Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact
Page 1 of GS2 Series Drives

Spec sheet · AutomationDirect

GS2 Series Drives

Spec sheet15 pagesPDF 2.7 MB

Catalog pages for AutomationDirect GS2 Series AC drives: features, specifications, installation, terminals, wiring and dimensions.

Download the PDF2.7 MB

Covers · 1 model

The models it covers

Summary

What is in it

Catalog pages for the AutomationDirect GS2 Series AC drives, which add dynamic braking, PID control and a removable keypad to the GS1 feature set. They cover the part numbering system, specifications for the 115V, 230V, 460V and 575V classes, accessories such as line reactors, filters, braking resistors and keypad cables, installation, control terminals, basic wiring, dimensions, wiring solutions and communications options.

Its parts

  1. GS2 Specifications
  2. GS2 Installation
  3. GS2 Terminals
  4. GS2 Basic Wiring
  5. GS2 Dimensions
  6. Wiring Solutions
  7. Communications
  8. Hitachi Drives Cross References

From the sheet

Key facts from this sheet

Each line names its page in the PDF.

AutomationDirect catalog pages (prices as of April 2014) for the GS2 series AC drives, 1/4 to 10 hp in 115V, 230V, 460V and 575V classes. They give the ratings of each model, the general specifications, the accessories that fit each model, the terminals and a basic wiring diagram. They also include a ZIPLink communication cable selector and Hitachi SJ300, L100 and SJ100 cross references.

Read for this summary: pages 1 to 9 and 11 to 15 of 15.

What it is
AC drive with Volts/Hertz control, sinusoidal PWM, IGBT technology, dynamic braking and PID p. 1
Ratings
115V class 1/4 to 1 hp; 230V class 1/2 to 7.5 hp; 460V and 575V classes 1 to 10 hp p. 2, 3, 4, 5
Input voltage
Code 1: 100-120 VAC; 2: 200-240 VAC; 4: 380-480 VAC; 5: 500-600 VAC p. 1
I/O
1 analog and 6 programmable digital inputs; 1 analog and 2 programmable relay outputs p. 1
Relay contacts
120VAC/24VDC at 5A; 230VAC at 2.5A p. 9
Communications
RS-232 or RS-485 Modbus RTU on an RJ-12 (6P4C) port, up to 38.4 Kbps p. 1, 6, 9
Analog I/O
Input 0 to 10VDC or 0/4 to 20mA, 10 bit; output 0 to 10VDC, 2mA max load, 8 bit p. 6
Overload
150% of rated current for 1 minute; starting torque 125% at 0.5Hz, 150% at 5.0Hz p. 6
Braking torque
20% without a dynamic braking resistor; 125% with the optional resistor p. 6
Keypad
Removable; 8 keys, 4-digit 7-segment LED, 14 status LEDs, potentiometer p. 1, 6
Ambient temperature
-10 to 50°C; -10 to 40°C for models 7.5 hp (5.5 kW) and higher p. 6
Enclosure
Protected chassis, IP20 p. 6
Keypad parts
Spare keypad GS2-KPD; keypad cables GS-CBL2-1L (1 meter) and GS-CBL2-3L (3 meter) p. 2
Comm options
Ethernet interface GS-EDRV100; USB to RS-485 adapter USB-485M; GSoft configuration software p. 1, 6

What this sheet walks you through

  • Reading the GS2 part number (voltage code and motor size) p. 1
  • Ratings, current, watt loss and weight of each model p. 2, 3, 4, 5
  • Choosing line reactors, braking resistors, filters and fuses for each model p. 2, 3, 4, 5
  • Installation environment, clearances and grounding p. 7
  • Main circuit and control circuit terminals p. 8
  • Basic wiring diagram, including the RJ-12 serial port pinout p. 9
  • Choosing ZIPLink cables to connect the drive to PLCs p. 13
  • Finding a GS2 replacement for Hitachi SJ300, L100 and SJ100 drives p. 14, 15

Good to know

  • Above 40°C and up to 50°C, the carrier frequency must be 2.1 kHz or less and output current derated to 80% or less. p. 7
  • A modem or telephone plugged into the RJ-12 serial port may cause permanent damage. p. 9
  • GS2-1xxx drives need 115V class input line reactors and 230V class output line reactors. p. 2
  • The sheet states that the 575V GS2-5xxx drives are not CE compliant. p. 1
  • The catalog is not meant as installation instructions; it points to the GS2-M user manual. p. 7

Questions this sheet answers

What serial communication does the GS2 drive have?

RS-232 or RS-485 Modbus RTU through an RJ-12 port, at up to 38.4 Kbps. An Ethernet interface, GS-EDRV100, is an option. p. 1, 6, 9

What are the GS2 relay output contact ratings?

The multi-function output contacts are rated 120VAC/24VDC at 5A or 230VAC at 2.5A. p. 9

Can a GS2 drive run at 50°C?

Models below 7.5 hp are rated to 50°C, but above 40°C the carrier frequency must be 2.1 kHz or less and output current derated to 80% or less. p. 7

What does the part number GS2-47P5 mean?

GS2 series, input voltage code 4 (380-480VAC), 7.5HP motor capacity. p. 1

Which GS2 drive replaces a Hitachi SJ300-007LFU?

The cross reference lists the GS2-21P0 (1.0 hp). Replacements may differ in dimensions, mounting holes and terminal layout. p. 14

The whole text · 2 parts

Read the sheet here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 81-8
  2. Pages 9 to 159-15

The file

Revision and size

RevisionBook 2 (14.1), April 16, 2014
PublisherAutomationDirect
Pages15
PDF2.7 MB
TextText from the PDF itself.

The first pages · 4 of 15

Look before you download

Each page opens the PDF at that page.

Page 1
Page 1of 15
Page 2
Page 2of 15
Page 3
Page 3of 15
Page 4
Page 4of 15

More documents · 1