For the AutomationDirect GS2

Page 41

Chapter 3: Keypad Operation and Quickstart

P 3.00

Source of Operation Command

Setting: 00 Default Setting: 00

Settings

00

Operation Determined by Digital Keypad

01

Operation determined by external control terminals. Keypad STOP is enabled.

02

Operation determined by external control terminals. Keypad STOP is disabled.

03

Operation determined by RS-232/RS-485 interface. Keypad STOP is enabled.

04

Operation determined by RS-232/RS-485 interface. Keypad STOP is disabled.

The AC drive operation will be determined by the Digital Keypad.

P 4.00

Source of Frequency Command

Setting: 00 Default: 00

Settings:

00

Frequency determined by keypad potentiometer

01

Frequency determined by digital keypad up/down

02

Frequency determined by 0 to +10V input on AI terminal. Switch, SW1 must be set to AVI. AVI ACI

03

Frequency determined by 4 to 20mA input on AI terminal. Switch SW1 must be set to ACI. AVI ACI

04

Switch SW1 must be set to ACI in order to use a 4 to 20mA input

Frequency determined by 0 to 20mA input on AI terminal. Switch SW1 must be set to ACI. AVI ACI

05

Switch SW1 must be set to AVI in order to use a 0 to +10V input

Switch SW1 must be set to ACI in order to use a 0 to 20mA input

Frequency determined by RS-232/RS-485 communication interface (RS-232 or RS-485 communication selected by switches SW2 and SW3. Refer to CHAPTER 5 for details.)

The frequency of the AC drive will be determined by keypad potentiometer.

1st Ed. Rev. C

12/2006

GS2 Series AC Drive User Manual

3–13

Page 42

Chapter 3: Keypad Operation and Quickstart

P 6.00

Electronic Thermal Overload Relay

Setting: 01

Default Setting: 00 Settings: 00 - Constant Torque (inverter/vector duty motor) 01 - Variable Torque (fan-cooled standard motor) 02 - Inactive This function setting 01 is used to derate the AC drive output current overload protection to protect a fan-cooled standard motor running at low speeds.

P 8.00

User Defined Display Function

Setting: 03 Default Setting: 00

Settings:

00 01 02 03 04 05 06 07 08 09

Output Frequency (Hz) Motor Speed (rpm) Output Frequency x P 8.01 Output Current (A) Motor Output Current (%) Output Voltage(V) DC Bus Voltage (V) PID Setpoint PID Feedback (PV) Frequency Setpoint

The AC drive display will default to indicate Output Current (A) when running. Note: For a complete list and description of the parameters for the GS2 Series AC drives, refer to CHAPTER 4.

3–14

GS2 Series AC Drive User Manual

Page 43

AC DRIVE PARAMETERS

CHAPTER

4

In This Chapter... GS2 Parameter Summary . . . . . . . . . . . . . . . . . . . .4–2 Detailed Parameter Listings . . . . . . . . . . . . . . . . .4–11 Motor Parameters . . . . . . . . . . . . . . . . . . . . . . . .4–11 Ramp Parameters . . . . . . . . . . . . . . . . . . . . . . . . .4–13 Volts/Hertz Parameters . . . . . . . . . . . . . . . . . . . . .4–19 Digital Parameters . . . . . . . . . . . . . . . . . . . . . . . .4–22 Setting Explanations for parameters P3.02 - P3.05 . . . . . . . . . .4–24

Analog Parameters . . . . . . . . . . . . . . . . . . . . . . . .4–32 Analog Input Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4–34

Preset Parameters . . . . . . . . . . . . . . . . . . . . . . . .4–41 Protection Parameters . . . . . . . . . . . . . . . . . . . . .4–43 PID Parameters . . . . . . . . . . . . . . . . . . . . . . . . . .4–51 Display Parameters . . . . . . . . . . . . . . . . . . . . . . . .4–55 Communication Parameters . . . . . . . . . . . . . . . . .4–56

Page 44

Chapter 4: AC Drive Parameters

GS2 Parameter Summary Motor Parameters GS2 Parameter

Description

P0.00

Motor Nameplate Voltage

115V/230V: 200/208/220/230/240 460V: 380/400/415/440/460/480 575V: 380 to 637

P0.01

Motor Nameplate Amps

Drive Rated Amps X .3 to 1.0

Drive Rated Amps x 1.0

P0.02 P0.03 P0.04

Motor Base Frequency

50/60/400

60

Motor Base RPM

375 to 9999 RPM

1750

Motor Maximum RPM

P0.03 to 9999 RPM

P0.03

Range

Default 240 480 575

Ramp Parameters P1.00 P1.01 P1.02 P1.03 P1.04 P1.05 P1.06 P1.07 P1.08 P1.09 P1.10 P1.11 P1.12 P1.17 P1.18 P1.20 P1.21 P1.22

