Page 81
Chapter 4: AC Drive Parameters
Example 5: Reduced Analog Gain and Increased Maximum Output Frequency This example illustrates two separate features: 1) limiting the Maximum Frequency Reference by reducing the Analog Input Gain 2) increasing the Maximum Output Frequency to run the motor faster than the Motor Base RPM
When the Analog Input is at its maximum value (10V or 20mA), the set-point frequency will be 50Hz. However, the Jog and Multi-speed settings can set the output as high as 70Hz. • Minimum Frequency Reference = 0Hz • Maximum Frequency Reference = 50 Hz • Motor Maximum RPM = 2042 rpm WARNING: The Motor Maximum RPM parameter (P0.04) should never exceed the maximum speed rating for the motor you are using. If this information is not readily available, consult your motor manufacturer.
Calculations A) Max. Output Frequency = B) Analog Offset % = C) Analog Gain % =
RPM x 60Hz = 70Hz ( 2042 1750 RPM )
0Hz ( 50Hz ) x 100 = 0%
– (0Hz) ( 50Hz70Hz ) x 100 = 71.4%
D) Mid-point Frequency =
( 50Hz –2 (0Hz) )+ (0Hz) = 25Hz
Parameter Settings P0.04: 2042 – Motor Maximum RPM P4.01: 00 – Offset disabled P4.02: 00 – 0% Analog Input Offset P4.03: 71.4 – 71.4% Analog Input Gain P4.04: 00 – Forward Motion Only
Results Max. Output Frequency
70Hz
Motor Base Frequency
60Hz
25
Max. Frequency Reference 50Hz 25Hz 0
0Hz 0V 0mA 4mA
1st Ed. Rev. C
12/2006
5V 10mA 12mA
10V 20mA 20mA
Hz
50
10V 0V 20mA 0mA 20mA 4mA Potentiometer Scale
GS2 Series AC Drive User Manual
4–39
Page 82
Chapter 4: AC Drive Parameters
P4.05
Loss of ACI Signal (4-20mA) Settings: 00 - Decelerate to 0Hz Default Setting: 00 01 - Stop immediately and display “EF”. 02 - Continue operation by the last frequency command This parameter determines the operation of the drive when the ACI frequency command is lost.
P4.11
Analog Output Signal Range: 00 - Frequency Hz 01 - Current A 02 - PV
Default Setting: 00
This parameter selects either Output Frequency or current to be displayed using the 0 to 10V A0 output.
P4.12
Analog Output Gain Range: 00 to 200%
Default Setting: 100
This parameter sets the voltage range of the analog output signal, on output terminal A0.
A0
ACM
A0
ACM
Potentiometer (3-5k⏲)
Potentiometer (3-5k⏲)
+
–
Analog Frequency Meter
+
–
Analog Current Meter
•The analog output voltage is directly proportional to the output frequency of the AC drive. With the factory setting of 100%, the Maximum Output Frequency of the AC drive corresponds to +10VDC analog voltage output. (The actual voltage is about +10VDC, and can be adjusted by P4.12) •The analog output voltage is directly proportional to the output current of the AC drive. With the factory setting of 100%, the 2.5 times rated current of the AC drive corresponds to +10 VDC analog voltage output. (The actual voltage is about +10 VDC, and can be adjusted by P4.12). Note: Any type of voltmeter can be used. If the meter reads full scale at a voltage less than 10 volts, then P4.12 should be set by the following formula: P4.12 = (meter full scale voltage ÷ 10)×100% For Example: When using the meter with full scale of 5 Volts, adjust P4.12 to 50%.
4–40
GS2 Series AC Drive User Manual
Page 83
Chapter 4: AC Drive Parameters
Preset Parameters P5.00
Jog Range: 0.0 to 400.0 Hz
Default Setting: 6.0
The Jog Command is selected by a Multi-Function Input Terminal (P3.02 to P3.05) set to the Jog Function (09).
Frequency Jog Frequency P 5.00
Jog Operation Command
1st Ed. Rev. C
12/2006
Accel
Decel
P 1.01/P 1.05
P 1.02/P 1.06
ON
Time
OFF
GS2 Series AC Drive User Manual
4–41
Page 84
Chapter 4: AC Drive Parameters
P5.01
Multi-Speed 1
P5.02
Multi-Speed 2
P5.03
Multi-Speed 3
P5.04
Multi-Speed 4
P5.05
Multi-Speed 5
P5.06
Multi-Speed 6
P5.07
Multi-Speed 7 Range for P5.01 - P5.07: 0.0 to 400.0 Hz
Default Setting: 0.0
•The Multi-Function Input Terminals (refer to P3.01 to P3.05) are used to select one of the AC drive Multi-Step speeds. The speeds (frequencies) are determined by P5.01 to P5.07 shown above.
