The text of a spec sheet · part 1 of 2
GS2 Series Drives, pages 1 to 8
Pages 1 to 8 of 15
The original document is the PDF (2.7 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the AutomationDirect GS2
Page 1
Prices as of April 16, 2014. Check Web site for most current prices.
GS2 Series - Introduction GS2 Series Drives 0.25 Hp 0.2 kW Single-Phase Input 115V Class 4 Single/Three-Phase Input 230V Class Three-Phase 230V Class Three-Phase 460V Class Three-Phase 575V Class
Motor Rating
Features Overview The GS2 series of AC drives offers all of the features of our GS1 drive plus dynamic braking, PID and a removable keypad. The drive can be configured using the built-in digital keypad or with the standard RS-232/RS-485 serial communications port. The standard keypad allows you to configure the drive, set the speed, start and stop the drive, command forward and reverse direction of motor shaft, and monitor specific parameters during operation. Each GS2 features one analog and six programmable digital inputs, and one analog and two programmable relay outputs.
GS2 series part numbering system
• Simple Volts/Hertz control • Pulse Width Modulation (PWM) • 1-12 kHz carrier frequency • IGBT technology • Starting torque: 125% at 0.5 Hz/150% at 5 Hz • 150% rated current for one minute • Electronic overload protection • Stall prevention • Adjustable accel and decel ramps • settings for acceleration and deceleration • Automatic torque compensation • Automatic slip compensation • Dynamic braking circuit • DC braking • Three skip frequencies • Trip history • Programmable jog speed • Integral PID control • keypad with speed potentiometer • Programmable analog input • Programmable analog output • Six programmable digital inputs • Two programmable relay outputs • Modbus communications up to 38.4 Kbps. • Optional Ethernet communications • Two-year warranty • listed * GS2-5xxx 575V drives NOT CE compliant
GS2- 4 7P5 Applicable Motor Capacity 0P2: 0.25HP 1P0: 1.0HP 3P0: 3.0HP 7P5: 7.5HP
0.5
1
2
3
5
7.5
10
0.4
0.75
1.5
2.2
3.7
5.5
7.5
4 4
4 4
4
4 4 4 4
4 4 4
4 4
4 4
4 4
4 4
Accessories
• AC line reactors • EMI filters • RF filter • Braking resistors • Fuse kits and replacement fuses • rail mounting adapter (see “Accessories” table for applicability) • keypads • cables in 1, 3, and 5-meter lengths • interface • and eight-port serial communication breakout boards • KEPDirect I/O or OPC Server • GSoft drive configuration software
• erial communication cables available for creating plug and play RS-232/RS-485 networks with AutomationDirect PLCs. See the comm cable matrix on page DR-93 • – USB to RS-485 PC adapter (see “Communications Products” chapter for detailed information) Detailed descriptions and specifications for GS accessories are available in the “GS/DURApulse Accessories” section.
Typical Applications • Conveyors • Fans • Pumps • Compressors • HVAC handling • • tools
0P5: 0.5HP 2P0: 2.0HP 5P0: 5.0HP 010: 10HP
Input Voltage 1: 100-120VAC 2: 200-240VAC 4: 380-480VAC 5: 500-600VAC
Series Name Book 2 (14.1)
eDR-22
AC Drives
1-800-633-0405
Page 2
Prices as of April 16, 2014. Check Web site for most current prices.
