For the AutomationDirect GS2

Page 1

Prices as of April 16, 2014. Check Web site for most current prices.

GS2 Series - Introduction GS2 Series Drives 0.25 Hp 0.2 kW Single-Phase Input 115V Class 4 Single/Three-Phase Input 230V Class Three-Phase 230V Class Three-Phase 460V Class Three-Phase 575V Class

Motor Rating

Features Overview The GS2 series of AC drives offers all of the features of our GS1 drive plus dynamic braking, PID and a removable keypad. The drive can be configured using the built-in digital keypad or with the standard RS-232/RS-485 serial communications port. The standard keypad allows you to configure the drive, set the speed, start and stop the drive, command forward and reverse direction of motor shaft, and monitor specific parameters during operation. Each GS2 features one analog and six programmable digital inputs, and one analog and two programmable relay outputs.

GS2 series part numbering system

• Simple Volts/Hertz control • Pulse Width Modulation (PWM) • 1-12 kHz carrier frequency • IGBT technology • Starting torque: 125% at 0.5 Hz/150% at 5 Hz • 150% rated current for one minute • Electronic overload protection • Stall prevention • Adjustable accel and decel ramps • settings for acceleration and deceleration • Automatic torque compensation • Automatic slip compensation • Dynamic braking circuit • DC braking • Three skip frequencies • Trip history • Programmable jog speed • Integral PID control • keypad with speed potentiometer • Programmable analog input • Programmable analog output • Six programmable digital inputs • Two programmable relay outputs • Modbus communications up to 38.4 Kbps. • Optional Ethernet communications • Two-year warranty • listed * GS2-5xxx 575V drives NOT CE compliant

GS2- 4 7P5 Applicable Motor Capacity 0P2: 0.25HP 1P0: 1.0HP 3P0: 3.0HP 7P5: 7.5HP

0.5

1

2

3

5

7.5

10

0.4

0.75

1.5

2.2

3.7

5.5

7.5

4 4

4 4

4

4 4 4 4

4 4 4

4 4

4 4

4 4

4 4

Accessories

• AC line reactors • EMI filters • RF filter • Braking resistors • Fuse kits and replacement fuses • rail mounting adapter (see “Accessories” table for applicability) • keypads • cables in 1, 3, and 5-meter lengths • interface • and eight-port serial communication breakout boards • KEPDirect I/O or OPC Server • GSoft drive configuration software

• erial communication cables available for creating plug and play RS-232/RS-485 networks with AutomationDirect PLCs. See the comm cable matrix on page DR-93 • – USB to RS-485 PC adapter (see “Communications Products” chapter for detailed information) Detailed descriptions and specifications for GS accessories are available in the “GS/DURApulse Accessories” section.

Typical Applications • Conveyors • Fans • Pumps • Compressors • HVAC handling • • tools

0P5: 0.5HP 2P0: 2.0HP 5P0: 5.0HP 010: 10HP

Input Voltage 1: 100-120VAC 2: 200-240VAC 4: 380-480VAC 5: 500-600VAC

Series Name Book 2 (14.1)

eDR-22

AC Drives

1-800-633-0405

Page 2

Prices as of April 16, 2014. Check Web site for most current prices.

GS2 Series Specifications

Company Information Drives

115V CLASS GS2 SERIES Model

GS2-10P2

GS2-10P5

GS2-11P0

Price

$156.00

$166.00

$186.00

HP

1/4hp

1/2hp

1hp kW

0.2kW

0.4kW

0.75kW

0.6

1.0

1.6

Motor Rating

Rated Output Capacity (kVA) Rated Input Voltage

Single-phase : 100 to 120 VAC ±10% 50/60 Hz ±5%�

Rated Output Voltage

Three-phase, two times proportion to input voltage

Rated Input Current (A) Rated Output Current (A) DC Braking

9

16

1.6

2.5

4.2

24

34

46

Weight (lb)

3.5

3.6

3.7

Sensors: Proximity

151.0 x 100.0 x 140.5 [5.94 x 3.94 x 5.53]