Multi-Speed Bits Bit 3 Bit 2 Bit 1
Speed Selection
OFF
OFF
OFF
OFF
OFF
ON P5.01: Multi-Speed 1
OFF
ON ON
OFF
ON P5.03: Multi-Speed 3
OFF
OFF
OFF
ON P5.05: Multi-Speed 5
ON ON
OFF
OFF
ON ON ON ON
P4.00: Source of Frequency P5.02: Multi-Speed 2 P5.04: Multi-Speed 4 P5.06: Multi-Speed 6
ON P5.07: Multi-Speed 7
Note: When all multi-speed inputs are off, the AC drive reverts back to the Command Frequency (P4.00).
4–42
GS2 Series AC Drive User Manual
Page 85
Chapter 4: AC Drive Parameters
Protection Parameters P6.00
Electronic Thermal Overload Relay Default Setting: 00 Settings: 00
Constant Torque (inverter/vector duty motors) Use this setting when using the drives with motors designed specifically for AC drive outputs and for running at low speeds with high currents. Motor currents will be 100% throughout the speed range, and can be up to 150% for one minute.
01
T 100%
Output (Hz)
Variable Torque (fan cooled standard motors) Use this setting when using the drives with motors which are NOT designed specifically for AC drive outputs. Motors with shaft mounted fans offer poor cooling at low speeds, therefore the output can be derated at lower output frequencies. This derated current is for protecting the motor at lower speeds.
T 100%
40%
50
Output (Hz)
The output current is derated as follows: • Ioutput (%) = [ ƒoutput (Hz) x 1.2 %/Hz ] + 40% Example: If the rated motor current is 10A, and the output frequency is 25Hz, the derating will be 70%, and the overload will be 10.5A (150%) for one minute. • Ioutput (%) = [ (25Hz) (1.2 %/Hz) ] + 40% = 70% • 10A x 70% = 7A • 7A x 150% = 10.5A 02
1st Ed. Rev. C
12/2006
Inactive
GS2 Series AC Drive User Manual
4–43
Page 86
Chapter 4: AC Drive Parameters
P6.01
Auto Restart After Fault Range: 00 to 10
Default Setting: 00
• After fault occurs (allowable faults: over-current OC, over-voltage OV), the AC drive can be reset/restarted automatically up to 10 times. Setting this parameter to 0 will disable the reset/restart operation after any fault has occurred. When enabled, the AC drive will restart with speed search, which starts at the previous Frequency. To set the fault recovery time after a fault, please see (P6.13) baseblock time for speed search.
P6.02
Momentary Power Loss Default Setting: 00 Settings:
00
Stop operation after momentary power loss.
01
Continue operation after momentary power loss, speed search from Speed Reference.
02
Continue operation after momentary power loss, speed search from Minimum Speed.
Note: Also refer to P6.30, Line Start Lockout. Note: This parameter (P6.02) will work only if the Source of Operation (P3.00) is set to something other than 00 (Operation determined by digital keypad).
P6.03
Reverse Operation Inhibit Default Setting: 00 Settings:
00
Enable Reverse Operation
01
Disable Reverse Operation
This parameter determines whether the AC Motor Drive can operate in the reverse direction.
4–44
GS2 Series AC Drive User Manual
Page 87
Chapter 4: AC Drive Parameters
P6.04
Auto Voltage Regulation Default Setting: 00 Settings:
00
AVR enabled
01
AVR disabled
02
AVR disabled during decel
03
AVR disabled during Stop
• AVR function automatically regulates the AC drive output voltage to the Maximum Output Voltage (P0.00). For instance, if P0.00 is set at 200 VAC and the input voltage is at 200V to 264 VAC, then the Maximum Output Voltage will automatically be regulated to 200 VAC. • Without AVR function, the Maximum Output Voltage may vary between 180V to 264 VAC, due to the input voltage varying between 180V to 264 VAC. • Selecting program value 2 enables the AVR function and also disables the AVR function during deceleration. This offers a quicker deceleration.
P6.05
Over-Voltage Stall Prevention Range: 00 Enable Over-voltage Stall Prevention 01 Disable Over-voltage Stall Prevention
Default Setting: 00
• During deceleration, the AC drive DC bus voltage may exceed its Maximum Allowable Value due to motor regeneration. When this function is enabled, the AC drive will stop decelerating, and maintain a constant output frequency. The drive will resume deceleration when the voltage drops below the factory-preset value.
DC bus voltage Over-voltage Detection Level time Output Frequency time Note: With moderate inertial loads, over-voltage during deceleration will not occur. For applications with high inertia loads, the AC drive will automatically extend the deceleration time. If deceleration time is critical for the application, a dynamic braking resistor should be used. Set this parameter to 01 (disable) when using a dynamic braking resistor.
