Chapter 4: AC Drive Parameters
Volts/Hertz Parameters Volts/Hertz Settings
P2.00
Settings: 00 - General Purpose (constant torque) 01 - High Starting Torque 02 - Fans and Pumps (variable torque) 03 - Custom
Default Setting: 0.0
Note: P2.04 through P2.07 are only used when the Volts/Hertz parameter (P2.00) is set to 03. 00: General Purpose Volts
03: Custom
Voltage
Volts
P0.00
P0.00
P0.00 P2.05
10/20
P2.07
10/20 60/400 Hz
1.5
1.5
60/400Hz Base Frequency
50.0 Hz
50Hz Base Frequency
Frequency P2.06 P2.04 P0.02 P0.04 x P0.02 P0.03
01: High Starting Torque Volts
Volts P0.00
P0.00
23/46
23/46 14/28
18/36 1.5 3
60/400 Hz
1.3 2.2
60/400Hz Base Frequency
50.0 Hz
50Hz Base Frequency
02: Fans and Pumps Volts P0.00
Volts P0.00
50/100 10/20 1.5 30
50/100 10/20 60/400 Hz 1.3 25
60/400Hz Base Frequency
1st Ed. Rev. C
12/2006
50.0 Hz
50Hz Base Frequency
GS2 Series AC Drive User Manual
4–19
Page 62
Chapter 4: AC Drive Parameters
P2.01
Slip Compensation Range: 0.0 to 10.0
Default Setting: 0.0
When controlling an asynchronous induction motor, load on the AC drive will increase causing an increase in slip. This parameter may be used to compensate the nominal slip within a range of 0 to 10. When the output current of the AC drive is greater than the Motor Nameplate Amps (P0.01), the AC drive will adjust its output frequency according to this parameter.
P2.02
Auto-torque Boost Range: 00 to 10
Default Setting: 00
This parameter functions similarly to the P2.00-01 High Starting Torque V/Hz setting, except that this parameter uses less current than does P2.00-01. P2.00-01 boosts starting torque by increasing current at every start beyond what is required to move the load. P2.02 Auto-torque Boost increases the current only as required to move the load. The proper setting for P2.02 is determined by trial and error.
P2.04 through P2.07 are used only when the Volts/Hertz parameter (P2.00) is set to 03.
P2.04
Mid-point Frequency Range: 0.1 to 400 Hz
Default Setting: 1.5
This parameter sets the Mid-Point Frequency of V/F curve. With this setting, the V/F ratio between Minimum Frequency and Mid-Point frequency can be determined. This parameter must be greater than or equal to the Minimum Output Frequency (P2.06) and less than or equal to the Maximum Voltage Frequency (P0.02). This parameter is used only when the Volts/Hertz parameter (P2.00) is set to 03.
P2.05
Mid-point Voltage Range: 115V/230V: 2.0 to 255V 460V: 2.0 to 510V 575V: 2.0 to 637V
Default Setting: 10.0 20.0 24.0
This parameter sets the Mid-Point Voltage of any V/F curve. With this setting, the V/F ratio between Minimum Frequency and Mid-Point Frequency can be determined. This parameter must be greater than or equal to the Minimum Output Voltage (P2.07) and less than or equal to the Maximum Output Voltage (P0.00). This parameter is used only when the Volts/Hertz parameter (P2.00) is set to 03.
4–20
GS2 Series AC Drive User Manual
Page 63
Chapter 4: AC Drive Parameters
P2.06
Minimum Output Frequency Range: 0.1 to 20.0 Hz
Default Setting: 1.5
This parameter sets the Minimum Output Frequency of the AC drive. This parameter must be less than or equal to the Mid-Point Frequency (P2.04). This parameter is used only when the Volts/Hertz parameter (P2.00) is set to 03.
P2.07
Minimum Output Voltage Range: 115V/230V: 2.0 to 50.0V 460V: 2.0 to 100.0V 575V: 2.0 to 130.6V
Default Setting: 10.0 20.0 24.0
This parameter sets the Minimum Output Voltage of the AC drive. This parameter must be equal to or less than Mid-Point Voltage (P2.05). This parameter is used only when the Volts/Hertz parameter (P2.00) is set to 03.
P2.08
PWM Carrier Frequency Range: 115V/230V/460V: 01 to 15 kHz 575V: 01 to 10 kHz
Default Setting: 12 6
This parameter sets the carrier frequency of PWM (Pulse-Width Modulated) output. • In the table below, we see that the carrier frequency of PWM output has a significant influence on the electromagnetic noise, leakage current, heat dissipation of the AC drive and the acoustic noise to the motor:
Carrier Frequency Acoustic Noise
1st Ed. Rev. C
Electromagnetic Noise, Heat Dissipation Leakage Current
1kHz significant minimal minimal
15 kHz minimal moderate moderate
12/2006
GS2 Series AC Drive User Manual
4–21
Page 64
Chapter 4: AC Drive Parameters
Digital Parameters P3.00
Source of Operation Command Default Setting: 00 Settings
00
Operation Determined by Digital Keypad
01
Operation determined by external control terminals. Keypad STOP is enabled.
