Page 141
MAINTENANCE AND TROUBLESHOOTING
CHAPTER
6
In This Chapter... Maintenance and Inspection . . . . . . . . . . . . . . . . .6–2 Monthly Inspection: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6–2 Annual Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6–2
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . .6–3 Fault Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6–3 Warning Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6–6
Page 142
Chapter 6: Maintenance and Troubleshooting
Maintenance and Inspection Modern AC drives are based on solid state electronics technology. Preventive maintenance is required to operate the AC drive in its optimal condition, and to ensure a long life. It is recommended that a qualified technician perform a regular inspection of the AC drive. Some items should be checked once a month, and some items should be checked yearly. Before the inspection, always turn off the AC Input Power to the unit. Wait at least 2 minutes after all display lamps have turned off, and then confirm that the capacitors have fully discharged by measuring the voltage between B1 and Frame Ground using a multimeter set to measure DC voltage. WARNING! Disconnect AC power and ensure that the internal capacitors have fully discharged before inspecting the AC drive!
Monthly Inspection: Check the following items at least once a month. 1. Make sure the motors are operating as expected. 2. Make sure the installation environment is normal. 3. Make sure the cooling system is operating as expected. 4. Check for irregular vibrations or sounds during operation. 5. Make sure the motors are not overheating during operation. 6. Check the input voltage of the AC drive and make sure the voltage is within the operating range. Check the voltage with a voltmeter.
Annual Inspection Check the following items once annually. 1. Tighten and reinforce the screws of the AC drive if necessary. They may loosen due to vibration or changing temperatures. 2. Make sure the conductors and insulators are not corroded and damaged. 3. Check the resistance of the insulation with mega-ohm meter. 4. Check the capacitors and relays; may require qualified repair shop to replace any defective components. Drive components are NOT field serviceable or replaceable. 5. Clean off any dust and dirt with a vacuum cleaner. Pay special attention to cleaning the ventilation ports, heat sinks, and PCBs. Always keep these areas clean. Accumulation of dust and dirt in these areas can cause unforeseen failures.
If the AC drive is not used for a long period of time, turn the power on at least once every two years and confirm that it still functions properly. To confirm functionality, disconnect the motor and energize the AC drive for 5 hours or more before attempting to run a motor with it.
6–2
GS2 Series AC Drive User Manual
Page 143
Chapter 6: Maintenance and Troubleshooting
Troubleshooting Fault Codes The AC drive has a comprehensive fault diagnostic system that includes several different alarms and fault messages. Once a fault is detected, the corresponding protective functions will be activated. The fault codes are then displayed on the digital keypad display. The six most recent faults can be read on the digital keypad display by viewing P6.31 to P6.36. NOTE: Faults can be cleared by a reset from the keypad or input terminal.
Fault Codes Fault Name Fault Descriptions
The AC drive detects an abnormal oc increase in current.
ou
The AC drive detects that the DC bus voltage has exceeded its maximum allowable value.
The AC drive temperature sensor oX detects excessive heat.
The AC drive detects that the DC
Lu bus voltage has fallen below its oL
1st Ed. Rev. C
Corrective Actions 1. Check whether the motor's horsepower corresponds to the AC drive output power. 2. Check the wiring connections between the AC drive and motor for possible short circuits. 3. Increase the Acceleration time (1-01 or 1-05). 4. Check for possible excessive loading conditions at the motor. 5. If there are any abnormal conditions when operating the AC drive after short-circuit is removed, the AC drive should be sent back to the manufacturer. 1. Check whether the input voltage falls within the rated AC drive input voltage. 2. Check for possible voltage transients. 3. Bus over-voltage may also be caused by motor regeneration. Either increase the decel time or add an optional braking resistor. 4. Check whether the required braking power is within the specified limits. 1. Ensure that the ambient temperature falls within the specified temperature range. 2. Make sure that the ventilation holes are not obstructed. 3. Remove any foreign objects on the heat sinks and check for possible dirty heat sink fins. 4. Provide enough spacing for adequate ventilation. Check whether the input voltage falls within the AC drive’s rated input voltage.
minimum value. The AC drive detects excessive drive 1. Check whether the motor is overloaded. output current. Note: The AC drive can withstand 2. Reduce torque compensation setting as set in 2-03. up to 150% of the rated current for 3. Increase the AC drive’s output capacity. a maximum of 60 seconds.
12/2006
GS2 Series AC Drive User Manual
6–3
Page 144
Chapter 6: Maintenance and Troubleshooting
Fault Codes Fault Name
Fault Descriptions oL1 Internal electronic overload trip oL2 ocA ocd ocn cF1 cF2
Corrective Actions 1. Check for possible motor overload. 2. Check electronic thermal overload setting. 3. Increase motor capacity. 4. Reduce the current level so that the AC drive output current does not exceed the value set by the Motor Rated Current 0-01.