GS2 Series Specifications
Company Information Drives
115V CLASS GS2 SERIES Model
GS2-10P2
GS2-10P5
GS2-11P0
Price
$156.00
$166.00
$186.00
HP
1/4hp
1/2hp
1hp kW
0.2kW
0.4kW
0.75kW
0.6
1.0
1.6
Motor Rating
Rated Output Capacity (kVA) Rated Input Voltage
Single-phase : 100 to 120 VAC ±10% 50/60 Hz ±5%�
Rated Output Voltage
Three-phase, two times proportion to input voltage
Rated Input Current (A) Rated Output Current (A) DC Braking
9
16
1.6
2.5
4.2
24
34
46
Weight (lb)
3.5
3.6
3.7
Sensors: Proximity
151.0 x 100.0 x 140.5 [5.94 x 3.94 x 5.53]
LR-10P2-1PH
Output side of drive (3 Phase)*
Braking Resistor
LR-10P5-1PH
Sensors: Limit Switches
LR-21P0 GS-20P5-BR
EMI Filter
20DRT1W3S
RF Filter
RF220X00A
Fuse Kit
LR-11P0-1PH
LR-20P5 GS-20P5-BR
GS-21P0-BR
Single Phase**
GS-10P2-FKIT-1P
GS-10P5-FKIT-1P
GS-11P0-FKIT-1P
GS-10P2-FUSE-1P
GS-10P5-FUSE-1P
GS-11P0-FUSE-1P
GS2-DR02
Spare Keypad, GS2 Series Drive
GS2-KPD
Keypad Cable, GS2 Series, 1 meter
GS-CBL2-1L
Keypad Cable, GS2 Series, 3 meter
GS-CBL2-3L
Keypad Cable, GS2 Series, 5 meter Ethernet Communications module for GS Series Drives (DIN rail mounted) USB to RS232 PC Communication Adapter RS-232 Serial Cable, GS2 Drive to DL05/06, CLICK, D2-250/260, D4-450, P3-550 USB to RS-485 PC Communication Adapter RS-485 Communication Distribution Module (for creating plug and play RS-485 networks) RS-485 Serial Cable, GS Drive to DL06/D2-260 RS-485 Serial Cable, GS Drive to ZIPLink CDM Module Software
GS-CBL2-5L
OPC Server
Sensors: Current Sensors: Pressure Sensors: Temperature
Replacement Fuses Single Phase** DIN Rail Mounting Adapter
Sensors: Photoelectric Sensors: Encoders
Accessories Input side of drive (1 Phase)*
Power Transmission Motion: Servos and Steppers
Frequency 60–0 Hz, 0–100% rated current, start time 0.0–5.0 seconds, Stop Time 0.0–25.0 seconds
Watt Loss @ 100% I (W)
Line Reactor
Motors
Motor Controls
6
Dimensions*** (HxWxD) (mm [in])
Soft Starters
Sensors: Level Sensors: Flow Switches Pushbuttons and Lights Stacklights Signal Devices
GS-EDRV100
Process
USB-RS232
Relays and Timers
GS-RJ12-CBL-2 USB-485M
Pneumatics: Air Prep
ZL-CDM-RJ12X4 / ZL-CDM-RJ12X10
Pneumatics: Directional Control Valves
GS-485HD15-CBL-2 GS-485RJ12-CBL-2
Pneumatics: Cylinders
GSoft / KEPDirect
Pneumatics: Tubing
KEPDirect
*Note: GS2-1xxx drives require 115V class input line reactors and 230V class output line reactors.
Pneumatics: Air Fittings
**Note: Single phase fuse kits and fuses are used only with GS2-1xxx drives. ***Note: Height dimension does not include external ground terminal, which adds 10 to 15 mm. Refer to dimensional drawings for details.
Appendix Book 2 Terms and Conditions
Book 2 (14.1)
www.automationdirect.com/drives
AC Drives eDR-23
Page 3
Prices as of April 16, 2014. Check Web site for most current prices.