LR-10P2-1PH

Output side of drive (3 Phase)*

Braking Resistor

LR-10P5-1PH

Sensors: Limit Switches

LR-21P0 GS-20P5-BR

EMI Filter

20DRT1W3S

RF Filter

RF220X00A

Fuse Kit

LR-11P0-1PH

LR-20P5 GS-20P5-BR

GS-21P0-BR

Single Phase**

GS-10P2-FKIT-1P

GS-10P5-FKIT-1P

GS-11P0-FKIT-1P

GS-10P2-FUSE-1P

GS-10P5-FUSE-1P

GS-11P0-FUSE-1P

GS2-DR02

Spare Keypad, GS2 Series Drive

GS2-KPD

Keypad Cable, GS2 Series, 1 meter

GS-CBL2-1L

Keypad Cable, GS2 Series, 3 meter

GS-CBL2-3L

Keypad Cable, GS2 Series, 5 meter Ethernet Communications module for GS Series Drives (DIN rail mounted) USB to RS232 PC Communication Adapter RS-232 Serial Cable, GS2 Drive to DL05/06, CLICK, D2-250/260, D4-450, P3-550 USB to RS-485 PC Communication Adapter RS-485 Communication Distribution Module (for creating plug and play RS-485 networks) RS-485 Serial Cable, GS Drive to DL06/D2-260 RS-485 Serial Cable, GS Drive to ZIPLink CDM Module Software

GS-CBL2-5L

OPC Server

Sensors: Current Sensors: Pressure Sensors: Temperature

Replacement Fuses Single Phase** DIN Rail Mounting Adapter

Sensors: Photoelectric Sensors: Encoders

Accessories Input side of drive (1 Phase)*

Power Transmission Motion: Servos and Steppers

Frequency 60–0 Hz, 0–100% rated current, start time 0.0–5.0 seconds, Stop Time 0.0–25.0 seconds

Watt Loss @ 100% I (W)

Line Reactor

Motors

Motor Controls

6

Dimensions*** (HxWxD) (mm [in])

Soft Starters

Sensors: Level Sensors: Flow Switches Pushbuttons and Lights Stacklights Signal Devices

GS-EDRV100

Process

USB-RS232

Relays and Timers

GS-RJ12-CBL-2 USB-485M

Pneumatics: Air Prep

ZL-CDM-RJ12X4 / ZL-CDM-RJ12X10

Pneumatics: Directional Control Valves

GS-485HD15-CBL-2 GS-485RJ12-CBL-2

Pneumatics: Cylinders

GSoft / KEPDirect

Pneumatics: Tubing

KEPDirect

*Note: GS2-1xxx drives require 115V class input line reactors and 230V class output line reactors.

Pneumatics: Air Fittings

**Note: Single phase fuse kits and fuses are used only with GS2-1xxx drives. ***Note: Height dimension does not include external ground terminal, which adds 10 to 15 mm. Refer to dimensional drawings for details.

Appendix Book 2 Terms and Conditions

Book 2 (14.1)

www.automationdirect.com/drives

AC Drives eDR-23

Page 3

Prices as of April 16, 2014. Check Web site for most current prices.

GS2 Series Specifications 230V CLASS GS2 SERIES Model Price Motor Rating

GS2-20P5

GS2-21P0

GS2-22P0

GS2-23P0

GS2-25P0

GS2-27P5 $465.00

$158.00

$177.00

$251.00

$309.00

$363.00

HP

1/2hp

1hp

2hp

3hp

5hp

7.5hp kW

0.4kW

0.75kW

1.5kW

2.2kW

3.7kW

5.5kW

1.0

1.9

2.7

3.8

6.5

9.5

Rated Output Capacity (kVA) Rated Input Voltage

Three-phase : 200/208/220/230/240 VAC ±10%; 50/60 Hz ±5%

Single/Three-phase : 200/208/220/230/240 VAC ±10%; 50/60Hz ±5%

Rated Output Voltage

Three-phase : Corresponds to input voltage

Rated Input Current (A)

6.3/2.9

11.5/6.3

15.7/8.8

27.0/12.5

19.6

28

Rated Output Current (A)

2.5

5.0

7.0

10

17

25

DC Braking

Frequency 60–0 Hz, 0–100% rated current, start time 0.0–5.0 seconds, Stop Time 0.0–25.0 seconds