Stop Methods

00: Ramp to Stop 01: Coast to Stop

00

Acceleration Time 1

0.1 to 600.0 sec

10.0

Deceleration Time 1

0.1 to 600.0 sec

30.0

Accel S-curve

0 to 7

00

Decel S-curve

0 to 7

00

Acceleration Time 2

0.1 to 600.0 sec

10.0

Deceleration Time 2

0.1 to 600.0 sec

30.0

Select method to use 2nd Accel/Decel

00: RMP2 from DI terminal 01: Transition Frequencies P1.08 & P1.09

00

0.0 to 400.0 Hz

0.0

0.0 to 400.0 Hz

0.0

Skip Frequency 1

0.0 to 400.0 Hz

0.0

Skip Frequency 2

0.0 to 400.0 Hz

0.0

Skip Frequency 3

0.0 to 400.0 Hz

0.0

Skip Frequency Band

0.0 to 20.0 Hz

0.0

DC Injection Current Level

00 to 100 %

00

DC Injection during Start-up

0.0 to 5.0 sec

0.0

DC Injection during Stopping

0.0 to 25.0 sec

0.0

Start-point for DC Injection

0.0 to 60.0 Hz

0.0

Accel 1 to Accel 2 frequency transition Decel 2 to Decel 1 frequency transition

Parameter can be set during RUN Mode.

4–2

GS2 Series AC Drive User Manual

Page 45

Chapter 4: AC Drive Parameters

Volts/Hertz Parameters GS2 Parameter

Description

Range

Default

00: General Purpose 01: High Starting Torque 02: Fans and Pumps 03: Custom

P2.00

Volts/Hertz Settings

P2.01 P2.02 P2.04

Slip Compensation

0.0 to 10.0

0.0

Auto-torque Boost

00 to 10

00

Mid-point Frequency

0.1 to 400 Hz

1.5

P2.05

Mid-point Voltage

P2.06

Min. Output Frequency

P2.07

Min. Output Voltage

P2.08

PWM Carrier Frequency

115V/230V: 460V: 575V:

00

2.0 to 255V 2.0 to 510V 2.0 to 637V 0.1 to 20.0 Hz

10.0 20.0 24.0 1.50

115V/230V: 460V: 575V:

2.0 to 50.0V 2.0 to 100.0V 2.0 to 130.6V

10.0 20.0 24.0

115V/230V/460V 575V

01 to 15 kHz 01 to 10 kHz

12 6

Digital Parameters

P3.00

P3.01

00: Operation determined by digital keypad 01: Operation determined by external control terminals, keypad STOP is enabled 02: Operation determined by external control Source of Operation Command terminals, keypad STOP is disabled 03: Operation determined by RS-485 interface, keypad STOP is enabled 04: Operation determined by RS-485 interface, keypad STOP is disabled 00: DI1 - FWD / STOP, DI2 - REV / STOP 01: DI1 - RUN / STOP, DI2- REV / FWD Multi-function Input Terminals 02: DI1 - RUN momentary (N.O.) (DI1 - DI2) DI2 - REV / FWD DI3 - STOP momentary (N.C.)

00

00

Parameter can be set during RUN Mode.

1st Ed. Rev. C

12/2006

GS2 Series AC Drive User Manual

4–3

Page 46

Chapter 4: AC Drive Parameters

Digital Parameters (cont.) GS2 Parameter

Description

P3.02

Multi-function Input (DI3)

P3.03

Multi-function Input (DI4)

P3.04

Multi-function Input (DI5)

P3.05

Multi-function Input (DI6)

P3.11

P3.12

P3.16 P3.17 P3.18 P3.19

Range 00: External Fault (N.O.) 01: External Fault (N.C.) 02: External Reset 03: Multi-Speed/PID SP Bit 1 04: Multi-Speed/PID SP Bit 2 05: Multi-Speed/PID SP Bit 3 06: Reserved 07: Reserved 08: Reserved 09: Jog 10: External Base Block (N.O.) 11: External Base Block (N.C.) 12: Second Accel/Decel Time 13: Speed Hold 14: Increase Speed 15: Decrease Speed 16: Reset Speed to Zero 17: PID Disable (N.O.) 18: PID Disable (N.C.) 99: Input Disable