GS2 Series Specifications 230V CLASS GS2 SERIES Model Price Motor Rating
GS2-20P5
GS2-21P0
GS2-22P0
GS2-23P0
GS2-25P0
GS2-27P5 $465.00
$158.00
$177.00
$251.00
$309.00
$363.00
HP
1/2hp
1hp
2hp
3hp
5hp
7.5hp kW
0.4kW
0.75kW
1.5kW
2.2kW
3.7kW
5.5kW
1.0
1.9
2.7
3.8
6.5
9.5
Rated Output Capacity (kVA) Rated Input Voltage
Three-phase : 200/208/220/230/240 VAC ±10%; 50/60 Hz ±5%
Single/Three-phase : 200/208/220/230/240 VAC ±10%; 50/60Hz ±5%
Rated Output Voltage
Three-phase : Corresponds to input voltage
Rated Input Current (A)
6.3/2.9
11.5/6.3
15.7/8.8
27.0/12.5
19.6
28
Rated Output Current (A)
2.5
5.0
7.0
10
17
25
DC Braking
Frequency 60–0 Hz, 0–100% rated current, start time 0.0–5.0 seconds, Stop Time 0.0–25.0 seconds
Watt Loss @ 100% I (W)
34
57
77
111
185
255
Weight (lb)
3.5
3.6
3.7
8.5
8.5
8.5
Dimensions* (HxWxD) (mm [in])
151.0 x 100.0 x 140.5 [5.94 x 3.94 x 5.53]
220.0 x 125.0 x 189.5 [8.66 x 4.92 x 7.46]
Accessories Line Reactor
Single-Phase Three-Phase
Braking Resistor
LR-20P5-1PH
LR-21P0-1PH
LR-22P0-1PH
LR-23P0-1PH n/a n/a
LR-20P5
LR-21P0
LR-22P0
LR-23P0
LR-25P0
LR-27P5
GS-20P5-BR
GS-21P0-BR
GS-22P0-BR
GS-23P0-BR
GS-25P0-BR
GS-27P5-BR
EMI Filter (single phase input)
20DRT1W3S
RF Filter
32DRT1W3C
40TDS4W4B
RF220X00A
Single-Phase GS-20P5-FKIT-1P GS-21P0-FKIT-1P GS-22P0-FKIT-1P GS-23P0-FKIT-1P
Fuse Kit Replacement Fuses
N/A
N/A
GS-25P0-FKIT-3P
GS-27P5-FKIT
N/A
N/A
Three-Phase GS-20P5-FUSE-3P GS-21P0-FUSE-3P GS-22P0-FUSE-3P GS-23P0-FUSE-3P
GS-25P0-FUSE
GS-27P5-FUSE
GS2-DR02 n/a
Three-Phase
GS-20P5-FKIT-3P
Single-Phase
GS-20P5-FUSE-1P GS-21P0-FUSE-1P GS-22P0-FUSE-1P GS-23P0-FUSE-1P
DIN Rail Mounting Adapter
GS-21P0-FKIT-3P
GS-22P0-FKIT-3P
GS-23P0-FKIT-3P
Spare Keypad, GS2 Series Drive
GS2-KPD
Keypad Cable, GS2 Series, 1 meter
GS-CBL2-1L
Keypad Cable, GS2 Series, 3 meter
GS-CBL2-3L
Keypad Cable, GS2 Series, 5 meter Ethernet Communications module for GS Series Drives (DIN rail mounted) USB to RS232 PC Communication Adapter RS-232 Serial Cable, GS2 Drive to DL05/06, CLICK, D2-250/260, D4-450, P3-550 USB to RS-485 PC Communication Adapter RS-485 Communication Distribution Module (for creating plug and play RS-485 networks) RS-485 Serial Cable, GS Drive to DL06/D2-260 RS-485 Serial Cable, GS Drive to ZIPLink CDM Module Software
GS-CBL2-5L
OPC Server
GS-EDRV100 USB-RS232 GS-RJ12-CBL-2 USB-485M ZL-CDM-RJ12X4 / ZL-CDM-RJ12X10 GS-485HD15-CBL-2 GS-485RJ12-CBL-2 GSoft / KEPDirect KEPDirect
*Note: Height dimension does not include external ground terminal, which adds 10 to 15 mm. Refer to dimensional drawings for details.
Book 2 (14.1)
eDR-24
AC Drives
1-800-633-0405
Page 4
Prices as of April 16, 2014. Check Web site for most current prices.