Watt Loss @ 100% I (W)

34

57

77

111

185

255

Weight (lb)

3.5

3.6

3.7

8.5

8.5

8.5

Dimensions* (HxWxD) (mm [in])

151.0 x 100.0 x 140.5 [5.94 x 3.94 x 5.53]

220.0 x 125.0 x 189.5 [8.66 x 4.92 x 7.46]

Accessories Line Reactor

Single-Phase Three-Phase

Braking Resistor

LR-20P5-1PH

LR-21P0-1PH

LR-22P0-1PH

LR-23P0-1PH n/a n/a

LR-20P5

LR-21P0

LR-22P0

LR-23P0

LR-25P0

LR-27P5

GS-20P5-BR

GS-21P0-BR

GS-22P0-BR

GS-23P0-BR

GS-25P0-BR

GS-27P5-BR

EMI Filter (single phase input)

20DRT1W3S

RF Filter

32DRT1W3C

40TDS4W4B

RF220X00A

Single-Phase GS-20P5-FKIT-1P GS-21P0-FKIT-1P GS-22P0-FKIT-1P GS-23P0-FKIT-1P

Fuse Kit Replacement Fuses

N/A

N/A

GS-25P0-FKIT-3P

GS-27P5-FKIT

N/A

N/A

Three-Phase GS-20P5-FUSE-3P GS-21P0-FUSE-3P GS-22P0-FUSE-3P GS-23P0-FUSE-3P

GS-25P0-FUSE

GS-27P5-FUSE

GS2-DR02 n/a

Three-Phase

GS-20P5-FKIT-3P

Single-Phase

GS-20P5-FUSE-1P GS-21P0-FUSE-1P GS-22P0-FUSE-1P GS-23P0-FUSE-1P

DIN Rail Mounting Adapter

GS-21P0-FKIT-3P

GS-22P0-FKIT-3P

GS-23P0-FKIT-3P

Spare Keypad, GS2 Series Drive

GS2-KPD

Keypad Cable, GS2 Series, 1 meter

GS-CBL2-1L

Keypad Cable, GS2 Series, 3 meter

GS-CBL2-3L

Keypad Cable, GS2 Series, 5 meter Ethernet Communications module for GS Series Drives (DIN rail mounted) USB to RS232 PC Communication Adapter RS-232 Serial Cable, GS2 Drive to DL05/06, CLICK, D2-250/260, D4-450, P3-550 USB to RS-485 PC Communication Adapter RS-485 Communication Distribution Module (for creating plug and play RS-485 networks) RS-485 Serial Cable, GS Drive to DL06/D2-260 RS-485 Serial Cable, GS Drive to ZIPLink CDM Module Software

GS-CBL2-5L

OPC Server

GS-EDRV100 USB-RS232 GS-RJ12-CBL-2 USB-485M ZL-CDM-RJ12X4 / ZL-CDM-RJ12X10 GS-485HD15-CBL-2 GS-485RJ12-CBL-2 GSoft / KEPDirect KEPDirect

*Note: Height dimension does not include external ground terminal, which adds 10 to 15 mm. Refer to dimensional drawings for details.

Book 2 (14.1)

eDR-24

AC Drives

1-800-633-0405

Page 4

Prices as of April 16, 2014. Check Web site for most current prices.

GS2 Series Specifications

Company Information Drives

460V CLASS GS2 SERIES Model

GS2-41P0

GS2-42P0

GS2-43P0

GS2-45P0

GS2-47P5

GS2-4010

Price

$261.00

$303.00

$357.00

$410.00

$586.00

$725.00

Motor Rating

HP

1hp

2hp

3hp

5hp

7.5hp

10hp kW

0.8kW

1.5kW

2.2kW

4kW

5.5kW

7.5kW

2.3

3.1

3.8

6.2

9.9

13.7

Rated Output Capacity (kVA) Rated Input Voltage

Three-phase: 380/400/415/440/460/480 VAC ±10%; 50/60 Hz ±5%

Rated Output Voltage

Corresponds to input voltage 4.2

5.7

6.0

8.5

14

23

Rated Output Current (A)

