Page 71
Chapter 4: AC Drive Parameters
Setting 99: Multi-Function Input Disable Setting a Multi-Function Input to 99 will disable that input. The purpose of this function is to provide isolation for unused Multi-Function Input Terminals. Any unused terminals should be programmed to 99 to make sure they have no effect on drive operation. Note: Any unused terminals should be programmed to 99 to make sure they have no effect on drive operation.
1st Ed. Rev. C
12/2006
GS2 Series AC Drive User Manual
4–29
Page 72
Chapter 4: AC Drive Parameters
P3.11
Multi-function Output Terminal 1 Default Setting: 00
P3.12
Multi-function Output Terminal 2 Default Setting: 01 Settings for P3.11 to P3.12: Settings:
00 01 02 03 04 05 06 07 08 09 10
AC Drive Running AC Drive Fault At Speed Zero Speed Above Desired Frequency (P3.16) Below Desired Frequency (P3.16) At Maximum Speed (P0.02) Over Torque Detected Above Desired Current (P3.17) Below Desired Current (P3.17) PID Deviation Alarm (P3.18 and P3.19)
Setting Function Explanations: 00: AC Drive Running - The terminal will be activated when there is an output from the drive. 01: AC Drive Fault - The terminal will be activated when one of the faults listed under parameters P6.31 through P6.36 occurs. 02: At Speed - The terminal will be activated when the AC drive attains the Command Frequency (P4.00 or P5.01~P5.07). 03: Zero Speed - The output will be activated when Command Frequency (P4.00 or P5.01~P5.07) is lower than the Minimum Output Frequency (P2.06). 04: Above Desired Frequency - The output will be activated when the AC drive is above the Desired Frequency (P3.16). 05: Below Desired Frequency - The output will be activated when the AC drive is below the Desired Frequency (P3.16). 06: At Maximum Speed - The output will be activated when the AC drive reaches Motor Maximum RPM (P0.04). 07: Over Torque Detected - The output will be activated when the AC drive reaches the Over-torque Detection Level (P6.08), and exceeds this level for a time greater than the Over-torque Detection Time (P6.09). 08: Above Desired Current - The output will be activated when the AC drive is above the Desired Current (P3.17). 09: Below Desired Current - The output will be activated when the AC drive is below the Desired Current (P3.17). 10: PID Deviation Alarm - The output will be activated when the AC drive exceeds the PID Deviation Level (P3.18) for longer than the PID Deviation Time (P3.19).
4–30
GS2 Series AC Drive User Manual
Page 73
Chapter 4: AC Drive Parameters
P3.16
Desired Frequency Range: 0.0 to 400.0 Hz
Default Setting: 0.0
•If a Multi-function output terminal is set to function as Desired Frequency Attained (P3.11 or P3.12 = 04 or 05), then the output will be activated when the programmed frequency is attained.
Frequency Maximum Output Frequency Desired Frequency P3.16
Time Desired Frequency Attained Indication P3.11 & P3.12
P3.17
ON
Desired Current Range: 0.0 to <Drive Rated Amps>
P3.18
Default Setting: 10.0
PID Deviation Time Range: 0.1 to 300.0 sec
1st Ed. Rev. C
Default Setting: 0.0
PID Deviation Level Range: 1.0 to 50.0%
P3.19
OFF
12/2006
Default Setting: 5.0
GS2 Series AC Drive User Manual
4–31
Page 74
Chapter 4: AC Drive Parameters
Analog Parameters P4.00
Source of Frequency Command Default: 00 Settings:
00
Frequency determined by keypad potentiometer
01
Frequency determined by digital keypad up/down
02
Frequency determined by 0 to +10V input (including remote potentiometer) on AI terminal. Switch SW1 must be set to AVI. AVI
Switch SW1 must be set to AVI in order to use a 0 to +10V input
ACI
03
Frequency determined by 4 to 20mA input on AI terminal. Switch SW1 must be set to ACI. AVI
Switch SW1 must be set to ACI in order to use a 4 to 20mA input
ACI
04
Frequency determined by 0 to 20mA input on AI terminal. Switch SW1 must be set to ACI. AVI
Switch SW1 must be set to ACI in order to use a 0 to 20mA input
ACI
05
Frequency determined by RS-232/RS-485 communication interface. Switches SW2 and SW3 must be set to RS-232 or RS-485. RS485
SW3
SW2
RS232
P4.01
RS-232 / RS-485 communication is determined by switches SW2 & SW3
Analog Input Offset Polarity Range: 00 Offset disabled 01 Positive Offset 02 Negative Offset
Default Setting: 00
• This parameter sets the potentiometer Bias Frequency to be positive or negative. • The Analog Input Offset calculation will also define the Offset Polarity. See the note after P4.02.
