Page 51

Chapter 4: AC Drive Parameters

Communications Parameters GS2 Description Parameter Communication Address P9.00 P9.01

P9.02

01

Transmission Speed

00: 4800 baud 01: 9600 baud 02: 19200 baud 03: 38400 baud

01

Communication Protocol

00: Modbus ASCII mode 7 data bits,no parity,2 stop bits 01: Modbus ASCII mode 7 data bits,even parity,1 stop bit 02: Modbus ASCII mode 7 data bits,odd parity,1 stop bit 03: Modbus RTU mode 8 data bits,no parity,2 stop bits 04: Modbus RTU mode 8 data bits,even parity,1 stop bit 05: Modbus RTU mode 8 data bits,odd parity,1 stop bit

00

Transmission Fault Treatment

P9.04

Time Out Detection

P9.05

Time Out Duration

P9.08 P9.11 P9.12 P9.13 P9.14 P9.15 P9.16 P9.17 P9.18 P9.19 P9.20 P9.21 P9.22

Default

01 to 254

P9.03

P9.07

Range

Parameter Lock Restore to Default

00: Display fault and continue operating 01: Display fault and RAMP to stop 02: Display fault and COAST to stop 03: No fault displayed and continue operating 00: Disable 01: Enable 0.1 to 60.0 seconds 00: All parameters can be set and read 01: All parameters are read-only 99: Restores all parameters to factory defaults

00

00 0.5 00 00

Block Transfer Parameter 1

P0.00 to P8.01, P9.99

P9.99

Block Transfer Parameter 2

P0.00 to P8.01, P9.99

P9.99

Block Transfer Parameter 3

P0.00 to P8.01, P9.99

P9.99

Block Transfer Parameter 4

P0.00 to P8.01, P9.99

P9.99

Block Transfer Parameter 5

P0.00 to P8.01, P9.99

P9.99

Block Transfer Parameter 6

P0.00 to P8.01, P9.99

P9.99

Block Transfer Parameter 7

P0.00 to P8.01, P9.99

P9.99

Block Transfer Parameter 8

P0.00 to P8.01, P9.99

P9.99

Block Transfer Parameter 9

P0.00 to P8.01, P9.99

P9.99

Block Transfer Parameter 10

P0.00 to P8.01, P9.99

P9.99

Block Transfer Parameter 11

P0.00 to P8.01, P9.99

P9.99

Block Transfer Parameter 12

P0.00 to P8.01, P9.99

P9.99

Parameter can be set during RUN Mode. 1st Ed. Rev. C

12/2006

GS2 Series AC Drive User Manual

4–9

Page 52

Chapter 4: AC Drive Parameters

Communications Parameters (continued) GS2 Description Parameter Block Transfer Parameter 13 P9.23 Block Transfer Parameter 14 P9.24 Block Transfer Parameter 15 P9.25 Serial Comm Speed Reference P9.26 P9.27

Serial Comm RUN Command

P9.28

Serial Comm Direction Command

P9.29

Serial Comm External Fault

P9.30

Serial Comm Fault Reset

P9.31

Serial Comm JOG Command

Range

Default

P0.00 to P8.01

P9.99

P0.00 to P8.01

P9.99

P0.00 to P8.01

P9.99

0.0 to 400.0 Hz

60.0

00: Stop 01: Run 00: Forward 01: Reverse 00: No fault 01: External fault 00: No action 01: Fault Reset 00: Stop 01: Jog