3.0

4.0

5.0

8.2

13

18

Frequency 60–0 Hz, 0–100% rated current, Start Time 0.0–5.0 seconds, Stop Time 0.0–25.0 seconds

Watt Loss @ 100% I (W)

73

86

102

170

240

255

Weight (lb)

3.5

3.6

3.7

8.5

8.5

8.5

Dimensions* (HxWxD) (mm [in])

151.0 x 100.0 x 140.5 [5.94 x 3.94 x 5.53]

220.0 x 125.0 x 189.5 [8.66 x 4.92 x 7.46]

Accessories Line Reactor

LR-41P0

LR-42P0

LR-43P0

LR-45P0

LR-47P5

Braking Resistor

GS-41P0-BR

GS-42P0-BR

GS-43P0-BR

GS-45P0-BR

GS-47P5-BR

EMI Filter

11TDT1W4S

RF Filter

17TDT1W44

LR-4010 GS-4010-BR 26TDT1W4B4

RF220X00A

Fuse Kit

GS-41P0-FKIT

GS-42P0-FKIT

GS-43P0-FKIT

GS-45P0-FKIT

GS-47P5-FKIT

GS-4010-FKIT

Replacement Fuses

GS-41P0-FUSE

GS-42P0-FUSE

GS-43P0-FUSE

GS-45P0-FUSE

GS-47P5-FUSE

GS-4010-FUSE

DIN Rail Mounting Adapter

GS2-DR02

Motors Power Transmission Motion: Servos and Steppers Motor Controls

Rated Input Current (A) DC Braking

Soft Starters n/a

Sensors: Proximity Sensors: Photoelectric Sensors: Encoders Sensors: Limit Switches Sensors: Current Sensors: Pressure Sensors: Temperature Sensors: Level Sensors: Flow Switches

Spare Keypad, GS2 Series Microdrive

GS2-KPD

Keypad Cable, GS2 Series, 1 meter

GS-CBL2-1L

Keypad Cable, GS2 Series, 3 meter

GS-CBL2-3L

Pushbuttons and Lights

Keypad Cable, GS2 Series, 5 meter Ethernet Communications Module for GS Series Drives (DIN rail mounted) USB to RS232 PC Communication Adapter RS-232 Serial Cable, GS2 Drive to DL05/06, CLICK, D2-250/260, D4-450, P3-550 USB to RS-485 PC Communication Adapter RS-485 Communication Distribution Module (for creating plug and play RS-485 networks) RS-485 Serial Cable, GS Drive to DL06/D2-260 RS-485 Serial Cable, GS Drive to ZIPLink CDM Module Software

GS-CBL2-5L

Stacklights

GS-EDRV100

Signal Devices

OPC Server

USB-RS232

Process

GS-RJ12-CBL-2

Relays and Timers

USB-485M

Pneumatics: Air Prep

ZL-CDM-RJ12X4 / ZL-CDM-RJ12X10 GS-485HD15-CBL-2

Pneumatics: Directional Control Valves

GS-485RJ12-CBL-2

Pneumatics: Cylinders

GSoft / KEPDirect KEPDirect

Pneumatics: Tubing

*Note: Height dimension does not include external ground terminal, which adds 10 to 15 mm. Refer to dimensional drawings for details.

Pneumatics: Air Fittings Appendix Book 2 Terms and Conditions

Book 2 (14.1)

www.automationdirect.com/drives

AC Drives eDR-25

Page 5

Prices as of April 16, 2014. Check Web site for most current prices.

GS2 Series Specifications 575V CLASS GS2 SERIES Model Price Motor Rating

GS2-51P0

GS2-52P0

GS2-53P0

GS2-55P0

GS2-57P5

GS2-5010

$279.00

$319.00

$378.00

$491.00

$721.00

$812.00

HP

1hp

2hp

3hp

5hp

7.5hp

10hp kW

0.75kW

1.5kW

2.2kW

3.7kW

5.5kW

7.5kW

1.7

3.0

4.2

6.6

9.9

12.2

Rated Output Capacity (kVA) Rated Input Voltage

Three-phase: 500 to 600 VAC -15/+10%; 50/60 Hz ±5%

Rated Output Voltage

Corresponds to input voltage

Rated Input Current (A)