00: AC Drive Running 01: AC Drive Fault Multi-Function Output Terminal 02: At Speed 1 03: Zero Speed 04: Above Desired Frequency 05: Below Desired Frequency 06: At Maximum Speed Multi-Function Output Terminal 07: Over torque detected 08: Above Desired Current 2 09: Below Desired Current 10: PID Deviation Alarm

00

03

04

05

00

01

Desired Frequency

0.0 to 400.0 Hz

0.0

Desired Current

0.0 to <Drive Rated Amps>

0.0

PID Deviation Level

1.0 to 50.0 %

10.0

PID Deviation Time

0.1 to 300.0 sec

5.0

Parameter can be set during RUN Mode.

4–4

Default

GS2 Series AC Drive User Manual

Page 47

Chapter 4: AC Drive Parameters

Analog Parameters GS2 Parameter

P4.00

P4.01 P4.02 P4.03 P4.04

P4.05

Description

Range

Default

00: Frequency determined by keypad potentiometer 01: Frequency determined by digital keypad up/down 02: Frequency determined by 0 to +10V input on AI terminal with jumpers Source of Frequency Command 03: Frequency determined by 4 to 20mA input on AI terminal with jumpers 04: Frequency determined by 0 to 20mA input on AI terminal with jumpers 05: Frequency determined by RS-232C/ RS-485 communication interface 00: No Offset Analog Input Offset Polarity 01: Positive Offset 02: Negative Offset

00

00

Analog Input Offset

0.0 to 100.0%

0.0

Analog Input Gain

0.0 to 300.0%

100.0

00: Forward Motion Only 01: Reverse Motion Enable

00

00: Decelerate to 0Hz 01: Stop immediately and display error code “EF” 02: Continue operation by the last frequency command

00

Analog Input Reverse Motion Enable Loss of ACI Signal (4-20mA)

P4.11

Analog Output Signal

00: frequency Hz 01: Current A 02: PV

00

P4.12

Analog Output Gain

00 to 200%

100

Presets P5.00 P5.01 P5.02 P5.03 P5.04 P5.05 P5.06 P5.07

Jog

0.0 to 400.0 Hz

6.0

Multi-Speed 1

0.0 to 400.0 Hz

0.0

Multi-Speed 2

0.0 to 400.0 Hz

0.0

Multi-Speed 3

0.0 to 400.0 Hz

0.0

Multi-Speed 4

0.0 to 400.0 Hz

0.0

Multi-Speed 5

0.0 to 400.0 Hz

0.0

Multi-Speed 6

0.0 to 400.0 Hz

0.0

Multi-Speed 7

0.0 to 400.0 Hz

0.0

Parameter can be set during RUN Mode.

1st Ed. Rev. C

12/2006

GS2 Series AC Drive User Manual

4–5

Page 48

Chapter 4: AC Drive Parameters

Protection Parameters GS2 Parameter

Description

P6.00

Electronic Thermal Overload Relay

P6.01

Auto Restart after Fault

P6.02

Momentary Power Loss

P6.03

Reverse Operation Inhibit

Range 00: Constant Torque 01: Variable Torque 02: Inactive

00

00 to 10

00

00: Stop operation after momentary power loss 01: Continue operation after momentary power loss, speed search from Speed Reference 02: Continue operation after momentary power loss, speed search from Minimum Speed 00: Enable Reverse Operation 01: Disable Reverse Operation

00

00

00: AVR enabled 01: AVR disabled 02: AVR disabled during decel 03: AVR disabled during stop

00

P6.04

Auto Voltage Regulation

P6.05

Over-Voltage Stall Prevention

00: Enable Over-voltage Stall Prevention 01: Disable Over-voltage Stall Prevention

00

Auto Adjustable Accel/Decel

00: Linear Accel/Decel 01: Auto Accel, Linear Decel 02: Linear Accel, Auto Decel 03: Auto Accel/Decel 04: Auto Accel/Decel Stall Prevention (limited by P1.01, P1.02, P1.05, P1.06)

00

P6.07

Over-Torque Detection Mode

00: Disabled 01: Enabled during constant speed operation 02: Enabled during acceleration

00

P6.08 P6.09

Over-Torque Detection Level

30 to 200%

150

Over-Torque Detection Time

0.1 to 10.0

0.1

20 to 200%

150

20 to 200%

150

Maximum Allowable Power Loss Time

0.3 to 5.0 sec

2.0

P6.06

P6.10 P6.11

Over-Current Stall Prevention during Acceleration Over-Current Stall Prevention during Operation

P6.12 P6.13 P6.14 P6.15 P6.16

Base-Block Time for Speed Search

0.3 to 5.0 sec

0.5

Maximum Speed Search Current Level

30 to 200%

150

Upper Bound of Output Frequency

0.1 to 400Hz

400

Lower Bound of Output Frequency

0.0 to 400Hz

0.0

P6.30

Line Start Lockout

00: Enable Line Start Lockout 01: Disable Line Start Lockout

00

Parameter can be set during RUN Mode.