1. Reduce the motor load. Motor overload. Check the parameter 2. Adjust the over-torque detection setting to an settings (6-07 to 6-09) appropriate level. Over-current during acceleration: 1. Short-circuit at motor output. 2. Torque boost too high. 3. Acceleration time too short. 4. AC drive output capacity is too small. Over-current during deceleration 1. Short-circuit at motor output. 2. Deceleration time too short. 3. AC drive output capacity is too small.
1. Check for possible poor insulation at the output line. 2. Decrease the torque boost setting in 2-03. 3. Increase the acceleration time. 4. Replace the AC drive with one that has a higher output capacity (next HP size). 1. Check for possible poor insulation at the output line. 2. Increase the deceleration time. 3. Replace the AC drive with one that has a higher output capacity (next HP size).
Over-current during steady state operation: 1. Check for possible poor insulation at the output line. 1. Short-circuit at motor output. 2. Check for possible motor stall. 2. Sudden increase in motor loading. 3. Replace the AC drive with one that has a higher output capacity (next HP size). 3. AC drive output capacity is too small. 1. Switch off power supply. Internal memory IC cannot be 2. Check whether the input voltage falls within the AC programmed. drive's rated input voltage. 3. Switch the AC drive back on. 1. Check the connections between the main control board and the power board. Internal memory IC can not be read. 2. Reset drive to factory defaults.
XPF Hardware protection failure
Return to the factory.
codE Software protection failure
Return to the factory.
cF3
AC Drive’s internal circuitry abnormal
1. Switch off power supply. 2. Check whether the input voltage falls within the rated AC drive input voltage. Switch on the AC drive.
DI terminal EF-CM goes from OFF to Remove EF-CM N.O. signal, restore EF-CM N.C. signal, or restore 4-20mA AI signal.
EF ON, or 4-20mA AI signal is lost cFA Auto accel/decel failure
6–4
Don’t use the function of auto acceleration/ deceleration.
GS2 Series AC Drive User Manual
Page 145
Chapter 6: Maintenance and Troubleshooting
Fault Codes Fault Name u CFF bb PHL
1st Ed. Rev. C
Fault Descriptions
Corrective Actions
Ground fault : The AC drive output is abnormal. When the output terminal is Ground fault : grounded (short circuit current is 50% more than the AC drive rated 1. Check whether the IGBT power module is damaged. current), the AC drive power 2. Check for possible poor insulation at the output line. module may be damaged. The short circuit protection is provided for AC drive protection, not user protection. External Base Block: AC drive output is turned off.
1. When the external input terminal (base-block) is active, the AC drive output will be turned off. 2. Disable this connection and the AC drive will begin to work again.
Input Power 3 phase loss: One phase of the input power is lost.
1. Check for possible poor connection on the input power line. 2. Check for possible loss of phase on input power line.
12/2006
GS2 Series AC Drive User Manual
6–5
Page 146
Chapter 6: Maintenance and Troubleshooting
Warning Messages There are several Warning Messages that a GS2 AC Drive may give. The GS2 AC Drive allows you to decide its response to these messages. The descriptions of the Warning Messages are listed below.
Warning Messages Warning Name
Ce01
Ce02
Ce03
Corrective Actions
Communications Warning: Illegal command code - The command code received in the command message is not available for the AC drive. Communications Warning: Illegal data address - The data The corrective action can be set with the Transmission address received in the command Fault Treatment parameter (9-03). The available settings message is not available for the are: AC drive. 0 - Display fault and continue operating Communications Warning: 1 - Display fault and RAMP to stop Illegal data value - The data value 2 - Display fault and COAST to stop received in the command 3 - No fault displayed and continue operating message is not available for the The default setting is 0. AC drive.
Ce04
Communications Warning: Slave device failure - The AC drive is unable to perform the requested action.
Ce!0
Communications Warning: Communication Time Out
FbE
6–6
Warning Descriptions
The corrective action can be set with the PID Feedback Loss parameter (P7.27). The available settings are: PID Warning: PID Feedback Loss - The 4-20mA PID 00 - Warn and AC Drive Stop signal has been lost. 01 - Warn and Continue The default setting is 00.