2.4

Rated Output Current (A)

1.7

DC Braking

4.2

5.9

7.0

10.5

12.9

3.0

4.2

6.6

9.9

12.2

Frequency 60-0 Hz, 0-100% rated current, Start Time 0.0-5.0 seconds, Stop Time 0.0-25.0 seconds

Watt Loss @ 100% I (W)

30

58

83

132

191

211

Weight (lb)

3.3

3.3

4.4

7.0

7.0

7.3

Dimensions* (HxWxD) (mm [in])

151.0 x 100.0 x 140.5 [5.94 x 3.94 x 5.53]

220.0 x 125.0 x 189.5 [8.66 x 4.92 x 7.46]

Accessories Line Reactor Braking Resistor

LR-51P0

LR-52P0

GS-42P0-BR

EMI Filter

LR-53P0

LR-55P0

LR-5010

GS-42P0-BR x (2) in parallel

GS-4010-BR x (2) in series not available

RF Filter

RF220X00A

Fuse Block (Edison 3-pole part #) Replacement Fuses (Edison Fuse part #) DIN Rail Mounting Adapter

BC6033PQ or CHCC3D or CHCC3DI HCLR6 HCLR10 (10 fuses per pack) (10 fuses per pack)

HCLR15 (10 fuses per pack)

GS2-DR02 n/a

Spare Keypad, GS2 Series Microdrive

GS2-KPD

Keypad Cable, GS2 Series, 1 meter

GS-CBL2-1L

Keypad Cable, GS2 Series, 3 meter

GS-CBL2-3L

Keypad Cable, GS2 Series, 5 meter Ethernet Communications Module for GS Series Drives (DIN rail mounted) USB to RS232 PC Communication Adapter RS-232 Serial Cable, GS2 Drive to DL05/06, CLICK, D2-250/260, D4-450, P3-550 USB to RS-485 PC Communication Adapter RS-485 Communication Distribution Module (for creating plug and play RS-485 networks) RS-485 Serial Cable, GS Drive to DL06/D2-260 RS-485 Serial Cable, GS Drive to ZIPLink CDM Module Software

GS-CBL2-5L

OPC Server

HCLR20 HCLR30 (10 fuses per pack) (10 fuses per pack)

GS-EDRV100 USB-RS232 GS-RJ12-CBL-2 USB-485M ZL-CDM-RJ12X4 / ZL-CDM-RJ12X10 GS-485HD15-CBL-2 GS-485RJ12-CBL-2 GSoft / KEPDirect KEPDirect

*Note: Height dimension does not include external ground terminal, which adds 10 to 15 mm. Refer to dimensional drawings for details.

Book 2 (14.1)

eDR-26

AC Drives

1-800-633-0405

Page 6

Prices as of April 16, 2014. Check Web site for most current prices.

GS2 Series, General Specifications

Company Information Drives

General Specifications

Soft Starters

Control Characteristics Control System

Sinusoidal Pulse Width Modulation, carrier frequency 1kHz–12kHz

Output Frequency Resolution

0.1 Hz

Overload Capacity

150% of rated current for 1 minute

Motors Power Transmission

Torque Characteristics

Includes auto-torque boost, auto-slip compensation, starting torque 125% @ 0.5Hz/150% @ 5.0Hz

Braking Torque

20% without dynamic braking resistor, 125% with optional braking resistor

DC Braking

Operation frequency 60–0 Hz, 0–100% rated current. Start time 0.0–5.0 seconds. Stop time 0.0–0 25.0 seconds

Acceleration/Deceleration Time

0.1 to 600 seconds (linear or non-linear acceleration/deceleration), second acceleration/deceleration available

Voltage/Frequency Pattern

V/F pattern adjustable. Settings available for Constant Torque - low and high starting torque, Variable Torque - low and high starting torque, and user configured

Stall Prevention Level

20 to 200% or rated current

Operation Specifications

Inputs

External Signal

Potentiometer - 3k to 5kh/2W, 0 to 10VDC (input impedance 10kh), 0 to 20mA / 4 to 20 mA (input impedance 250h), Multi-speed inputs 1 to 3, Serial Communication RS232 and RS485 (Modbus RTU)

