For the AutomationDirect Direct Logic DL06

Page 240

Appendix C: Instruction Execution Times

Number Conversion Instructions

1 2 C 4 5 6 7 8 9 10 11 12 13 14 A B C D

Number Conversion Instructions (Accumulator) Instruction BIN BCD INV BCDPL ATH HTA GRAY SFLDGT BTOR RTOB RADR DEGR

Legal Data Types None None None None V V None None None None None None

DL06 Execute

Not Execute

100.2 µs 95.2 µs 2.5 µs 75.6 µs 25.4 µs 25.4 µs 110.8 µs 23.1 µs 18.6 µs 8.6 µs 51.4 µs 81.5 µs

0.9 µs 0.9 µs 1.0 µs 1.0 µs 1.0 µs 1.0 µs 1.0 µs 1.0 µs 1.0 µs 1.0 µs 1.0 µs 1.0 µs

Table Instructions

C–20

Table Instructions Instruction MOV

Legal Data Types

DL06 Execute

Not Execute

60.2 µs+9.5 x N

0.9 µs

35 µs + 10.4 µs x N

0.9 µs

6.4 µs

1.3 µs

V: Data Reg V:Bit Reg

29.4 µs + 8.0 µs x N

1.0 µs

K:Constant

26.2 µs + 8.0 µs x N

P:Indir. (Data) P:Indir. (bit)

55.1 µs + 8.0 µs x N

Move V:data reg. to V:data reg Move V:bit reg. to V:data reg Move V:data reg. to V:bit reg Move V:bit reg. to V:bit reg. N=#of words Move V:data Reg to EEPROM Move V:Bit Reg to EEPROM

MOVMC

Move from Date Label to V: Data Reg Move from Data Label to V: Bit Reg N= #of words

LDLBL

FILL

FIND

K

V: Data Reg (N bits) V:Bit Reg. (N bits) K:Constant(N bits)

DL06 Micro PLC User Manual, 3rd Edition Rev. A

66.8 µs 66.8 µs 64.0 µs

1.0 µs 1.0 µs 1.0 µs 1.0 µs 1.0 µs

Page 241

Appendix C: Instruction Execution Times

Table Instructions (cont’d) Table Instructions Instruction FDGT

FINDB TTD RFB STT RFT ATT TSHFL TSHFR ANDMOV ORMOV XORMOV SWAP SETBIT RSTBIT

Legal Data Types V: Data Reg (N bits) V:Bit Reg. (N bits) K:Constant(N bits) V: Data Reg (N bits) V:Bit Reg. (N bits) P:Indir. (Data) P:Indir. (Bit) V: Data Reg V:Bit Reg V: Data Reg V:Bit Reg V: Data Reg V:Bit Reg K:Constant V: Data Reg V:Bit Reg V: Data Reg V:Bit Reg K:Constant V: Data Reg V:Bit Reg V: Data Reg V:Bit Reg V: Data Reg V:Bit Reg V: Data Reg V:Bit Reg V: Data Reg V:Bit Reg V: Data Reg V:Bit Reg V: Data Reg (N bits) V:Bit Reg. (N bits) V: Data Reg (N bits) V:Bit Reg. (N bits)

DL06 Execute

Not Execute

66.1 µs 66.1 µs 55.2 µs 210.8 µs 210.8 µs 237.0 µs 237.0 µs 66.9 µs 66.9 µs 66.8 µs 66.8 µs 67.8 µs 67.8 µs 65.0 µs 51.1 µs 51.1 µs 53.5 µs 53.5 µs 50.8 µs 134.0 µs 134.0 µs 133.9 µs 133.9 µs 80.2 µs 80.2 µs 80.4 µs 80.4 µs 80.4 µs 80.4 µs 84.1 µs 84.1 µs 59.5 µs 59.5 µs 59.5 µs 59.5 µs

1.0 µs 1.0 µs 1.0 µs 1.0 µs 1.0 µs 1.0 µs 1.0 µs 1.0 µs 1.0 µs 1.0 µs 1.0 µs 1.0 µs 1.0 µs 1.0 µs 1.0 µs 1.0 µs 1.0 µs 1.0 µs 1.0 µs 1.0 µs 1.0 µs 1.0 µs 1.0 µs 1.0 µs 1.0 µs 1.0 µs 1.0 µs 1.0 µs 1.0 µs 1.0 µs 1.0 µs 1.0 µs 1.0 µs 1.0 µs 1.0 µs