GS2 Series Specifications
Company Information Drives
460V CLASS GS2 SERIES Model
GS2-41P0
GS2-42P0
GS2-43P0
GS2-45P0
GS2-47P5
GS2-4010
Price
$261.00
$303.00
$357.00
$410.00
$586.00
$725.00
Motor Rating
HP
1hp
2hp
3hp
5hp
7.5hp
10hp kW
0.8kW
1.5kW
2.2kW
4kW
5.5kW
7.5kW
2.3
3.1
3.8
6.2
9.9
13.7
Rated Output Capacity (kVA) Rated Input Voltage
Three-phase: 380/400/415/440/460/480 VAC ±10%; 50/60 Hz ±5%
Rated Output Voltage
Corresponds to input voltage 4.2
5.7
6.0
8.5
14
23
Rated Output Current (A)
3.0
4.0
5.0
8.2
13
18
Frequency 60–0 Hz, 0–100% rated current, Start Time 0.0–5.0 seconds, Stop Time 0.0–25.0 seconds
Watt Loss @ 100% I (W)
73
86
102
170
240
255
Weight (lb)
3.5
3.6
3.7
8.5
8.5
8.5
Dimensions* (HxWxD) (mm [in])
151.0 x 100.0 x 140.5 [5.94 x 3.94 x 5.53]
220.0 x 125.0 x 189.5 [8.66 x 4.92 x 7.46]
Accessories Line Reactor
LR-41P0
LR-42P0
LR-43P0
LR-45P0
LR-47P5
Braking Resistor
GS-41P0-BR
GS-42P0-BR
GS-43P0-BR
GS-45P0-BR
GS-47P5-BR
EMI Filter
11TDT1W4S
RF Filter
17TDT1W44
LR-4010 GS-4010-BR 26TDT1W4B4
RF220X00A
Fuse Kit
GS-41P0-FKIT
GS-42P0-FKIT
GS-43P0-FKIT
GS-45P0-FKIT
GS-47P5-FKIT
GS-4010-FKIT
Replacement Fuses
GS-41P0-FUSE
GS-42P0-FUSE
GS-43P0-FUSE
GS-45P0-FUSE
GS-47P5-FUSE
GS-4010-FUSE
DIN Rail Mounting Adapter
GS2-DR02
Motors Power Transmission Motion: Servos and Steppers Motor Controls
Rated Input Current (A) DC Braking
Soft Starters n/a
Sensors: Proximity Sensors: Photoelectric Sensors: Encoders Sensors: Limit Switches Sensors: Current Sensors: Pressure Sensors: Temperature Sensors: Level Sensors: Flow Switches
Spare Keypad, GS2 Series Microdrive
GS2-KPD
Keypad Cable, GS2 Series, 1 meter
GS-CBL2-1L
Keypad Cable, GS2 Series, 3 meter
GS-CBL2-3L
Pushbuttons and Lights
Keypad Cable, GS2 Series, 5 meter Ethernet Communications Module for GS Series Drives (DIN rail mounted) USB to RS232 PC Communication Adapter RS-232 Serial Cable, GS2 Drive to DL05/06, CLICK, D2-250/260, D4-450, P3-550 USB to RS-485 PC Communication Adapter RS-485 Communication Distribution Module (for creating plug and play RS-485 networks) RS-485 Serial Cable, GS Drive to DL06/D2-260 RS-485 Serial Cable, GS Drive to ZIPLink CDM Module Software
GS-CBL2-5L
Stacklights
GS-EDRV100
Signal Devices
OPC Server
USB-RS232
Process
GS-RJ12-CBL-2
Relays and Timers
USB-485M
Pneumatics: Air Prep
ZL-CDM-RJ12X4 / ZL-CDM-RJ12X10 GS-485HD15-CBL-2
Pneumatics: Directional Control Valves
GS-485RJ12-CBL-2
Pneumatics: Cylinders
GSoft / KEPDirect KEPDirect
Pneumatics: Tubing
*Note: Height dimension does not include external ground terminal, which adds 10 to 15 mm. Refer to dimensional drawings for details.
Pneumatics: Air Fittings Appendix Book 2 Terms and Conditions
Book 2 (14.1)
www.automationdirect.com/drives
AC Drives eDR-25
Page 5
Prices as of April 16, 2014. Check Web site for most current prices.
