD 10 in the lower byte of V7633 to select the High-Speed Counter Mode.

1 2 3 4 Choose the most convenient method of programming V7633 from the following: E • Include load and out instructions in your ladder program • DirectSOFT 5’s memory editor or Data View 6 • Use the Handheld Programmer D2–HPP We recommend using the first method above so that the HSIO setup becomes an integral part of 7 your application program. An example program later in this section shows how to do this. 8 Presets and Special Relays Presets are used to cause a particular action to occur when the count reaches the preset value. Refer to the figure below. Each counter features 24 presets, which you can program. Presets 9 are double word numbers so they occupy two V-memory registers. The user selects the preset values, and the counter continuously compares the current count with the preset. When the 10 two are equal, a special relay contact is energized and program execution jumps to the interrupt routine. We recommend using the special relay(s) in the interrupt service routine to cause any immediate action you 11 desire. After the interrupt service routine is complete, the CPU returns to the ladder program, resuming program execution from the point of interruption. The compare function is ready for the next preset event. 12 13 14 A B C D Memory Location V7633

Bits

15

14

13

12 11

10

9

8

7

6

5

4

3

2

1

0

0

0

0

0

0

0

0

0

0

0

1

0

0

0

0

0

0

0

1

For the function of bits 8 - 15, refer to page 3-6.

X0, up counter clock X2, external reset

Counter 1 Reset 1

Current Value

Counter 2 Reset 2

Current Value

X1, up counter clock

X3, external reset

Counter 2: Preset Data 1500 V3710 0000 2500 V3712 0000 V3632 0000 Data2000 Counter 1: Preset V3630 V3634 0000 0000 1000 2500 2000 V3632 0000 V3636 0000 3175 V3634 0000 2500 V3636

V3706

V3706

0000

3175

0921

0000

High 0921

Low 0000

Word High Word

0

HSIO Mode Setup (BCD) 10 = High-Speed Counter

CPU Scan

Does Count 1 = Preset?

Does Count 2 = Preset?

=

Input Update

Ladder Program Execution

=

Current Instruction Output Update

INT

HSIO Interrupt Routine Program SPxxx IRT

Word Low Word

DL06 Micro PLC User Manual, 3rd Edition Rev. A

E–9