DL06 Micro PLC User Manual, 3rd Edition Rev. A

1 2 C 4 5 6 7 8 9 10 11 12 13 14 A B C D C–21

Page 242

Appendix C: Instruction Execution Times

CPU Control Instructions

1 2 C 4 5 6 7 8 9 10 11 12 13 14 A B C D

CPU Control Instructions Instruction NOP END STOP RSTWT

DL06

Legal Data Types

Execute

Not Execute

None None None None

1.1 µs 24.0 µs 10.0 µs 5.9 µs

1.1 µs 24.0 µs 1.1 µs 2.2 µs

Program Control Instructions Program Control Instructions Instruction GOTO LBL FOR NEXT GTS SBR RTC RT MLS MLR

Legal Data Types K K V, K None K K None None K K

DL06 Execute

Not Execute

5.1 µs 5.7 µs 125.9 µs 64.4 µs 27.5 µs 1.5 µs 25.7 µs 21.2 µs (1–7) 35.2 µs (0–7) 30.9 µs

4.8 µs 0.0 µs 14.5 µs 64.4 µs 14.8 µs 1.5 µs 12.1 µs 21.2 µs 35.2 µs 30.9 µs

Interrupt Instructions Interrupt Instructions Instruction ENI DISI INT IRTC IRT

DL06

Legal Data Types

Execute

Not Execute

None None O(0,1) None None

24.2 µs 9.4 µs 7.5 µs 0.9 µs 6.6 µs

2.7 µs 2.3 µs – 1.3 µs –

Network Instructions Network Instructions Instruction RX

WX

C–22

DL06

Legal Data Types

Execute

Not Execute

X, Y, C, T, CT, SP, S, $ V:Data Reg. V:Bit Reg. P:Indir. (Data) P:Indir. (Bit) X, Y, C, T, CT, SP, S, $ V:Data Reg. V:Bit Reg. P:Indir. (Data) P:Indir. (Bit)

852.0 µs 852.0 µs 852.0 µs 868.2 µs 868.2 µs 1614.0 µs 1614.0 µs 1614.0 µs 1630.0 µs 1630.0 µs

4.4 µs 4.4 µs 4.4 µs 4.2 µs 4.2 µs 4.4 µs 4.4 µs 4.4 µs 4.4 µs 4.4 µs

DL06 Micro PLC User Manual, 3rd Edition Rev. A

Page 243

Appendix C: Instruction Execution Times

Intelligent I/O Instructions Network Instructions Instruction RD WT

DL06

Legal Data Types

Execute

Not Execute

V:Data Reg. V:Bit Reg. V:Data Reg. V:Bit Reg.

385.7 µs 385.7 µs 385.6 µs 385.6 µs

1.2 µs 1.2 µs 1.2 µs 1.2 µs

Message Instructions Message Instructions Instruction FAULT DLBL NCON ACON PRINT

DL06

Legal Data Types

Execute

Not Execute

V:Data Reg. V:Bit Reg. K:Constant K K A ASCII

65.0 µs 65.0 µs 204.7 µs – – – 631.0 µs

4.4 µs 4.4 µs 4.4 µs – – – 3.6 µs

RLLPLUS Instructions RLLplus Instructions Instruction ISG SG JMP NJMP CV CVJMP BCALL BLK BEND

DL06

Legal Data Types

Execute

Not Execute

S S S S S S C C None

44.0 µs 44.0 µs 76.0 µs 77.4 µs 42.1 µs 89.5 µs 22.1 µs 17.1 µs 8.7 µs

41.1 µs 41.1 µs 9.3 µs 9.3 µs 27.5 µs 17.6 µs 22.6 µs 14.6 µs 0.0 µs

Drum Instructions Drum Instructions Instruction DRUM EDRUM MDRMD MDRMW

DL06

Legal Data Types

Execute

Not Execute

CT CT CT CT

840.0 µs 753.2 µs 411.3 µs 378.6 µs

339.6 µs 357.0 µs 216.4 µs 147.0 µs

DL06 Micro PLC User Manual, 3rd Edition Rev. A

1 2 C 4 5 6 7 8 9 10 11 12 13 14 A B C D C–23

Page 244

Appendix C: Instruction Execution Times

Clock / Calender Instructions

1 2 C 4 5 6 7 8 9 10 11 12 13 14 A B C D

Clock / Calender Instructions Instruction V:Data Reg. V:Bit Reg. V:Data Reg. V:Bit Reg.