1st Ed. Rev. C
12/2006
GS2 Series AC Drive User Manual
4–45
Page 88
Chapter 4: AC Drive Parameters
P6.06
Auto Adjustable Accel/Decel Default Setting: 00 Settings:
00
Linear Accel/Decel
01
Auto Accel, Linear Decel
02
Linear Accel, Auto Decel
03
Auto Accel/Decel
04
Auto Accel/Decel Stall Prevention
If the auto accel/decel is selected, the AC drive will accel/decel in the fastest and smoothest means possible by automatically adjusting the time of accel/decel. This parameter provides five modes to choose: • 00 Linear Acceleration and deceleration (operation by P1.01, P1.02 or P1.05, P1.06 acceleration/deceleration time). • 01 Automatic acceleration, linear deceleration (Operation by automatic acceleration time, P1.02 or P1.06 deceleration time). • 02 Linear acceleration and automatic deceleration (Operation by automatic acceleration time, P1.01 or P1.05 acceleration time). • 03 Automatic acceleration, deceleration (Operation by AC drive auto adjustable control). • 04 Auto acceleration, deceleration. The auto accel/decel will not be quicker than the settings for acceleration (P1.01 or P1.05) or deceleration (P1.02 or P1.06). The operation is specific to preventing a stall.
P6.07
Over-Torque Detection Mode Default Setting: 00 Settings:
P6.08
00
Disabled
01
Enabled during constant speed operation
02
Enabled during acceleration
Over-Torque Detection Level Range: 30 to 200%
Default Setting: 150
• A setting of 100% is proportional to the Rated Output Current of the drive. • This parameter sets the Over-Torque Detection level in 1% increments. (The AC drive rated current is equal to 100%.)
P6.09
Over-Torque Detection Time Range: 0.1 to 10.0
Default Setting: 0.1
This parameter sets the Over-Torque Detection Time in units of 0.1 seconds.
4–46
GS2 Series AC Drive User Manual
Page 89
Chapter 4: AC Drive Parameters
P6.10
Over-Current Stall Prevention During Acceleration Range: 20 to 200%
Default Setting: 150
A setting of 100% is equal to the Rated Output Current of the drive. • Under certain conditions, the AC drive output current may increase abruptly, and exceed the value specified by P6.10 This is commonly caused by rapid acceleration or excessive load on the motor. When this function is enabled, the AC drive will stop accelerating and maintain a constant output frequency. The AC drive will only resume acceleration when the current drops below the maximum value.
P6.11
Over-Current Stall Prevention During Operation Range: 20 to 200%
Default Setting: 150
• During steady-state operation with motor load rapidly increasing, the AC drive output current may exceed the limit specified in P6.11. When this occurs, the output frequency will decrease to maintain a constant motor speed. The drive will accelerate to the steady-state output frequency only when the output current drops below the level specified by P6.11. Output current
Output current
Over-current detection level
Over-current detection level P 6.11
P 6.10 tim e Output frequency tim e output freq tim e Over-current Stall Prevention during Acceleration
1st Ed. Rev. C
12/2006 tim e Over-current Stall Prevention during Operation
GS2 Series AC Drive User Manual
4–47
Page 90
Chapter 4: AC Drive Parameters
P6.12
Maximum Allowable Power Loss Time Range: 0.3 to 5.0 sec
Default Setting: 2.0
• During a power loss, if the power loss time is less than the time defined by this parameter, the AC drive will resume operation. If the Maximum Allowable Power Loss Time is exceeded, the AC drive output is turned off.
P6.13
Base-Block Time for Speed Search Range: 0.3 to 5.0 sec
Default Setting: 0.5
• When a momentary power loss is detected, the AC drive turns off for a specified time interval determined by P6.13 before resuming operation. This time interval is called Base-Block. This parameter should be set to a value where the residual output voltage due to regeneration is nearly zero, before the drive resumes operation. • This parameter also determines the searching time when performing external BaseBlock and Fault Reset (P6.01)
P6.14
Maximum Speed Search Current Level Range: 30 to 200%
Default Setting: 150
• Following a power failure, the AC drive will start its speed search operation only if the output current is greater than the value determined by P6.14. When the output current is less than that of P6.14, the AC drive output frequency is at a "speed synchronization point". The drive will start to accelerate or decelerate back to the operating frequency at which it was running prior to the power failure. Max. Allowable Power Loss Time Input Power
Output Frequency
Output Voltage
P 6.12
P 6.12 speed synchronization detection
P 6.02 = 01 Speed Search starts with the previous Frequency
Baseblock Time P 6.13
Speed Search
4–48
Max. Allowable Power Loss Time
GS2 Series AC Drive User Manual
P 6.02 = 02 Speed Search starts w ith Minimum Output Frequency Baseblock Time P 6.13