4–32
GS2 Series AC Drive User Manual
Page 75
Chapter 4: AC Drive Parameters
Analog Input Offset
P4.02
Range: 0.0 to 100% This parameter can be set during the operation
Default Setting: 0.0
• This parameter provides a frequency offset for an analog input. • Use the equation below to determine the Analog Input Offset. For this equation, you will need to know the necessary Minimum Frequency References and and Maximum Output Frequency needed for your application.
Analog Offset % =
Min. Frequency Reference x 100 ( Max. Frequency Reference )
Note: The result of the Analog Input Offset calculation will also define the Analog Input Offset Polarity (P4.01). A positive answer means you should have a positive offset. A negative answer means you should have a negative offset.
Analog Input Gain
P4.03
Range: 0.0 to 300.0% This parameter can be set during the operation
Default Setting: 100.0
• This parameter sets the ratio of analog input vs frequency output. • Use the equation below to calculate the Analog Input Gain. For this equation, you will need to know the minimum and maximum set-point frequencies needed for your application.
Analog Gain % =
P4.04
Reference – Min. Frequency Reference ( Max. FrequencyMaximum ) x 100 Output Frequency
Analog Input Reverse Motion Enable Range: 00 Forward Motion Only 01 Reverse Motion Enable
Default Setting: 00
•P4.01 to P4.04 are used when the source of frequency command is the analog signal (0 to +10 VDC, 0 to 20 mADC, or 4 to 20 mADC). Refer to the following examples:
1st Ed. Rev. C
12/2006
GS2 Series AC Drive User Manual
4–33
Page 76
Chapter 4: AC Drive Parameters
Analog Input Examples Use the equations below when calculating the values for the Maximum Output Frequency, Analog Input Offset, Analog Input Gain, and the Mid-point Frequency.
A) Max. Output Frequency =
Motor Max. RPM (P0-04) x Base Frequency (P0-02) ( Motor Base RPM (P0-03) )
Note: The Maximum Output Frequency is not a parameter setting, but is needed in order to calculate the Analog Gain. The default Maximum Output Frequency for the GS2 drive is 60Hz. If parameters P0.02, P0.03, or P0.04 are changed, then the Maximum Output Frequency will change.
B) Analog Offset % =
Min. Frequency Reference x 100 ( Max. Frequency Reference )
C) Analog Gain % =
Reference – Min. Frequency Reference ( Max. FrequencyMaximum ) x 100 Output Frequency
D) Mid-point Freq. =
( Max. Freq. Reference 2– Min. Freq. Reference ) + Min. Freq. Reference
Note: The Mid-point Frequency calculation shows the frequency reference of the drive when the potentiometer or other analog device is at its mid-point.
4–34
GS2 Series AC Drive User Manual
Page 77
Chapter 4: AC Drive Parameters
Example 1: Standard Operation This example illustrates the default operation of the drive. The example is given to further illustrate the use of the analog calculations. The full range of the analog input signal corresponds to the full forward frequency range of the AC drive. • Minimum Frequency Reference = 0Hz • Maximum Frequency Reference = 60Hz
Calculations A) Max. Output Frequency = B) Analog Offset % = C) Analog Gain % =
RPM x 60Hz = 60Hz ( 1750 1750 RPM )
0Hz ( 60Hz ) x 100 = 0%
– 0Hz ) x 100 = 100% ( 60Hz60Hz
D) Mid-point Frequency =
( 60Hz2– 0Hz ) + 0Hz = 30Hz
Parameter Settings P4.01: 01 – Positive Input Offset Polarity P4.02: 00 – 0% Analog Input Offset P4.03: 100 – 100% Analog Input Gain P4.04: 00 – Forward Motion Only
Results Maximum 60Hz Output Frequency
30
0 0Hz 0V 0mA 4mA
1st Ed. Rev. C
12/2006
5V 10mA 12mA
10V 20mA 20mA
Hz
60
10V 0V 20mA 0mA 20mA 4mA Potentiometer Scale
GS2 Series AC Drive User Manual
4–35
Page 78
Chapter 4: AC Drive Parameters