4–6

Default

GS2 Series AC Drive User Manual

Page 49

Chapter 4: AC Drive Parameters

Protection Parameters (cont.) GS2 Parameter P6.31

P6.32

P6.33

P6.34

P6.35

P6.36

Description

Range

Default

00: No Fault occurred 01: Over-current (oc) Present Fault Record 02: Over-voltage (ov) 03: Overheat (oH) 04: Overload (oL) Second Most Recent Fault Record 05: Overload 1 (oL1) 06: Overload 2 (oL2) 07: External Fault (EF) Third Most Recent Fault Record 08: CPU failure 1 (CF1) 09: CPU failure 2 (CF2) 10: CPU failure 3 (CF3) 11: Hardware Protection Failure (HPF) Fourth Most Recent Fault Record 12: Over-current during accel (OCA) 13: Over-current during decel (OCd) 14: Over-current during steady state (OCn) 15:Ground fault or fuse failure (GFF) Fifth Most Recent Fault Record 16: Reserved 17: Input power 3-phase loss 18: External Base-Block (bb) Sixth Most Recent Fault Record 19: Auto Adjust accel/decel failure (cFA) 20: Software protection code (codE)

00

00

00

00

00

00

Parameter can be set during RUN Mode.

1st Ed. Rev. C

12/2006

GS2 Series AC Drive User Manual

4–7

Page 50

Chapter 4: AC Drive Parameters

PID Parameters GS2 Parameter

P7.00

Description

Range

00: Inhibit PID operation 01: Forward-acting (heating loop) PID feedback, PV from AVI (0 to + 10V 02: Forward-acting (heating loop) PID Input Terminal for PID Feedback feedback, PV from ACI (4 to 20mA) 03: Reverse-acting (cooling loop) PID feedback, PV from AVI (0 to +10V). 04: Reverse-acting (cooling loop) PID feedback, PV from ACI (4 to 20mA).

P7.01

PV 100% Value

P7.02

PID Setpoint Source

P7.10 P7.11 P7.12 P7.13 P7.14 P7.15 P7.16 P7.17 P7.20 P7.21 P7.22 P7.23 P7.24 P7.25 P7.26 P7.27

Default

00

0.0 to 999 00: Keypad 01: Serial Communications

100.0

Keypad PID Setpoint

0.0 to 999

0.0

PID Multi-setpoint 1

0.0 to 999

0.0

PID Multi-setpoint 2

0.0 to 999

0.0

PID Multi-setpoint 3

0.0 to 999

0.0

PID Multi-setpoint 4

0.0 to 999

0.0

PID Multi-setpoint 5

0.0 to 999

0.0

PID Multi-setpoint 6

0.0 to 999

0.0

PID Multi-setpoint 7

0.0 to 999

0.0

00

Proportional Control

0.0 to 10.0

1.0

Integral Control

0.00 to 100.0 sec

1.00

Derivative Control

0.00 to 1.00 sec

0.00

Upper Bound for Integral Control

00 to 100%

100

Derivative Filter Time Constant

0.0 to 2.5 sec

0.0

PID Output Frequency Limit

00 to 110%

100

Feedback Signal Detection Time

0.0 to 3600 sec. 00: Warn and AC Drive Stop 01: Warn and Continue Operation

60

PID Feedback Loss

00

Display Parameters

P8.00

User Defined Display Function

P8.01

Frequency Scale Factor

00: Output Frequency (Hz) 01: Motor Speed (RPM) 02: Output Freq. X P8.01 03: Output Current (A) 04: Motor Output Current (%) 05: Output Voltage (V) 06: DC Bus Voltage (V) 07: PID Setpoint 08: PID Feedback Signal (PV) 09: Frequency Setpoint

00

0.01 to 160.0

1.0

Parameter can be set during RUN Mode.

4–8

GS2 Series AC Drive User Manual