Operation Setting

Keypad

Setting by <RUN>, <STOP> buttons

External Signal

Input Terminals

Digital

Forward/Stop, Reverse/Stop (run/stop, fwd/rev), 3-wire control, Serial Communication RS232 and RS485 (Modbus RTU) 6 user-programmable: FWD/STOP, REV/STOP, RUN/STOP, REV/FWD, Run momentary (N.O.), STOP momentary (N.C.), External Fault (N.O./N.C.), External Reset, Multi-Speed Bit (1-3), Jog, External Base Block (N.O./N.C.), Second Accel/Decel Time, Speed Hold, Increase Speed, Decrease Speed, Reset Speed to Zero, PID Disable (N.O.), PID Disable (N.C.), Input Disable 1 user-configurable, 0 to 10VDC (input impedance 10k h) or 0 to 20mA / 4 to 20mA (input impedance 250h ), 10 bit resolution Frequency setpoint or PID process variable PV

Outputs

Output Terminals

Digital

2 user-programmable; Inverter Running, Inverter Fault, At Speed, Zero Speed, Above Desired Frequency, Below Desired Frequency, At Maximum Speed, Over Torque Detected, Above Desired Current, Below Desired Current, PID Deviation Alarm

Analog

1 user-programmable: 0 to 10VDC (max load 2mA), 8 bit resolution frequency, current, process variable PV

Operating Functions Protective Functions

Operator Interface

Environment

Options

Sensors: Proximity

Sensors: Encoders

Setting by <UP> or <DOWN> buttons or potentiometer

Analog

Motor Controls

Sensors: Photoelectric

Keypad

Frequency Setting

Motion: Servos and Steppers

Automatic voltage regulation, voltage/frequency characteristics selection, non-linear acceleration/deceleration, upper and lower frequency limiters, 7-stage speed operation, adjustable carrier frequency (1 to 12 kHz), PID control, skip frequencies, analog gain & bias adjustment, jog, electronic thermal relay, automatic torque boost, trip history, software protection Electronic Thermal, Overload Relay, Auto Restart after Fault, Momentary Power Loss, Reverse Operation Inhibit, Auto Voltage Regulation, Over-Voltage Trip Prevention, Auto Adjustable Accel/Decel, Over-Torque Detection Mode, Over-Torque Detection Level, Over-Torque Detection Time, Over-Current Stall Prevention during Acceleration, Over-Current Stall Prevention during Operation

Sensors: Limit Switches Sensors: Current Sensors: Pressure Sensors: Temperature Sensors: Level Sensors: Flow Switches Pushbuttons and Lights Stacklights Signal Devices

Operator Devices

8-key, 4-digit, 7-segment LED, 14 status LEDs, potentiometer

Programming

Parameter values for setup and review, fault codes

Status Display

Actual Operating Frequency, RPM, Scaled Frequency, Amps, % Load, Output Voltage, DC Bus Voltage, Process Variable, Set-point Frequency

Relays and Timers

Key Functions

RUN, STOP/RESET, FWD/REV, PROGRAM, DISPLAY, <UP>, <DOWN>, ENTER

Enclosure Rating

Protected chassis, IP20

Pneumatics: Air Prep

Ambient Temperature

-10° to 50°C (14°F to 122°F) -10° to 40°C (14°F to 104°F) For models 7.5 hp (5.5 kW) and higher

Storage Temperature

-20° to 60 °C (-4°F to 140°F) - during short-term transportation period

Ambient Humidity

20 to 90% RH (non-condensing)

Vibration

9.8 m/s2 (1G), less than 10Hz; 5.9 m/s2 (0.6G) 10 to 60 Hz

Installation Location

Altitude 1000m or lower above sea level, keep from corrosive gas, liquid and dust

Process

Pneumatics: Directional Control Valves Pneumatics: Cylinders Pneumatics: Tubing

Noise filter, input AC reactor, output AC reactor, cable for remote operator, programming software (GSOFT), Dynamic braking resistor, input fuses, ethernet interface (GS-EDRV100), EMI filters

Pneumatics: Air Fittings Appendix Book 2 Terms and Conditions

Book 2 (14.1)

www.automationdirect.com/drives

AC Drives eDR-27

Page 7

Prices as of April 16, 2014. Check Web site for most current prices.