Example 2: Positive Offset In this example, the Analog Input will have a positive offset while still using the full scale of the potentiometer. When the potentiometer is at its lowest value (0V, 0mA, or 4mA), the set-point frequency will be at 10Hz. When the potentiometer is at its maximum value (10V or 20mA), the set-point frequency will be at 60Hz. • Minimum Frequency Reference = 10Hz • Maximum Frequency Reference = 60Hz
Calculations A) Max. Output Frequency = B) Analog Offset % = C) Analog Gain % =
RPM x 60Hz = 60Hz ( 1750 1750 RPM )
x 100 = 16.7% ( 10Hz 60Hz )
– 10Hz ( 60Hz60Hz ) x 100 = 83.3%
D) Mid-point Frequency =
( 60Hz 2– 10Hz ) + 10Hz = 35Hz
Parameter Settings P4.01: 01 – Positive Input Offset Polarity P4.02: 16.7 – 16.7% Analog Input Offset P4.03: 83.3 – 83.3% Analog Input Gain P4.04: 00 – Forward Motion Only
Results Maximum Output Frequency 60Hz
35
10Hz
10
Positive Offset 0Hz
4–36
0V 0mA 4mA
5V 10mA 12mA
GS2 Series AC Drive User Manual
10V 20mA 20mA
Hz
60
10V 0V 20mA 0mA 4mA 20mA Potentiometer Scale
Page 79
Chapter 4: AC Drive Parameters
Example 3: Forward and Reverse Operation In this example, the potentiometer is programmed to run a motor full-speed in both forward and reverse direction. The frequency reference will be 0Hz when the potentiometer is positioned at mid-point of its scale. Parameter P4.04 must be set to enable reverse motion. Note: When calculating the values for the Analog Input using reverse motion, the reverse frequency reference should be shown using a negative (-) number. Pay special attention to signs (+/-) for values representing reverse motion. • Minimum Frequency Reference = -60Hz (reverse) • Maximum Frequency Reference = 60Hz
Calculations A) Max. Output Frequency = B) Analog Offset % =
RPM x 60Hz = 60Hz ( 1750 1750 RPM )
x 100 = -100% ( -60Hz 60Hz )
Note: The negative (-) value for the Analog Offset % shows that a negative offset is needed for P4.01. C) Analog Gain % =
– (-60Hz) (60Hz60Hz ) x 100 = 200%
D) Mid-point Frequency =
( 60Hz –2(-60Hz) ) + (-60Hz) = 0Hz
Parameter Settings P4.01: 02 – Negative Input Offset Polarity P4.02: 100 – 100% Analog Input Offset P4.03: 200 – 200% Analog Input Gain P4.04: 01 – Reverse Motion Enable
Results Maximum Output Frequency 60Hz
0
Forward 0Hz Reverse -60
-60Hz 0V 0mA 4mA
1st Ed. Rev. C
12/2006
5V 10mA 12mA
10V 20mA 20mA
Hz
60
10V 0V 20mA 0mA 20mA 4mA Potentiometer Scale
GS2 Series AC Drive User Manual
4–37
Page 80
Chapter 4: AC Drive Parameters
Example 4: Forward Run/Reverse Jog This example shows an application in which the drive runs full-speed forward and jogs in reverse. The full scale of the potentiometer will be used. Note: When calculating the values for the Analog Input using reverse motion, the reverse frequency reference should be shown using a negative (-) number. Pay special attention to signs (+/-) for values representing reverse motion. • Minimum Frequency Reference = -15Hz (reverse) • Maximum Frequency Reference = 60Hz
Calculations A) Max. Output Frequency = B) Analog Offset % =
RPM x 60Hz = 60Hz ( 1750 1750 RPM )
x 100 = -25% (-15Hz 60Hz )
Note: The negative (-) value for the Analog Offset % shows that a negative offset is needed for P4.01. C) Analog Gain % =
– (-15Hz) (60Hz60Hz ) x 100 = 125%
D) Mid-point Frequency =
( 60Hz –2(-15Hz) ) + (-15Hz) = 22.5Hz
Parameter Settings P4.01: 02 – Negative Input Offset Polarity P4.02: 25 – 25% Analog Input Offset P4.03: 125 – 125% Analog Input Gain P4.04: 01 – Reverse Motion Enable
Results Maximum Output Frequency 60Hz
22.5
0
22.5Hz Forward
-15
0Hz -15Hz 0V 0mA 4mA
4–38
Reverse 5V 10mA 12mA
10V 20mA 20mA
GS2 Series AC Drive User Manual
Hz
60
10V 0V 20mA 0mA 20mA 4mA Potentiometer Scale