For the AutomationDirect GS2
Page 151
Appendix A: Accessories
Line Reactor Applications and Connections Input Side of AC Drive When installed on the input side of the AC Drive, line reactors will reduce line notching, and limit current and voltage spikes and surges from the incoming line. The line reactors will also reduce harmonic distortion from the AC Drive onto the line. Units are installed in front of the AC Drive as shown.
C1
C2
L3 T3
B1
B2
T2
L2
T1 A1
A2
L1
Output Side of AC Drive When installed on the output side of the AC Drive, line reactors protect the drive from short circuits at the load. Voltage and current waveforms from the drive are enhanced, reducing motor overheating and noise emissions.
T3
C1
C2
T2
B1
B2
T1
A1
A2
Single-phase line reactors should NOT be installed on the output of the AC Drive. Use only three-phase reactors on drive outputs.
1st Ed. Rev. C
12/2006
GS2 Series AC Drive User Manual
A–5
Page 152
Appendix A: Accessories
Line Reactor Applications and Connections (continued) Multiple AC Drives Individual line reactors are recommended when installing multiple AC Drives on the same power line. Individual line reactors eliminate cross-talk between multiple drives, and provide isolated protection for each drive for its own specific load.
C1
C2
L3 T3
B1
B2
T2
L2
T1 A1
A2
L1
C1
C2
L3
B1
B2
L2
T3 T2 T1 A1
A2
L1
Multiple Motors A single reactor can be used when the application calls for multiple motors on the same AC Drive, if the motors operate simultaneously. The reactor is sized based on the total horsepower of all the motors. Overload relays (not shown) are recommended for use in multi-motor applications.
T3
C1
C2
T2
B1
B2
T1
A1
A2
A single reactor should be used with multiple motors ONLY when the motors will operate simultaneously. OVERLOAD RELAYS are recommended for use in multiple motor applications.
A–6
GS2 Series AC Drive User Manual
Page 153
Appendix A: Accessories
Line Reactor Applications and Connections (continued) Single-Phase Applications Some of the line reactors are listed for use with single-phase input power. Follow the connection diagram shown below. Make sure that terminals B1 and B2 are properly insulated before any connections are made.
C1
C2
L2 T3
B1
T2
B2
T1 A1
A2
L1
WARNING: Please ensure that you properly insulate terminals B1 and B2 before making any connections to single-phase power.
1st Ed. Rev. C
12/2006
GS2 Series AC Drive User Manual
A–7
Page 154
Appendix A: Accessories
Braking Resistors Braking resistors are used to increase the control torque of the AC Drive, for frequently repeated ON-OFF cycles of the AC Drive, or for decelerating a load with large inertia. The use of braking resistors with GS2 Series AC drives requires no parameter setup. The AC drive automatically senses the presence of braking resistors.