00 00 00 00 00

P9.39

Firmware Version

#.##

#.##

P9.41

GS Series Number

01: GS1 02: GS2 03: GS3

##

Manufacturer Model Information

00: GS2-20P5 (230V 1ph/3ph 0.5hp) 01: GS2-21P0 (230V 1ph/3ph 1hp) 02: GS2-22P0 (230V 1ph/3ph 2hp) 03: GS2-23P0 (230V 1ph/3ph 3hp) 04: GS2-25P0 (230V 3ph 5hp) 05: GS2-27P5 (230V 3ph 7.5hp) 06: Reserved 07: GS2-41P0 (460V 3ph 1hp) 08: GS2-42P0 (460V 3ph 2hp) 09: GS2-43P0 (460V 3ph 3hp) 10: GS2-45P0 (460V 3ph 5hp) 11: GS2-47P5 (460V 3ph 7.5hp) 12: GS2-4010 (460V 3ph 10hp) 13: GS2-10P2 (115V 1ph 0.25hp) 14: GS2-10P5 (115V 1ph 0.5hp) 15: GS2-11P0 (115V 1ph 1hp) 16~20: Reserved 21: GS2-51P0 (575V 3ph 1hp) 22: GS2-52P0 (575V 3ph 2hp) 23: GS2-53P0 (575V 3ph 3hp) 24: GS2-55P0 (575V 3ph 5hp) 25: GS2-57P5 (575V 3ph 7.5hp) 26: GS2-5010 (575V 3ph 10hp)

##

P9.42

Parameter can be set during RUN Mode.

4–10

GS2 Series AC Drive User Manual

Page 53

Chapter 4: AC Drive Parameters

Detailed Parameter Listings Parameter Name

Parameter Number

P0.00

Motor Nameplate Voltage Range: 115V/230V classes: 200/208/220/230/240 460V class: 380/400/415/440/460/480 575V class: 380 to 637

Default Setting: 240 Default Setting: 480 Default Setting: 575

•This parameter determines the Maximum Output Voltage of the AC drive. The Maximum Output Voltage setting must be less than or equal to the rated voltage of the motor as indicated on the motor nameplate. The setting value must be equal to or greater than the Mid-Point Voltage (P2.05).

Parameter Setting Range

Parameter Description

Parameter Default Setting

Note: If the symbol is found next to the parameter name, the parameter can be edited when the AC drive is in RUN Mode.

Motor Parameters P0.00

Motor Nameplate Voltage Range: 115V/230V classes: 200/208/220/230/240 460V class: 380/400/415/440/460/480 575V class: 380 to 637

Default Setting: 240 480 575

This parameter determines the Maximum Output Voltage of the AC drive. The Maximum Output Voltage setting must be less than or equal to the rated voltage of the motor as indicated on the motor nameplate. The setting value must be equal to or greater than the Mid-Point Voltage (P2.05).

P0.01

Motor Nameplate Amps Range: Drive Rated Amps x 0.3 to Drive Rated Amps x 1.0

Default Setting: Drive Rating (A)

This parameter sets the output current to the motor, and is used by the drive to set the motor overload protection. Set this parameter value to the full load current listed on the motor nameplate. (Also refer to P6.00 to set overload curve type.)

1st Ed. Rev. C

12/2006

GS2 Series AC Drive User Manual

4–11

Page 54

Chapter 4: AC Drive Parameters

P0.02

Motor Base Frequency Range: 50/60/400

Default Setting 60

•This value should be set according to base frequency of the motor as indicated on the motor nameplate. Motor Base Frequency determines the volts per hertz ratio.

P0.03

Motor Base RPM Range: 375 to 9999 RPM

Default Setting: 1750

• This value should be set according to rated Base RPM of the motor as indicated on the motor nameplate.

P0.04

Motor Maximum RPM Range: P0.03 to 9999 RPM

Default Setting: P0.03

• This value should be set according to the desired maximum speed of the motor. This value should not exceed the motor’s maximum rated speed. WARNING: The Motor Maximum RPM parameter (P0.04) should never exceed the maximum speed rating for the motor you are using. If this information is not readily available, consult your motor manufacturer. • This value cannot be set lower than Motor Base RPM (P0.03).