DATE TIME

DL06 Execute

Not Execute

24.0 µs

1.2 µs

50.8 µs

1.2 µs

MODBUS Instructions Clock / Calender Instructions Instruction Input, Input Register Coil, Holding Register Input, Input Register Coil, Holding Register

MRX MWX

DL06 Execute

Not Execute

120.2 µs

1.3 µs

21.3 µs

1.3 µs

ASCII Instructions

C–24

ASCII Instructions Instruction AIN AFIND AEX CMPV SWAPB VPRINT PRINTV ACRB

DL06

Legal Data Types

Execute

Not Execute

V V V V V Text Data V V

13.9 µs 111.5 µs 111.7 µs 12.2 µs 109.8 µs 161.6 µs 163.3 µs 3.9 µs

12.0 µs 1.3 µs 1.3 µs 1.3 µs 1.3 µs 1.3 µs 1.3 µs 1.1 µs

DL06 Micro PLC User Manual, 3rd Edition Rev. A

Page 245 read from a scan by OCR; it may hold reading errors

>PENDIX SPECIAL RELAYS

In This Appendix... DLO6 PLC Special Relays .......... 0... eee eee eee eee D-2

Page 246

Appendix D: Special Relays

1 2 3 D 5 6 7 8 9 10 11 12 13 14 A B C D

DL06 PLC Special Relays “Special Relays” are just contacts that are set by the CPU operating system to indicate a particular system event has occurred. These contacts are available for use in your ladder program. Knowing just the right special relay contact to use for a particular situation can save a lot of programming time. Since the CPU operating system sets and clears special relay contacts, the ladder program only has to use them as inputs in ladder logic.

Startup and Real-Time Relays SP0

First scan

On for the first scan after a power cycle or program to run transition only. The relay is reset to off on the second scan. It is useful where a function needs to be performed only on program startup.

SP1 SP2 SP3 SP4 SP5 SP6 SP7

Always ON

Provides a contact to insure an instruction is executed every scan.

Always OFF

Provides a contact that is always off

1 minute clock

On for 30 seconds and off for 30 seconds.

1 second clock

On for 0.5 second and off for 0.5 second.

100 ms clock

On for 50 ms. and off for 50 ms.

50 ms clock

On for 25 ms. and off for 25 ms.

Alternate scan

On every other scan.

CPU Status Relays SP11 SP12 SP13 SP15 SP16 SP17 SP20 SP22

D–2

Forced run mode

On when the mode switch is in the run position and the CPU is running.

Terminal run mode

On when the mode switch is in the TERM position and the CPU is in the run mode.

Test run mode

On when the CPU is in the test run mode.

Test stop mode

On when the CPU is in the test stop mode.

Terminal PGM mode

On when the mode switch is in the TERM position and the CPU is in program mode.

Forced stop

On when the mode switch is in the STOP position.

Forced stop mode

On when the STOP instruction is executed.

Interrupt enabled

On when interrupts have been enabled using the ENI instruction.

DL06 Micro PLC User Manual, 3rd Edition Rev. A

Page 247

Appendix D: Special Relays

System Monitoring SP36 SP37 SP40 SP41 SP42 SP43 SP44 SP45 SP46 SP50 SP51

Override setup relay

On when the override function is used.

Scan controller

On when the actual scan time runs over the prescribed scan time.

Critical error

On when a critical error such as I/O communication loss has occurred.

Warning

On when a non critical error has occurred.

Diagnostics error

On when a diagnostics error or a system error occurs.

Low battery error

On when the CPU battery voltage is low.

Program memory error

On when a memory error such as a memory parity error has occurred.

I/O error

On when an I/O error such as a blown fuse occurs.

Communications error

On when a communication error occurs on any of the CPU ports.

Fault instruction

On when a Fault Instruction is executed.

Watch Dog timeout

On if the CPU Watch Dog timer times out.

SP52

Grammatical error

On if a grammatical error has occurred either while the CPU is running or if the syntax check is run. V7755 will hold the exact error code.

SP53 SP54

Solve logic error

On if CPU cannot solve the logic.

Communication error

On when RX, WX, instructions are executed with the wrong parameters.

SP56

Table instruction overrun

On if a table instruction with a pointer is executed and the pointer value is outside the table boundary.

Accumulator Status SP60 SP61 SP62 SP63 SP64 SP65 SP66 SP67 SP70 SP71 SP72

Value less than

On when the accumulator value is less than the instruction value.

Value equal to

On when the accumulator value is equal to the instruction value.

Greater than

On when the accumulator value is greater than the instruction value.

Zero

On when the result of the instruction is zero (in the accumulator).