Braking Resistor Specifications Part Number GS-20P5-BR GS-21P0-BR GS-22P0-BR GS-23P0-BR GS-25P0-BR GS-27P5-BR GS-41P0-BR GS-42P0-BR GS-43P0-BR GS-45P0-BR GS-47P5-BR GS-4010-BR
Quantity Drive Model & Wiring GS2-10P2, GS2-10P5, GS2-20P5 1 GS2-11P0, GS2-21P0 1 GS2-22P0 1 GS2-23P0 1 GS2-25P0 1 GS2-27P5 1 GS2-41P0 1 GS2-42P0, GS2-51P0, GS2-52P0 1 2 in parallel GS2-53P0, GS2-55P0, GS2-57P5 GS2-43P0 1 GS2-45P0 1 GS2-47P5 1 GS2-4010 1 GS2-5010 2 in series
Braking Duty Ohms Watts Torque Cycle 270%
200⏲
80
10%
125%
200⏲
80
10%
125%
100⏲
300
10%
125%
70⏲
300
10%
125%
40⏲
400
10%
125%
30⏲
500
10%
125%
750⏲
80
10%
125%
400⏲
300
10%
125%
250⏲
300
10%
125%
150⏲
400
10%
125%
100⏲
500
10%
125%
75⏲
1000
10%
Braking Resistor Connections
Braking Resistor B1 B2
A–8
GS2 Series AC Drive User Manual
Page 155
Appendix A: Accessories
Braking Resistor Dimensions Braking Resistor Dimensions (mm) Part Number
Figure
L1
L2
H
D
W
Maximum weight (g)
GS-20P5-BR GS-21P0-BR GS-22P0-BR GS-23P0-BR GS-25P0-BR GS-27P5-BR GS-41P0-BR GS-42P0-BR GS-43P0-BR GS-45P0-BR GS-47P5-BR GS-4010-BR
1
140
125
20
5.3
60
160
1
140
125
20
5.3
60
160
1
215
200
30
5.3
60
750
1
215
200
30
5.3
60
750
1
265
250
30
5.3
60
930
2
335
320
30
5.3
60
1100
1
140
125
20
5.3
60
160
1
215
200
30
5.3
60
750
1
215
200
30
5.3
60
750
1
265
250
30
5.3
60
930
2
335
320
30
5.3
60
1100
2
400
385
50
5.3
100
2800
Figure 1
W+ - 0.5
D+ - 0.5
L2 + -- 2
RING TERMINAL
H+ - 0.5
150±2
L1+ -2
L2+ -2
D+ - 0.5
W+ - 0.5
Figure 2
H+ - 0.5
TERMINAL: 2t x 125 x Ø63
L1+ -2
1st Ed. Rev. C
12/2006
GS2 Series AC Drive User Manual
A–9
Page 156
Appendix A: Accessories
EMI Input Filters The EC Declaration of Conformity for the GS2 Series AC Drives was completed in conjunction with EMI Filters listed below. CE compliance requires the use of EMI filters; not available for 575V drives.
EMI Input Filter Specifications EMI Filter
20DRT1W3S
32DRT1W3C not available
AC Drive Model / Input Phase
Filter Input Rating
Filter Dimensions
GS2-10P2 / 1ph GS2-10P5 / 1ph GS2-11P0 / 1ph GS2-20P5 / 1ph GS2-21P0 / 1ph GS2-22P0 / 1ph
250V, 1-phase, 20A
Figure 1
GS2-23P0 / 1ph
250V, 1-phase, 32A
Figure 2
GS2-20P5 / 3ph n/a
10TDT1W4C *
GS2-21P0 / 3ph GS2-22P0 / 3ph
250V, 3-phase, 10A
Figure 3
26TDT1W4C *
GS2-23P0 / 3ph
250V, 3-phase, 26A
Figure 4
40TDS4W4B
GS2-25P0 / 3ph GS2-27P5 / 3ph
250V, 3-phase, 40A
Figure 5
11TDT1W4S
GS2-41P0 / 3ph GS2-42P0 / 3ph GS2-43P0 / 3ph
480V, 3-phase, 11A
Figure 6
17TDT1W44
GS2-45P0 / 3ph GS2-47P5 / 3ph
480V, 3-phase, 17A
Figure 7
GS2-4010 / 3ph
480V, 3-phase, 26A
Figure 8
26TDT1W4B4 not available
GS2-5xxx n/a
* EMI filters 10TDT1W4C and 26TDT1W4C do not mount underneath GS2 drives.
A–10
GS2 Series AC Drive User Manual
Page 157
Appendix A: Accessories
EMI Filter Dimensions These filters, except 10TDT1W4C and 26TDT1W4C, mount between the drive and the subpanel. The filters have threaded holes on their front surface for this purpose, and the drives mount directly to the front of the filters.