GS2 Series AC Drive User Manual
Page 147
ACCESSORIES
APPENDIX
A
In This Appendix... Accessories Part Numbering . . . . . . . . . . . . . . . . . . . . . . . . . .A–2 Line Reactors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A–2 Line Reactor Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A–4 Line Reactor Applications and Connections . . . . . . . . . . . . . . . . .A–5
Braking Resistors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A–8 Braking Resistor Connections . . . . . . . . . . . . . . . . . . . . . . . . . . .A–8 Braking Resistor Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . .A–9
EMI Input Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A–10 EMI Filter Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A–11 EMI Filter Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A–15
RF Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A–16 Fuses and Fuse Kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A–17 Fuses and Fuse Kits Dimensions . . . . . . . . . . . . . . . . . . . . . . . .A–18
GS-EDRV Ethernet Interface . . . . . . . . . . . . . . . . . . . . . . . . .A–20 GS Drive Configuration Software . . . . . . . . . . . . . . . . . . . . .A–22 System Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A–22 Software Configuration Methods . . . . . . . . . . . . . . . . . . . . . . .A–22
Miscellaneous Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . .A–25 Configuration Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A–25 Spare Keypad . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A–25 Keypad Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A–25 Communication Distribution Blocks . . . . . . . . . . . . . . . . . . . . .A–26
Page 148
Appendix A: Accessories
Accessories Part Numbering With the exception of EMI Filters, RF Filters, and some Line Reactors, GS2 Series accessory part numbers incorporate the part numbers of the AC Drives for which they are compatible. Each accessory part number begins with the AC Drive series and rating. This is followed by an accessory code, and, when applicable, a description code. The accessory part numbering scheme is shown below.
GS - 23P0 - LR - 3PH Description Code (optional) 1PH: Single phase 3PH: Three phase ENC: Enclosure Blank: For reactor, check specific part # to determine phase
Accessory Code BR: Braking resistor FKIT: Fuse Kit FUSE: Replacement fuses for FKIT LR: Line reactor
Drive Rating (See Drive P/N description) BZL: Bezel CBL: Cable DBU: Dynamic Brake Unit EDRV: Ethernet board FB: Feedback board KPD: Keypad RS: Recommended Standard
Drive Series GS: All GS and DURApulse Series Drives GS1: GS1 Series GS2: GS2 Series GS3: DURApulse Series
Line Reactors Input line reactors protect the AC drive from transient overvoltage conditions typically caused by utility capacitor switching. Input line reactors also reduce the harmonics associated with AC drives, and are recommended for all installations. Output line (load) reactors protect the motor insulation against AC drive short circuits and IGBT reflective wave damage, and also allow the motor to run cooler by “smoothing” the motor current waveform. They are recommended for operating “non-inverter-duty” motors, and for any motors when the length of wiring between the AC drive and motor exceeds 75 feet.
115V Single Phase Input Line Reactors* Part Number GS-10P2-LR GS-10P5-LR GS-11P0-LR
Rated Watt Impedance Inductance Amps Loss
GS2 Drive Model and Side / Phase / Volts
Drive hp
18
3%
0.80 mH
19
GS2-10P2 (input) / 1ph / 115V
0.25
25
3%
0.50 mH
23
GS2-10P5 (input) / 1ph / 115V
0.5
35
3%
0.40 mH
36
GS2-11P0 (input) / 1ph / 115V
1
*NOTE: Single phase line reactors should NOT be installed on the output side of the AC drive.
A–2
GS2 Series AC Drive User Manual
Page 149
Appendix A: Accessories
Line Reactors (continued) 230V Single Phase Input Line Reactors* Rated Watt Impedance Inductance Amps Loss
Part Number GS-20P5-LR-1PH GS-21P0-LR-1PH GS-22P0-LR-1PH GS-23P0-LR-1PH
GS2 Drive Model and Side / Phase / Volts
Drive hp
8
3%
6.50 mH
13
GS2-20P5 (input) / 1ph / 230V
0.5
12
3%
6.50 mH
13
GS2-21P0 (input) / 1ph / 230V
1
18
3%
3.00 mH
25
GS2-22P0 (input) / 1ph / 230V
2
35
3%
2.50 mH
26
GS2-23P0 (input) / 1ph / 230V
3
*NOTE: Single phase line reactors should NOT be installed on the output side of the AC drive.