This parameter, along with P0.02 and P0.03, determines the Maximum Output Frequency of the AC Drive. The Maximum Output Frequency can be calculated as follows: Max. Output Frequency =

Motor Max. RPM (P0-04) x Base Frequency (P0-02) ( Motor Base RPM (P0-03) )

• If an output limit based on Maximum Output Frequency is desired, use the following equation to determine the corresponding value for Motor Maximum RPM: Motor Maximum RPM =

4–12

Max. Output Frequency

( Motor Base Frequency (P 0.02) ) x Motor Base RPM (P 0.03)

GS2 Series AC Drive User Manual

Page 55

Chapter 4: AC Drive Parameters

Ramp Parameters Stop Methods

P1.00

Range: 00 Ramp to Stop 01 Coast to stop

Default Setting: 00

This parameter determines how the motor is stopped when the AC drive receives a valid stop command. • Ramp: The AC drive decelerates the motor to Minimum Output Frequency (P2.06) and then stops according to the deceleration time set in P1.02 or P1.06. •Coast:The AC drive stops output instantly upon command, and the motor free runs until it comes to a complete stop. Note: The drive application or system requirements will determine which stop method is needed. Hz

Hz

Frequency

Frequency

Stops according to deceleration time

Free running to stop

Motor Speed

Motor Speed time

Operation Command

?

decel time ON

OFF

Ramp

P1.01 time

ON

OFF

Coast

Acceleration Time 1 Range: 0.1 to 600 sec Default Setting: 10 sec This parameter is used to determine the time required for the AC drive to ramp from 0 to its Maximum Motor RPM (P0.04). The rate is linear unless S-Curve is "Enabled."

1st Ed. Rev. C

12/2006

GS2 Series AC Drive User Manual

4–13

Page 56

Chapter 4: AC Drive Parameters

P1.02

Deceleration Time 1 Range: 0.1 to 600 sec

Default Setting: 30 sec

This parameter is used to determine the time required for the AC drive to decelerate from the Maximum Motor RPM (P0.04) down to 0Hz. The rate is linear unless S-Curve is “Enabled.”

P1.03

Accel S-Curve Range: 00 to 07

Default Setting: 00

This parameter is used whenever the motor and load need to be accelerated more smoothly. The Accel S-Curve may be set from 0 to 7 to select the desired acceleration S Curve.

Frequency

Time S-curve characteristics Time

S-curve characteristics Time P 1.04 = 00 "Decel S curve Disabled"

P 1.03 = 00 "Accel S curve Disabled"

Time Accel Time 1 or 2

4–14

GS2 Series AC Drive User Manual

Decel Time 1 or 2

Page 57

Chapter 4: AC Drive Parameters

P1.04

Decel S-Curve Range: 00 to 07

Default Setting: 00

This parameter is used whenever the motor and load need to be decelerated more smoothly. The Decel S-Curve may be set from 00 to 07 to select the desired deceleration S-Curve. Note: From the diagram shown below, the original setting accel/decel time will be for reference when the function of the S-curve is enabled. The actual accel/decel time will be determined based on the S-curve selected (1 to 7).

Frequency

P 1.04

P 1.03 (1)

(2) (4)

(3)

Time (1)

(2)

(4)

(3) S curve is disabled in (1), (2) P 1.03 sets S curve for (3) P 1.04 sets S curve for (4) P1.05

Acceleration Time 2 Range: 0.1 to 600 sec

Default Setting: 10.0

•The Second Acceleration Time determines the time for the AC drive to accelerate from 0 RPM to Maximum Motor RPM (P0.04). Acceleration Time 2 (P1.05) can be selected using a multi-function input terminal or frequency transition (P1.07).

P1.06

Deceleration Time 2 Range: 0.1 to 600 sec

Default Setting: 30 sec

•The Second Deceleration Time determines the time for the AC drive to decelerate from Maximum Motor RPM (P0.04) to 0 RPM. Deceleration Time 2 (P1.06) can be selected using a multi-function input terminal or frequency transition (P1.07).

