Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact
Page 1 of GS2 Series Drives User Manual

Manual · AutomationDirect

GS2 Series Drives User Manual

Manual190 pagesPDF 5.6 MB

User manual for the AutomationDirect GS2 Series AC drives: installation, wiring, keypad setup, parameters and Modbus communications.

Download the PDF5.6 MB

Covers · 1 model

The models it covers

Summary

What is in it

The AutomationDirect user manual for the GS2 Series AC drives, which vary the speed of three phase AC induction motors. It covers drive specifications and model numbering, ambient conditions, installation, dimensions and circuit connections, the digital keypad and a quickstart, the full parameter set (motor, ramp, volts/hertz, digital, analog, PID, protection and communication), Modbus communications with DirectLOGIC PLCs and third-party devices, maintenance and troubleshooting, and accessories.

Its parts

  1. Getting Started
  2. Installation and Wiring
  3. Keypad Operation and Quickstart
  4. AC Drive Parameters
  5. GS2 Modbus Communications
  6. Maintenance and Troubleshooting

From the manual

Key facts from this manual

Some pages are scans or cannot be read; this says only what the readable text supports. Each line names its page in the PDF.

User manual (first edition, revision C, dated 12/2006) for the AutomationDirect GS2 series AC drives, 0.25 to 10 hp in 115V, 230V, 460V and 575V input classes. It covers specifications, installation and wiring, the keypad and a quickstart, the parameters, Modbus communications, fault codes and accessories such as the GS-EDRV Ethernet interface.

Read for this summary: pages 1 to 4, 7 to 8, 11, 13 to 16, 26 to 27, 30, 143 to 146 and 166 of 190.

Ratings
115V input 0.25-1.0 hp; 230V 0.5-7.5 hp; 460V 1.0-10 hp; 575V 1.0-10 hp p. 1
Input voltage
Code 1: 100-120VAC; 2: 200-240VAC; 4: 380-480VAC; 5: 500-600VAC p. 11
I/O
6 programmable digital inputs, 1 analog input, 2 programmable relay outputs, 1 analog output p. 15, 26
Relay contacts
120 VAC / 24 VDC at 5A; 230 VAC at 2.5A p. 26
Digital inputs
Internally supplied, 4-12V range; no external voltage sources p. 26
Analog I/O
Input 0 to 10 VDC, 0 to 20 mA or 4 to 20 mA, 10 bit; output 0 to 10 VDC, 2mA max, 8 bit; +10 VDC supply, 10 mA max p. 15, 26
Communications
RS-232C and RS-485 Modbus RTU on an RJ-12 (6P4C) port p. 15, 27
Overload
150% of rated current for 1 minute; starting torque 125% at 0.5 Hz, 150% at 5.0 Hz p. 15
Braking
Built-in braking transistor; braking torque 20% without, 125% with the optional braking resistor p. 15
Keypad
4-digit LED display, 14 LED indicators, 8 function keys, potentiometer p. 30
Ambient temperature
-10°C to 50°C; -10°C to 40°C for models 7.5 hp (5.5 kW) and higher p. 16
Short circuit withstand
5kA rms symmetrical (at 120, 240, 480 or 600 VAC by class) p. 13, 14
Fault codes
oc: abnormal current increase; ou: DC bus voltage above maximum; Lu: DC bus voltage below minimum p. 143
Ethernet option
GS-EDRV, DIN rail mounted, external 24 VDC (10-33 VDC, 90-135 mA), fits all GS2 models p. 166

What this manual walks you through

  • Checking the package, the model number and the nameplate p. 11
  • Ratings and specifications of each model p. 13, 14, 15, 16
  • Wiring the control terminals p. 26
  • Basic wiring diagram and the RJ-12 serial port pinout p. 27
  • Using the digital keypad and reading its LED indicators p. 30
  • Fault codes and corrective actions p. 143, 144, 145
  • Communication and PID warning messages p. 146
  • Connecting the drive to Ethernet with the GS-EDRV interface p. 166
  • Modbus communication with DirectLOGIC PLCs and third-party devices p. 8

Good to know

  • External voltage sources must not be connected to the digital inputs, or permanent damage may result. p. 26
  • A modem or telephone plugged into the RJ-12 port may cause permanent damage; pins 2 and 5 are not a power source. p. 27
  • The output short circuit protection protects the drive, not the user. p. 145
  • The manual states UL and cUL listing; CE applies only to the 115V, 230V and 460V class drives. p. 16
  • Control signal shields are connected only at the drive end. p. 26

Questions this manual answers

How do I see past faults on a GS2 drive?

The six most recent faults are shown on the keypad in P6.31 to P6.36. Faults are cleared by a reset from the keypad or an input terminal. p. 143

What does fault ou mean on a GS2?

The drive detected that the DC bus voltage exceeded its maximum allowable value. p. 143

Does the GS-EDRV Ethernet interface need its own power?

Yes, it needs an external 24 VDC supply; its input range is 10-33 VDC at 90-135 mA. p. 166

Can I power the GS2 digital inputs from an external 24V supply?

No. The digital inputs are internally supplied, and external voltage sources may cause permanent damage. p. 26

The whole text · 19 parts

Read the manual here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 101-10
  2. Pages 11 to 2011-20
  3. Pages 21 to 3021-30
  4. Pages 31 to 4031-40
  5. Pages 41 to 5041-50
  6. Pages 51 to 6051-60
  7. Pages 61 to 7061-70
  8. Pages 71 to 8071-80
  9. Pages 81 to 9081-90
  10. Pages 91 to 10091-100
  11. Pages 101 to 110101-110
  12. Pages 111 to 120111-120
  13. Pages 121 to 130121-130
  14. Pages 131 to 140131-140
  15. Pages 141 to 150141-150
  16. Pages 151 to 160151-160
  17. Pages 161 to 170161-170
  18. Pages 171 to 180171-180
  19. Pages 181 to 190181-190

The file

Revision and size

Part no.GS2-M
RevisionFirst Edition, Revision C, 12/2006
PublisherAutomationDirect
Pages190
PDF5.6 MB
TextText from the PDF itself; page 190 is a scan, read by OCR, which may hold reading errors.
GS2-M

The first pages · 3 of 190

Look before you download

Each page opens the PDF at that page.

Page 1
Page 1of 190
Page 2
Page 2of 190
Page 3
Page 3of 190

More documents · 1

For the same models