GS2 Specifications, Installation Understanding the installation requirements for your GS2 drive will help to ensure that it operates within its environmental and electrical limits. Note: Never use only this catalog for installation instructions or operation of equipment; refer to the user manual, GS2-M.

Environmental Specifications

Fan

Protective Structure 1 IP20 Ambient Operating Temperature 2

-10 to 50°C (14°F to 122°F) -10 to 40°C (14°F to 104°F) for models 7.5HP and higher

Storage Temperature 3

-20 to 60°C (-4°F to 140°F)

Humidity

To 90% (no condensation)

Vibration 4

5.9 m/s2 (0.6g), 10 to 55 Hz

Location

Altitude 1,000 m or less, indoors (no corrosive gases or dust)

6in [150mm] minimum 2in [50mm] min

2in [50mm] minimum

1: Protective structure is based upon EN60529 2: ambient temperature must be in the range of -10° to 40° C. If the range will be up to 50° C, you will need to set the carrier frequency to 2.1 kHz or less and derate the output current to 80% or less. See our Web site for derating curves.

6in [150mm] minimum

3: storage temperature refers to the short-term temperature during transport. 4: to the test method specified in JIS CO911 (1984) Input Power

Watt-loss Chart GS2 Drive Model

At full load

GS2-10P2

24

GS2-10P5

34

GS2-11P0

46

GS2-20P5

34

GS2-21P0

57

GS2-22P0

77

GS2-23P0

111

GS2-25P0

185

GS2-27P5

255

GS2-41P0

73

GS2-42P0

86

GS2-43P0

102

GS2-45P0

170

GS2-47P5

240

GS2-4010

255

GS2-51P0

30

GS2-52P0

58

GS2-53P0

83

GS2-55P0

132

GS2-57P5

191

GS2-5010

211

To Motor

Warning: M aximum ambient temperatures must not exceed 50°C (122°F), or 40°C (104°F) for models 7.5 hp (5.5 kW) and higher!

Panel

Air Flow

Ground braid copper lugs

Panel or single point ground*

Star washers*

* For painted sub-panels, scrape the paint from underneath the star washers before tightening them.

Warning: AC drives generate a large amount of heat which may damage the AC drive. Auxiliary cooling methods are typically required in order not to exceed maximum ambient temperatures.

Book 2 (14.1)

eDR-28

AC Drives

1-800-633-0405

Page 8

Prices as of April 16, 2014. Check Web site for most current prices.

GS2 Specifications, Terminals

Company Information Drives

Main Circuit Wiring

Soft Starters

Terminal Description Input power L1, L2, L3 AC drive output T1, T2, T3 DB resistor input B1, B2

Motors Power Transmission

Ground

Motion: Servos and Steppers Motor Controls Sensors: Proximity Sensors: Photoelectric Sensors: Encoders Sensors: Limit Switches Sensors: Current Sensors: Pressure Sensors: Temperature Sensors: Level Sensors: Flow Switches Pushbuttons and Lights Stacklights Signal Devices

Control Circuit Terminals Terminal Symbol R1O R1C R1 R2O R2C R2 DI1 DI2 DI3 DI4 DI5 DI6 DCM AI +10V AO ACM

Description

Process

Relay output 1 normally open Relay output 1 normally closed

Relays and Timers

Relay output 1 common

Pneumatics: Air Prep

Relay output 2 normally open Relay output 2 normally closed

Pneumatics: Directional Control Valves

Relay output 2 common Digital input 1 Digital input 2

Pneumatics: Cylinders

Digital input 3 Digital input 4

Pneumatics: Tubing

Digital input 5 Digital input 6

Pneumatics: Air Fittings

Digital common Analog input

Appendix Book 2

Internal power supply (DC 10V) @ 10 mA Analog output

Terms and Conditions

Analog common

Note: twisted-shielded, twisted-pair or shielded-lead wires for the control signal wiring. It is recommended to run all signal wiring in a separate steel conduit. The shield wire should only be connected at the drive. Do not connect shield wire on both ends.

Book 2 (14.1)

www.automationdirect.com/drives

AC Drives eDR-29