Half borrow

On when the 16 bit subtraction instruction results in a borrow.

Borrow

On when the 32 bit subtraction instruction results in a borrow.

Half carry

On when the 16 bit addition instruction results in a carry.

Carry

On when the 32 bit addition instruction results in a carry.

Sign

On anytime the value in the accumulator is negative.

Pointer reference error

On when the V-memory specified by a pointer (P) is not valid.

Floating point number

On anytime the value in the accumulator is a valid floating point number.

SP73

Overflow

On if overflow occurs in the accumulator when a signed addition or subtraction results in an incorrect sign bit.

SP74 SP75 SP76

Underflow

On anytime a floating point math operation results in an underflow error.

Data error

On if a BCD number is expected and a non–BCD number is encountered.

Load zero

On when any instruction loads a value of zero into the accumulator.

DL06 Micro PLC User Manual, 3rd Edition Rev. A

D–3

1 2 3 D 5 6 7 8 9 10 11 12 13 14 A B C D

Page 248

Appendix D: Special Relays

HSIO Input Status

1 2 3 D 5 6 7 8 9 10 11 12 13 14 A B C D

SP100 SP101

X0 status

On when X0 is on

X1 status

On when X1 is on

HSIO Pulse Output Relay SP104

Profile Complete

On when the pulse output profile is completed. (Mode 30)

Communication Monitoring Relay SP116

CPU port busy Port 2

On when port 2 is the master and sending data.

SP117

Communications error Port 2

On when port 2 is the master and has a communication error.

Option Slot Communication Monitoring Relay SP120 SP121 SP122 SP123 SP124 SP125 SP126 SP127

Slot 1 busy

H0-ECOM/D0-DCM Port2

Slot 1 error

H0-ECOM/D0-DCM Port2

Slot 2 busy

H0-ECOM/D0-DCM Port2

Slot 2 error

H0-ECOM/D0-DCM Port2

Slot 3 busy

H0-ECOM/D0-DCM Port2

Slot 3 error

H0-ECOM/D0-DCM Port2

Slot 4 busy

H0-ECOM/D0-DCM Port2

Slot 4 error

H0-ECOM/D0-DCM Port2

Option Slot Special Relay SP140-237 SP240-337 SP340-437 SP430-537

D–4

Slot 1

SP relay for option card

Slot 2

SP relay for option card

Slot 3

SP relay for option card

Slot 4

SP relay for option card

DL06 Micro PLC User Manual, 3rd Edition Rev. A

Page 249

Appendix D: Special Relays

Counter 1 Mode 10 Equal Relays SP540 SP541 SP542 SP543 SP544 SP545 SP546 SP547 SP550 SP551 SP552 SP553 SP554 SP555 SP556 SP557 SP560 SP561 SP562 SP563 SP564 SP565 SP566 SP567

Current = target value

On when the counter current value equals the value in V3631/3630

Current = target value

On when the counter current value equals the value in V3633/3632

Current = target value

On when the counter current value equals the value in V3635/3634

Current = target value

On when the counter current value equals the value in V3637/3636

Current = target value

On when the counter current value equals the value in V3641/3640

Current = target value

On when the counter current value equals the value in V3643/3642

Current = target value

On when the counter current value equals the value in V3645/3644

Current = target value

On when the counter current value equals the value in V3647/3646

Current = target value

On when the counter current value equals the value in V3651/3650

Current = target value

On when the counter current value equals the value in V3653/3652

Current = target value

On when the counter current value equals the value in V3655/3654

Current = target value

On when the counter current value equals the value in V3657/3656

Current = target value

On when the counter current value equals the value in V3661/3660

Current = target value

On when the counter current value equals the value in V3663/3662

Current = target value

On when the counter current value equals the value in V3665/3664

Current = target value

On when the counter current value equals the value in V3667/3666

Current = target value

On when the counter current value equals the value in V3671/3670

Current = target value

On when the counter current value equals the value in V3673/3672

Current = target value

On when the counter current value equals the value in V3675/3674

Current = target value

On when the counter current value equals the value in V3677/3676

Current = target value

On when the counter current value equals the value in V3771/3770

Current = target value

On when the counter current value equals the value in V3703/3702

Current = target value

On when the counter current value equals the value in V3705/3704

Current = target value

On when the counter current value equals the value in V3707/3706

DL06 Micro PLC User Manual, 3rd Edition Rev. A

1 2 3 D 5 6 7 8 9 10 11 12 13 14 A B C D D–5