POWER-IN
Figure 1 [units = mm]
20DRT1W3S
Figure 2 [units = mm]
A _ 2.0 306.0 +
M5X0.8(4x) 10.0
C
_1.0 122.0 + D
POWER-IN
_ 2.0 153.0 + E
R3.0
101 AWG 12 BLUE 101 AWG 12 BLACK 101 AWG 12 G/Y F
_10.0 250.0 +
R4.5 _ 2.0 50.0 +
B
_1.0 284.0 +
32DRT1W3C
H _ 1.0 25.0 + o8.0(4x)
G _1.0 284.0 +
1st Ed. Rev. C
12/2006
GS2 Series AC Drive User Manual
A–11
Page 158
Appendix A: Accessories
EMI Filter Dimensions (continued) Figure 3 [units = mm (in)]
100.0±1.0 (3.93±0.0393)
125.0±2.0(4.92±0.0787)
237.0 ± 2.0 (9.33 ± 0.0787) 10.0 (.39)
R2.5
1015 AWG18
R4.0 BLUE BLACK BROWN G/Y
200 ± 10 (7.9 ± .39)
215.0 ± 1.0 (8.46 ± 0.0393)
40.0±2.0 (1.57±0.0787)
Units: mm(inches)
Dia. 8.0 4x (.315)
10TDT1W4C
20.0±1.0(0.787±0.0393) 215.0 ± 1.0 (8.46 ± .0393)
Figure 4 [units = mm (in)]
122.0±1.0 (4.8±0.0393)
153.0±2.0 (6.02±0.0787)
306.0 ±2.0 (12.05± 0.0787)
R3.0 1015 AWG 14 Blue Black Brown G/Y
250.0±10.0 (9.84±0.393) R4.5
50.0±2.0(1.97±0.787)
284.0±1.0 (11.8 ±0.0393)
Dia. 8.0(4X) (.315)
26TDT1W4C
25.0±1.0(.984±.0393)
284.0±1.0(11.8 ±.0393)
A–12
GS2 Series AC Drive User Manual
Page 159
Appendix A: Accessories
EMI Filter Dimensions (continued) Figure 5 [units = mm] 30.0 o7,0(2x)
40.0
40.0
40.0 o7.0X10(2x)
_ 1.0 80.0 +
_ 2.0 90.0 +
M4X0.7
_ +
POWER-IN A 250.0 + _ 2.0 B 270.0 + _ 1.0 C 293.0 MAX.
40TDS4W4B M6X1.0(4x) _ 10 300.0 +
20.0 20.0 20.0
_ 2.0 150.0 +
177.0 MAX
1015 AWG10 Y/G 1015 AWG10 BLUE T/L3 1015 AWG10 BLUE S/L2 1015 AWG10 BLUE R/L1
Figure 6 [units = mm] A
_ 2.0 220.0 +
F _ 10.0 200.0 +
C45.0 + _ 2.0
POWER-IN
C _ 1.0 100.0 +
B _ 2.0 130.0 +
1015 AWG18 BLUE 1015 AWG18 BLACK 1015 AWG18 BROWN
R/L1 S/L2 T/L3
1015 AWG18 Y/G
E
_1.0 198.0 +
M4X0.7(3x)
11TDT1W4S
1st Ed. Rev. C
12/2006
GS2 Series AC Drive User Manual
A–13
Page 160
Appendix A: Accessories
EMI Filter Dimensions (continued) Figure 7 [units = mm] A _ 2.0 306.0 +
M5X0.8(4x) 10.0
_1.0 122.0 + D
1015 AWG16 BLUE R/L1 1015 AWG16 BLACK S/L2 1015 AWG16 BROWN T/L3 1015 AWG16 Y/G
POWER-IN
_ 2.0 153.0 + E
R3.0
_ 10.0 300.0 +
R4.5 _ 2.0 50.0 +
B
_1.0 284.0 +
H _ 1.0 25.0 +
C
17TDT1W44 G _1.0 284.0 +
Figure 8 [units = mm]
26TDT1W4B4
A–14
GS2 Series AC Drive User Manual o8.0(4x)