GS2 Series Specifications 575V CLASS GS2 SERIES Model Price Motor Rating
GS2-51P0
GS2-52P0
GS2-53P0
GS2-55P0
GS2-57P5
GS2-5010
$279.00
$319.00
$378.00
$491.00
$721.00
$812.00
HP
1hp
2hp
3hp
5hp
7.5hp
10hp kW
0.75kW
1.5kW
2.2kW
3.7kW
5.5kW
7.5kW
1.7
3.0
4.2
6.6
9.9
12.2
Rated Output Capacity (kVA) Rated Input Voltage
Three-phase: 500 to 600 VAC -15/+10%; 50/60 Hz ±5%
Rated Output Voltage
Corresponds to input voltage
Rated Input Current (A)
2.4
Rated Output Current (A)
1.7
DC Braking
4.2
5.9
7.0
10.5
12.9
3.0
4.2
6.6
9.9
12.2
Frequency 60-0 Hz, 0-100% rated current, Start Time 0.0-5.0 seconds, Stop Time 0.0-25.0 seconds
Watt Loss @ 100% I (W)
30
58
83
132
191
211
Weight (lb)
3.3
3.3
4.4
7.0
7.0
7.3
Dimensions* (HxWxD) (mm [in])
151.0 x 100.0 x 140.5 [5.94 x 3.94 x 5.53]
220.0 x 125.0 x 189.5 [8.66 x 4.92 x 7.46]
Accessories Line Reactor Braking Resistor
LR-51P0
LR-52P0
GS-42P0-BR
EMI Filter
LR-53P0
LR-55P0
LR-5010
GS-42P0-BR x (2) in parallel
GS-4010-BR x (2) in series not available
RF Filter
RF220X00A
Fuse Block (Edison 3-pole part #) Replacement Fuses (Edison Fuse part #) DIN Rail Mounting Adapter
BC6033PQ or CHCC3D or CHCC3DI HCLR6 HCLR10 (10 fuses per pack) (10 fuses per pack)
HCLR15 (10 fuses per pack)
GS2-DR02 n/a
Spare Keypad, GS2 Series Microdrive
GS2-KPD
Keypad Cable, GS2 Series, 1 meter
GS-CBL2-1L
Keypad Cable, GS2 Series, 3 meter
GS-CBL2-3L
Keypad Cable, GS2 Series, 5 meter Ethernet Communications Module for GS Series Drives (DIN rail mounted) USB to RS232 PC Communication Adapter RS-232 Serial Cable, GS2 Drive to DL05/06, CLICK, D2-250/260, D4-450, P3-550 USB to RS-485 PC Communication Adapter RS-485 Communication Distribution Module (for creating plug and play RS-485 networks) RS-485 Serial Cable, GS Drive to DL06/D2-260 RS-485 Serial Cable, GS Drive to ZIPLink CDM Module Software
GS-CBL2-5L
OPC Server
HCLR20 HCLR30 (10 fuses per pack) (10 fuses per pack)
GS-EDRV100 USB-RS232 GS-RJ12-CBL-2 USB-485M ZL-CDM-RJ12X4 / ZL-CDM-RJ12X10 GS-485HD15-CBL-2 GS-485RJ12-CBL-2 GSoft / KEPDirect KEPDirect
*Note: Height dimension does not include external ground terminal, which adds 10 to 15 mm. Refer to dimensional drawings for details.
Book 2 (14.1)
eDR-26
AC Drives
1-800-633-0405
Page 6
Prices as of April 16, 2014. Check Web site for most current prices.
GS2 Series, General Specifications
Company Information Drives
General Specifications
Soft Starters
Control Characteristics Control System
Sinusoidal Pulse Width Modulation, carrier frequency 1kHz–12kHz
Output Frequency Resolution
0.1 Hz
Overload Capacity
150% of rated current for 1 minute
Motors Power Transmission
Torque Characteristics
Includes auto-torque boost, auto-slip compensation, starting torque 125% @ 0.5Hz/150% @ 5.0Hz
Braking Torque
20% without dynamic braking resistor, 125% with optional braking resistor
DC Braking
Operation frequency 60–0 Hz, 0–100% rated current. Start time 0.0–5.0 seconds. Stop time 0.0–0 25.0 seconds
Acceleration/Deceleration Time
0.1 to 600 seconds (linear or non-linear acceleration/deceleration), second acceleration/deceleration available
Voltage/Frequency Pattern
V/F pattern adjustable. Settings available for Constant Torque - low and high starting torque, Variable Torque - low and high starting torque, and user configured
Stall Prevention Level
20 to 200% or rated current
Operation Specifications
Inputs
External Signal
Potentiometer - 3k to 5kh/2W, 0 to 10VDC (input impedance 10kh), 0 to 20mA / 4 to 20 mA (input impedance 250h), Multi-speed inputs 1 to 3, Serial Communication RS232 and RS485 (Modbus RTU)
Operation Setting
Keypad
Setting by <RUN>, <STOP> buttons
