Page 91
Chapter 4: AC Drive Parameters
P6.15
Upper Bound of Output Frequency Range: 0.1 to 400 Hz
Default Setting: 400
• The Upper/Lower Bound of Output Frequency is to prevent operation error and machine damage. • This parameter must be equal to or greater than the Lower Bound of Output Frequency (P6.16). • If the Upper Bound of Output Frequency is 50 Hz and the Maximum Output Frequency is 60 Hz, then any Command Frequency above 50 Hz will generate a 50 Hz output from the drive. • The Output Frequency is also limited by the Motor Maximum RPM (P0.04).
P6.16
Lower Bound of Output Frequency Range: 0.0 to 400 Hz
Default Setting: 0.0
• The Upper/Lower Bound of Output Frequency is to prevent operation error and machine damage. • This parameter must be equal to or less than the Upper Bound of Output Frequency (P6.15). • If the Lower Bound of Output Frequency is 10 Hz, and the Minimum Output Frequency (P2.06) is set at 1.0 Hz, then any Command Frequency between 1-10 Hz will generate a 10 Hz output from the drive. • The Upper/Lower Bound of Output Frequency is to prevent operation error and machine damage. Maximum Output Frequency P 6.15
P 6.16 Command Frequency
P6.30
Line Start Lockout Default Setting: 00 Settings:
00 01
Enable Line Start Lockout Disable Line Start Lockout
When this parameter is enabled, the AC Motor Drive will not start when powered up with a RUN command already applied. The drive must see the RUN command change from STOP to RUN before it will start. When this parameter is disabled, the AC Motor Drive will start when powered up with a RUN command already applied.
1st Ed. Rev. C
12/2006
GS2 Series AC Drive User Manual
4–49
Page 92
Chapter 4: AC Drive Parameters
P6.31
Present Fault Record
P6.32
Second Most Recent Fault Record
P6.33
Third Most Recent Fault Record
P6.34
Fourth Most Recent Fault Record
P6.35
Fifth Most Recent Fault Record
P6.36
Sixth Most Recent Fault Record Default Setting: 00 Settings for P6.31 - P6.36:
4–50
00
No Fault occurred
01
Over-current (oc)
02
Over-voltage (ov)
03
Overheat (oH)
04
Overload (oL)
05
Overload 1 (oL1)
06
Overload 2 (oL2)
07
External Fault (EF)
08
CPU failure 1 (CF1)
09
CPU failure 2 (CF2)
10
CPU failure 3 (CF3)
11
Hardware Protection Failure (HPF)
12
Over-current during accel (OCA)
13
Over-current during decel (OCd)
14
Over-current during steady state (OCn)
15
Ground fault or fuse failure (GFF)
16
Reserved
17
Input Power 3 phase loss
18
External Base Block (bb)
19
Auto Adjust Accel/decel failure (cFA)
20
Software protection code (co)
GS2 Series AC Drive User Manual
Page 93
Chapter 4: AC Drive Parameters
PID Parameters Input Terminal for PID Feedback
P7.00
Default Setting: 00 Settings:
00 01
Inhibit PID operation. Forward-acting (heating loop) PID feedback, PV from AVI (0 to +10V)
02
Forward-acting (heating loop) PID feedback, PV from ACI (4 to 20mA)
03
Reverse-acting (cooling loop) PID feedback, PV from AVI (0 to +10V)
04
Reverse-acting (cooling loop) PID feedback, PV from ACI (4 to 20mA)
Forward-acting Loop Setpoint
P
+ –
P 7.10-P7.17
P7.20
I
P 7.21
Integral gain limit
+
P 7.23
+ +
Output Freq. Limit
P 7.25
Digital filter
P 7.24
Freq. Command
D
P 7.22 PID Feedback Signal
Reverse-acting Loop Setpoint
P
–
P 7.10-P7.17
+
P7.20
I
P 7.21
Integral gain limit
P 7.23
+
+ +
Output Freq. Limit
P 7.25
Digital filter
P 7.24
Freq. Command
D
P 7.22 PID Feedback Signal
Note: Reverse-acting PID loops are available only for GS2 AC drives with firmware version 1.04 or higher. Note: When using PID operation, the Source of Frequency parameter (P4.00) must be set to 00 or 01. If PID operation is disabled, the AC drive will operate using the Source of Frequency specified by P4.00.
1st Ed. Rev. C
12/2006
GS2 Series AC Drive User Manual
4–51
Page 94
Chapter 4: AC Drive Parameters
P7.01
PV 100% Value Range: 0.0 to 999 Default Setting: 100.0 This parameter should be set to the value corresponding to the 100% value of the process variable (PV). The setting for P7.01 cannot be less than any setting for P7.10 to P7.17. Note: The setting for PV 100% value (P7.01) cannot be set less than any value set for P7.10 to P7.17. If you are unable to reduce P7.01 to the desired value, check parameters P7.10 to P7.17 and reduce these values accordingly.
P7.02
PID Setpoint Source Settings: 00 - Keypad 01 - Serial Communications
P7.10
Default Setting: 00
Keypad PID Setpoint Range: 0.0 to 999
Default Setting: 0.0
Note: The settings for P7.10 to P7.17 cannot exceed the setting for P7.01.