02
Operation determined by external control terminals. Keypad STOP is disabled.
03
Operation determined by communication interface. Keypad STOP is enabled.
04
Operation determined by communication interface. Keypad STOP is disabled.
• This parameter sets the input source for the AC drive operation commands. • Refer to P3.01 to P3.05 for more details.
P3.01
Multi-function Input Terminals (DI-DI2) Default Setting: 00 Settings
00
DI1 - FWD/STOP DI2 - REV/STOP
01
DI1 - RUN/STOP DI2 - REV/FWD
02
DI1 - RUN (N.O. latching input) DI2 - REV/FWD DI3 - STOP (N.C. latching input)
Note: Multi-function Input Terminals DI1 and DI2 do not have separate parameter designations. DI1 and DI2 must be used in conjunction with each other to operate two and three wire control. P3.01: Setting 00
FWD/STOP
DI1
DI2
Result
OFF
OFF
STOP
ON
OFF
FWD
DI2
OFF
ON
REV
DCM
ON
ON
STOP
REV/STOP
4–22
DI1
GS2 Series AC Drive User Manual
Page 65
Chapter 4: AC Drive Parameters
P3.01: Setting 01
P3.01: Setting 02
STOP RUN/STOP DI1 FWD/REV DI2 DCM
P3.02
DI1- RUN/STOP select "Open" : Stop "Close" : Run DI2- FWD/REV select "Open" : FWD "Close" : REV
DI1- RUN command Latching input (N.O.) Runs when closed
RUN DI1 DI3
FWD/REV DI2 DCM
DI2- FWD/REV select "Open" : FWD "Close" : REV DI3- STOP command Latching input (N.C.) Stops when open
Multi-Function Input (DI3) Default Setting: 00
P3.03
Multi-Function Input (DI4) Default Setting: 03
P3.04
Multi-function Input (DI5) Default Setting: 04
P3.05
Multi-function Input (DI6) Settings for P3.02 to P3.05: 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 99
Default Setting: 05
*External Fault (N.O.) *External Fault (N.C.) External Reset Multi-Speed/PID SP Bit 1 Multi-Speed/PID SP Bit 2 Multi-Speed/PID SP Bit 3 Reserved Reserved Reserved Jog External Base Block (N.O.) External Base Block (N.C.) Second Accel/Decel Time Speed Hold Increase Speed (P4.00 must be set to 01) Decrease Speed (P4.00 must be set to 01) Reset Speed to Zero (P4.00 must be set to 01) PID Disable (N.O.) PID Disable (N.C.) Input Disable
* Use either 00 or 01, but not both. Use interposing relays if more contacts are needed.
1st Ed. Rev. C
12/2006
GS2 Series AC Drive User Manual
4–23
Page 66
Chapter 4: AC Drive Parameters
Setting Explanations for parameters P3.02 - P3.05 Setting 00: External Fault (N.O.) When an External Fault input signal is received, the AC drive output will turn off, the drive will display “EF” on the LED Display, and the motor will Coast to Stop. To resume normal operation, the external fault must be cleared, and the drive must be reset.
External Fault (N.O)
DI3-DI6
DI3-DI6: External Fault (N.O.) "Close": Drive receives external fault input signal
DCM
Setting 01: External Fault (N.C.)
External Fault (N.C)
DI3-DI6
DI3-DI6: External Fault (N.C.) "Open": Drive receives external fault input signal
DCM
Setting 02: External Reset An External Reset has the same function as the Reset key on the digital keypad. Use an External Reset to reset the drive after a fault.
External Reset
DI3-DI6 DCM
4–24
GS2 Series AC Drive User Manual
DI3-DI6: External Reset "Close": Drive receives external reset input signal
Page 67
Chapter 4: AC Drive Parameters
Settings 03, 04, and 05: Multi-Speed/PID SP Bits 1, 2, and 3 If PID operation is inhibited (P7.00 = 00), the three Multi-Speed/PID SP Bits are used to select the multi-speed settings defined by P5.01 to P5.07. If PID operation is enabled (P7.00 ≠ 00), the three Multi-Speed/PID SP Bits are used to select the PID multi-setpoint settings defined by P7.11 to P7.17.