230V Three Phase Input / Output Line Reactors Rated Watt Impedance Inductance Amps Loss
Part Number GS-20P5-LR-3PH GS-21P0-LR-3PH GS-22P0-LR-3PH GS-23P0-LR-3PH GS-25P0-LR GS-27P5-LR
GS2 Drive Model and Side / Phase / Volts
Drive hp
4
3%
6.50 mH
13
GS2-20P5 (in/out) / 3ph / 230V
0.5
4
3%
3.00 mH
7
GS2-21P0 (in/out) / 3ph / 230V
1
8
3%
1.50 mH
11
GS2-22P0 (in/out) / 3ph / 230V
2
12
3%
1.30 mH
23
GS2-23P0 (in/out) / 3ph / 230V
3
18
3%
0.80 mH
19
GS2-25P0 (in/out) / 3ph / 230V
5
25
3%
0.50 mH
23
GS2-27P5 (in/out) / 3ph / 230V
7.5
460V & 575V Three Phase Input / Output Line Reactors Part Number
Rated Watt Impedance Inductance Amps Loss
GS2 Drive Model and Side / Phase / Volts
Drive hp
GS2-41P0 (in/out) / 3ph / 460V
1
GS2-42P0 (in/out) / 3ph / 460V GS2-53P0 (in/out) / 3ph / 575V GS2-43P0 (in/out) / 3ph / 460V GS2-55P0 (in/out) / 3ph / 575V
2 3 3 5
GS-41P0-LR
2
3%
12.0 mH
7
GS-42P0-LR
4
3%
6.50 mH
13
GS-43P0-LR
8
3%
5.00 mH
31
GS-45P0-LR
8
3%
3.00 mH
25
GS2-45P0 (in/out) / 3ph / 460V
5
GS-47P5-LR
12
3%
2.50 mH
26
GS2-47P5 (in/out) / 3ph / 460V GS2-57P5 (in/out) / 3ph / 575V GS2-5010 (in/out) / 3ph / 575V
7.5 7.5 10
GS-4010-LR GS-51P0-LR GS-52P0-LR
18
3%
1.50 mH
29
GS2-4010 (in/out) / 3ph / 460V
10
2
3%
20.0 mH
9
GS2-51P0 (in/out) / 3ph / 575V
1
4
3%
9.10 mH
15
GS2-52P0 (in/out) / 3ph / 575V
2
1st Ed. Rev. C
12/2006
GS2 Series AC Drive User Manual
A–3
Page 150
Appendix A: Accessories
Line Reactor Dimensions AC Line Reactor Dimensions (inches) Part Number
H
W
D
Mtg. D
Mtg. W
Mtg Slot Hole Size
Weight (lbs)
GS-10P2-LR GS-10P5-LR GS-11P0-LR GS-20P5-LR-1PH GS-20P5-LR-3PH GS-21P0-LR-1PH GS-21P0-LR-3PH GS-22P0-LR-1PH GS-22P0-LR-3PH GS-23P0-LR-1PH GS-23P0-LR-3PH GS-25P0-LR GS-27P5-LR GS-41P0-LR GS-42P0-LR GS-43P0-LR GS-45P0-LR GS-47P5-LR GS-4010-LR GS-51P0-LR GS-52P0-LR
4.80
6.00
3.30
2.09
2.00
0.28 x 0.63
7
5.70
6.00
3.09
2.09
3.00
0.28 x 0.63
7
5.70
6.00
3.34
2.34
3.00
0.28 x 0.63
9
3.40
4.40
2.83
1.77
1.44
0.28 x 0.63
2.80
3.40
4.40
2.83
1.77
1.44
0.28 x 0.63
2.80
3.40
4.40
2.83
1.77
1.44
0.28 x 0.63
2.80
3.40
4.40
2.83
1.77
1.44
0.28 x 0.63
2.30
3.40
4.40
2.83
1.77
2.00
0.28 x 0.63
3.10
3.40
4.40
2.83
1.77
2.00
0.28 x 0.63
2.80
4.80
6.00
3.30
2.09
2.00
0.28 x 0.63
7.50
3.40
4.40
2.83
1.77
2.00
0.28 x 0.63
2.90
4.80
6.00
3.30
2.09
2.00
0.28 x 0.63
7.10
5.70
6.00
3.09
2.09
3.00
0.28 x 0.63
7.00
3.40
4.40
2.83
1.77
1.44
0.28 x 0.63
2.30
3.40
4.40
2.83
1.77
1.44
0.28 x 0.63
2.80
3.40
4.40
3.39
2.39
2.00
0.28 x 0.63
4.30
3.40
4.40
2.83
1.77
2.00
0.28 x 0.63
3.10
4.80
6.00
3.30
2.09
2.00
0.28 x 0.63
7.50
4.80
6.30
3.55
2.34
2.00
0.28 x 0.63
9.10
3.40
4.40
2.83
1.77
1.44
0.28 x 0.63
3
3.40
4.40
3.33
2.37
1.44
0.28 x 0.63
3
W
Top View MTG W
H
AC Line Reactor Dimensions
A–4
GS2 Series AC Drive User Manual
Label
Mounting Holes
MTG D
D