External Signal
Input Terminals
Digital
Forward/Stop, Reverse/Stop (run/stop, fwd/rev), 3-wire control, Serial Communication RS232 and RS485 (Modbus RTU) 6 user-programmable: FWD/STOP, REV/STOP, RUN/STOP, REV/FWD, Run momentary (N.O.), STOP momentary (N.C.), External Fault (N.O./N.C.), External Reset, Multi-Speed Bit (1-3), Jog, External Base Block (N.O./N.C.), Second Accel/Decel Time, Speed Hold, Increase Speed, Decrease Speed, Reset Speed to Zero, PID Disable (N.O.), PID Disable (N.C.), Input Disable 1 user-configurable, 0 to 10VDC (input impedance 10k h) or 0 to 20mA / 4 to 20mA (input impedance 250h ), 10 bit resolution Frequency setpoint or PID process variable PV
Outputs
Output Terminals
Digital
2 user-programmable; Inverter Running, Inverter Fault, At Speed, Zero Speed, Above Desired Frequency, Below Desired Frequency, At Maximum Speed, Over Torque Detected, Above Desired Current, Below Desired Current, PID Deviation Alarm
Analog
1 user-programmable: 0 to 10VDC (max load 2mA), 8 bit resolution frequency, current, process variable PV
Operating Functions Protective Functions
Operator Interface
Environment
Options
Sensors: Proximity
Sensors: Encoders
Setting by <UP> or <DOWN> buttons or potentiometer
Analog
Motor Controls
Sensors: Photoelectric
Keypad
Frequency Setting
Motion: Servos and Steppers
Automatic voltage regulation, voltage/frequency characteristics selection, non-linear acceleration/deceleration, upper and lower frequency limiters, 7-stage speed operation, adjustable carrier frequency (1 to 12 kHz), PID control, skip frequencies, analog gain & bias adjustment, jog, electronic thermal relay, automatic torque boost, trip history, software protection Electronic Thermal, Overload Relay, Auto Restart after Fault, Momentary Power Loss, Reverse Operation Inhibit, Auto Voltage Regulation, Over-Voltage Trip Prevention, Auto Adjustable Accel/Decel, Over-Torque Detection Mode, Over-Torque Detection Level, Over-Torque Detection Time, Over-Current Stall Prevention during Acceleration, Over-Current Stall Prevention during Operation
Sensors: Limit Switches Sensors: Current Sensors: Pressure Sensors: Temperature Sensors: Level Sensors: Flow Switches Pushbuttons and Lights Stacklights Signal Devices
Operator Devices
8-key, 4-digit, 7-segment LED, 14 status LEDs, potentiometer
Programming
Parameter values for setup and review, fault codes
Status Display
Actual Operating Frequency, RPM, Scaled Frequency, Amps, % Load, Output Voltage, DC Bus Voltage, Process Variable, Set-point Frequency
Relays and Timers
Key Functions
RUN, STOP/RESET, FWD/REV, PROGRAM, DISPLAY, <UP>, <DOWN>, ENTER
Enclosure Rating
Protected chassis, IP20
Pneumatics: Air Prep
Ambient Temperature
-10° to 50°C (14°F to 122°F) -10° to 40°C (14°F to 104°F) For models 7.5 hp (5.5 kW) and higher
Storage Temperature
-20° to 60 °C (-4°F to 140°F) - during short-term transportation period
Ambient Humidity
20 to 90% RH (non-condensing)
Vibration
9.8 m/s2 (1G), less than 10Hz; 5.9 m/s2 (0.6G) 10 to 60 Hz
Installation Location
Altitude 1000m or lower above sea level, keep from corrosive gas, liquid and dust
Process
Pneumatics: Directional Control Valves Pneumatics: Cylinders Pneumatics: Tubing
Noise filter, input AC reactor, output AC reactor, cable for remote operator, programming software (GSOFT), Dynamic braking resistor, input fuses, ethernet interface (GS-EDRV100), EMI filters
Pneumatics: Air Fittings Appendix Book 2 Terms and Conditions
Book 2 (14.1)
www.automationdirect.com/drives
AC Drives eDR-27
Page 7
Prices as of April 16, 2014. Check Web site for most current prices.