Multi-Spd/PID SP
Speed PID SP Bit 3 Bit 2 Bit 1 Selection Selection
03: Mult-Spd/PID SP Bit 1 DI3-DI6 04: Mult-Spd/PID SP Bit 2 DI3-DI6 05: Mult-Spd/PID SP Bit 3 DI3-DI6 DCM
OFF
OFF
OFF
OFF
OFF
ON P5.01: Spd 1 P7.11: SP 1
OFF
ON ON
OFF
ON P5.03: Spd 3 P7.13: SP 3
OFF
OFF
OFF
ON P5.05: Spd 5 P7.15: SP 5
ON ON
OFF
OFF
ON ON ON ON
P4.00
P7.02
P5.02: Spd 2 P7.12: SP 2 P5.04: Spd 4 P7.14: SP 4 P5.06: Spd 6 P7.16: SP 6
ON P5.07: Spd 7 P7.17: SP 7
Note: In order to use the Multi-Speed settings, parameters 5.01 to 5.07 must be set. In order to use the Multi-PID SP settings, parameters 7.11 to 7.17 must be set. Note: When all multi-speed inputs are off, the AC drive reverts back to the Source of Frequency Command (P4.00), or the PID Setpoint Source (P7.02).
Setting 09: Jog Command This setting configures a Multi-function Input Terminal to give the Jog Command when activated. P5.00 sets the Jog Speed.
Jog Command
DI3-DI6
DI3-DI6: Jog Command "Close": Drive receives Jog Command signal
DCM Note: The motor must be stopped to initiate this command. The Jog Command cannot be used simultaneously with an active FWD/STOP, REV/STOP, or RUN/STOP command. The Jog Command can be used with an active REV/FWD command.
1st Ed. Rev. C
12/2006
GS2 Series AC Drive User Manual
4–25
Page 68
Chapter 4: AC Drive Parameters
Settings 10 and 11: External Base Block (N.O.) and External Base Block (N.C.) Value 10 is for a normally open (N.O) input and value 11 is for a normally closed (N.C.) input. DI3-DI6: Base Block Input
Base Block (N.O.) DI3-DI6
Base Block (N.C)
DCM
DI3-DI6 DCM
When an External Base Block is activated, the LED display shows bb, the AC drive stops all output, and the motor will free run. When the External Base Block is deactivated, the AC drive will start the speed search function and synchronize with the motor speed. The AC drive will then accelerate to the Master Frequency.
P 6.13
4–26
GS2 Series AC Drive User Manual
Page 69
Chapter 4: AC Drive Parameters
Setting 12: Second Accel/Decel Time Multi-function Input Terminals DI3-DI6 can be set to select between Accel/Decel times 1 and 2. Parameters P1.01 and P1.02 set Accel 1 and Decel 1 times. Parameters P1.05 and P1.06 set Accel 2 and Decel 2 times.
Accel/Decel 2
DI3-DI6
DI3-DI6: Accel/Decel Time 2 Command "Close": Drive receives Accel/Decel 2 Command signal
DCM Frequency Maximum Output Frequency P 0.04
Accel 1 P 1.01
Accel 2 P 1.05
Decel 2 P 1.06
Decel 1 P 1.02
Time Multi-function Input Terminal
On Off
Setting 13: Speed Hold When the Speed Hold command is received, the drive acceleration or deceleration is stopped and the drive maintains a constant speed. Frequency
Master Frequency Accel inhibit
Decel inhibit Actual Operation Freq.
Accel inhibit
Decel inhibit
Actual Operation Frequency Time Speed Hold Run Command
1st Ed. Rev. C
12/2006
ON
ON
ON ON
ON OFF
GS2 Series AC Drive User Manual
4–27
Page 70
Chapter 4: AC Drive Parameters
Settings 14 and 15: Increase and Decrease Speed (Electronic Motor Operated Potentiometer)
Settings 14 and 15 allow the Multi-function terminals to be used to increase or decrease speed. As long as the DI terminal is activated, the speed reference will continuously increase or decrease according to the acceleration and deceleration ramp settings.
Setting 14: Increase
DI3-DI6 DI3-DI6: Increase or Decrease Frequency "Close": Drive receives Increase or Decrease Frequency Input
Setting 15: Decrease DI3-DI6 DCM
Note: In order to use these settings, P4.00 must be set to 01.
Setting 16: Reset Speed to Zero
Reset Speed to Zero
DI3-DI6
DI3-DI6: Reset Speed to Zero "Close": Drive receives Reset Speed to Zero signal
DCM
Settings 17 and 18: PID Disable (N.O) and (N.C.) Settings 17 and 18 set the Multi-function terminals to disable PID operation.
Setting 17: PID Disable (N.O.) DI3-DI6 DI3-DI6: PID Disable (N.O.) or (N.C.) Setting 18: PID Disable (N.C.)
DI3-DI6 DCM
4–28