1st Ed. Rev. C

12/2006

GS2 Series AC Drive User Manual

4–15

Page 58

Chapter 4: AC Drive Parameters

P1.07

Select method for 2nd Accel/Decel Range: 00: Second Accel/Decel from DI terminal 01: Frequency Transition P1.08 & P1.09

Default Setting: 00

• The second set of acceleration and deceleration times P1.05 and P1.06 can be selected either with a multi-function input terminal programmed to Second Accel/Decel, or by the values of the transition frequencies P1.08 and P1.09

Second Accel/Decel Times selected with Multi-Function Input Terminal Frequency Maximum Output Frequency P 0.04

Accel 1 P 1.01

Accel 2 P 1.05

Decel 2 P 1.06

Decel 1 P 1.02

Time Multi-function Input Terminal

P1.08

On Off

Accel 1 to Accel 2 Frequency Transition Range: 0.0 to 400.0 Hz Default Setting: 0.0 Second Accel/Decel Times selected with Frequency Transition Frequency Maximum Output Frequency P 0.04 Accel 1 to Accel 2 Frequency Transition P 1.08

Accel 2 P 1.05 Accel 1 P 1.01

P1.09

Decel 1 P 1.02

Decel 2 to Decel 1 Frequency Transition P 1.09

Time

Decel 1 to Decel 2 Frequency Transition Range: 0.0 to 400.0 Hz

4–16

Decel 2 P 1.06

GS2 Series AC Drive User Manual

Default Setting: 0.0

Page 59

Chapter 4: AC Drive Parameters

P1.10

Skip Frequency 1 Range: 0.0 to 400.0 Hz

P1.11

Skip Frequency 2 Range: 0.0 to 400.0 Hz

P1.12

Default Setting: 0.0

Default Setting: 0.0

Skip Frequency 3 Range: 0.0 to 400.0 Hz

Default Setting: 0.0

• P1.10, P1.11, and P1.12 determine the location of the frequency bands that will be skipped during AC drive operation.

P1.17

Skip Frequency Band Range: 0.0 to 20.0 Hz

Default Setting: 0.0

This parameter determines the frequency band for a given Skip Frequency (P1.10, P1.11, or P1.12). Half of the Skip Frequency Band is above the Skip Frequency and the other half is below. Programming this parameter to 0.0 disables all skip frequencies. Output frequency

Skip Frequency 3 P 1.12 Skip Frequency 2 P 1.11 Skip Frequency 1 P 1.10

Skip Frequency Set Point

1st Ed. Rev. C

12/2006

Skip Frequency Band P 1.17

GS2 Series AC Drive User Manual

4–17

Page 60

Chapter 4: AC Drive Parameters

P1.18

DC Injection Current Level Range: 00 to 100%

Default Setting: 00

This parameter determines the amount of DC Braking Current applied to the motor during start-up and stopping. When setting DC Braking Current, please note that 100% is equal to the rated current of the drive. It is recommended to start with a low DC Braking Current Level and then increase until proper holding torque has been attained.

P1.20

DC Injection during Start-up Range: 0.0 to 5.0 sec

Default Setting: 0.0

This parameter determines the duration of time that the DC Braking Current will be applied to the motor during the AC drive start-up. DC Braking will be applied for the time set in this parameter until the Minimum Frequency is reached during acceleration.

P1.21

DC Injection during Stopping Range: 0.0 to 25.0 sec

Default Setting: 0.0

This parameter determines the duration of time that the DC braking voltage will be applied to the motor during stopping. If stopping with DC Braking is desired, then P1.00 must be set to Ramp to Stop (00).

P1.22

Start-point for DC Injection Range: 0.0 to 60.0 Hz

Default Setting: 0.0

This parameter determines the frequency when DC Braking will begin during deceleration. Master Frequency Min. Output Frequency Operation Command time P 1.21

P 1.20 ON DC Injection Current Level P 1.18

4–18

Start-Point for DC Braking

P 1.22

GS2 Series AC Drive User Manual

OFF