GS2 Specifications, Installation Understanding the installation requirements for your GS2 drive will help to ensure that it operates within its environmental and electrical limits. Note: Never use only this catalog for installation instructions or operation of equipment; refer to the user manual, GS2-M.
Environmental Specifications
Fan
Protective Structure 1 IP20 Ambient Operating Temperature 2
-10 to 50°C (14°F to 122°F) -10 to 40°C (14°F to 104°F) for models 7.5HP and higher
Storage Temperature 3
-20 to 60°C (-4°F to 140°F)
Humidity
To 90% (no condensation)
Vibration 4
5.9 m/s2 (0.6g), 10 to 55 Hz
Location
Altitude 1,000 m or less, indoors (no corrosive gases or dust)
6in [150mm] minimum 2in [50mm] min
2in [50mm] minimum
1: Protective structure is based upon EN60529 2: ambient temperature must be in the range of -10° to 40° C. If the range will be up to 50° C, you will need to set the carrier frequency to 2.1 kHz or less and derate the output current to 80% or less. See our Web site for derating curves.
6in [150mm] minimum
3: storage temperature refers to the short-term temperature during transport. 4: to the test method specified in JIS CO911 (1984) Input Power
Watt-loss Chart GS2 Drive Model
At full load
GS2-10P2
24
GS2-10P5
34
GS2-11P0
46
GS2-20P5
34
GS2-21P0
57
GS2-22P0
77
GS2-23P0
111
GS2-25P0
185
GS2-27P5
255
GS2-41P0
73
GS2-42P0
86
GS2-43P0
102
GS2-45P0
170
GS2-47P5
240
GS2-4010
255
GS2-51P0
30
GS2-52P0
58
GS2-53P0
83
GS2-55P0
132
GS2-57P5
191
GS2-5010
211
To Motor
Warning: M aximum ambient temperatures must not exceed 50°C (122°F), or 40°C (104°F) for models 7.5 hp (5.5 kW) and higher!
Panel
Air Flow
Ground braid copper lugs
Panel or single point ground*
Star washers*
* For painted sub-panels, scrape the paint from underneath the star washers before tightening them.
Warning: AC drives generate a large amount of heat which may damage the AC drive. Auxiliary cooling methods are typically required in order not to exceed maximum ambient temperatures.
Book 2 (14.1)
eDR-28
AC Drives
1-800-633-0405
Page 8
Prices as of April 16, 2014. Check Web site for most current prices.
GS2 Specifications, Terminals
Company Information Drives
Main Circuit Wiring
Soft Starters
Terminal Description Input power L1, L2, L3 AC drive output T1, T2, T3 DB resistor input B1, B2
Motors Power Transmission
Ground
Motion: Servos and Steppers Motor Controls Sensors: Proximity Sensors: Photoelectric Sensors: Encoders Sensors: Limit Switches Sensors: Current Sensors: Pressure Sensors: Temperature Sensors: Level Sensors: Flow Switches Pushbuttons and Lights Stacklights Signal Devices
Control Circuit Terminals Terminal Symbol R1O R1C R1 R2O R2C R2 DI1 DI2 DI3 DI4 DI5 DI6 DCM AI +10V AO ACM
Description
Process
Relay output 1 normally open Relay output 1 normally closed
Relays and Timers
Relay output 1 common
Pneumatics: Air Prep
Relay output 2 normally open Relay output 2 normally closed
Pneumatics: Directional Control Valves
Relay output 2 common Digital input 1 Digital input 2
Pneumatics: Cylinders
Digital input 3 Digital input 4
Pneumatics: Tubing
Digital input 5 Digital input 6
Pneumatics: Air Fittings
Digital common Analog input
Appendix Book 2
Internal power supply (DC 10V) @ 10 mA Analog output
Terms and Conditions
Analog common
Note: twisted-shielded, twisted-pair or shielded-lead wires for the control signal wiring. It is recommended to run all signal wiring in a separate steel conduit. The shield wire should only be connected at the drive. Do not connect shield wire on both ends.
Book 2 (14.1)
www.automationdirect.com/drives
AC Drives eDR-29