P7.11
PID Multi-setpoint 1 Range: 0.0 to 999
Default Setting: 0.0
•The Multi-Function Input Terminals DI3 to DI6 are used to select one of the PID Multi-Setpoints. (For further explanation, refer to settings 03, 04, and 05 for P3.02 to P3.05.) The setpoints are determined by P7.11 to P7.17.
P7.12
PID Multi-setpoint 2 Range: 0.0 to 999
Default Setting: 0.0
•Refer to P7.11 for explanation.
P7.13
PID Multi-setpoint 3 Range: 0.0 to 999
Default Setting: 0.0
•Refer to P7.11 for explanation.
P7.14
PID Multi-setpoint 4 Range: 0.0 to 999
Default Setting: 0.0
•Refer to P7.11 for explanation.
P7.15
PID Multi-setpoint 5 Range: 0.0 to 999 •Refer to P7.11 for explanation.
4–52
GS2 Series AC Drive User Manual
Default Setting: 0.0
Page 95
Chapter 4: AC Drive Parameters
P7.16
PID Multi-setpoint 6 Range: 0.0 to 999
Default Setting: 0.0
•Refer to P7.11 for explanation.
P7.17
PID Multi-setpoint 7 Range: 0.0 to 999
Default Setting: 0.0
•Refer to P7.11 for explanation.
P7.20
Proportional Control (P) Range: 0.0 to 10.0 Default Setting: 1.0 The first parameter of PID control is Proportional Control (P). For a given process, if the Proportional Value is set too low, the control action will be too sluggish. If the Proportional value is set too high, the control action will be unstable (erratic). Set the Integral Control (I) and Derivative Control (D) to zero (0). Begin tuning the process with a low Proportional Value, and increase the Proportional value until the system goes unstable (erratic). When instability is reached, reduce the Proportional Value slightly until the system becomes stable (smaller values reduce system Gain). Stability can be tested by moving between two wide-spread setpoint values. With 10% deviation and P=1, then P X 10% = Control Output. For example, if the speed of a motor is dragged down 10% due to a load increase, a corrective speed signal increase of 10% is generated. In a perfect world, this increase in speed command should bring the motor speed back to normal.
P7.21
Integral Control (I) Range: 0.00 to 100.0 sec (0.00 disable)
Default Setting: 1.00
Using only the Proportional Control, the corrective action may not increase fast enough or the setpoint may never be reached because of system losses. The Integral Control is used to generate additional corrective action. When tuning, begin with a large Integral value and reduce the value until the system goes unstable (erratic). When instability is reached, increase the Integral value slightly until the system becomes stable and the desired setpoint value is reached.
P7.22
Derivative Control (D) Range: 0.00 to 1.00 sec
Default Setting: 0.00
If the control output is too sluggish after the Proportional Control (P) and Integral Control (I) values are set, Derivative Control (D) may be required. Begin with a high Derivative value and reduce the value to the point of system instability. Then increase the Derivative value until the control output regains stability. Stability can be tested by moving between two wide-spread setpoint values.
1st Ed. Rev. C
12/2006
GS2 Series AC Drive User Manual
4–53
Page 96
Chapter 4: AC Drive Parameters
P7.23
Upper Bound for Integral Control Range: 00 to 100%
Default Setting: 100
• This parameter defines an upper boundary or limit for the integral gain (I) and therefore limits the Master Frequency. Use the formula below to calculate the Integral upper limit. Max. Output Frequency =
Motor Max. RPM (P0-04) x Base Frequency (P0-02) ( Motor Base RPM (P0-03) )
• The formula is: Integral upper limit = (Maximum Output Frequency) X P7.23. This parameter can limit the Maximum Output Frequency
P7.24
Derivative Filter Time Constant Range: 0.0 to 2.5 sec
Default Setting: 0.0
• To avoid amplification of measured noise in the controller output, a derivative digital filter is inserted. This filter helps smooth oscillations. Larger values for P7.24 provide more smoothing.
P7.25
PID Output Frequency Limit Range: 00 to 110%
Default Setting: 100
• This parameter defines the percentage of output frequency limit during the PID control. The formula is Output Frequency Limit = (Maximum Output Frequency) X P7.25. This parameter will limit the Maximum Output Frequency. Max. Output Frequency =
P7.26
Motor Max. RPM (P0-04) x Base Frequency (P0-02) ( Motor Base RPM (P0-03) )
Feedback Signal Loss Detection Time Range: 0.0 to 3600 sec
Default Setting: 60
• This parameter defines how long the PID Feedback signal is lost before an error is generated. Setting this parameter to 0.0 disables the PID Feedback loss timer. When the feedback signal is lost, PID Feedback loss timer starts timing. When the timer value is greater than the setting value of P. 7.26, the PID Feedback Loss parameter (P7.27) is activated. Furthermore, the Keypad will display "FbE" means the feedback abnormality detected. When the signal is corrected, the warning message "FbE" will automatically be cleared.
P7.27
PID Feedback Loss Operation Range: 00 - Warn and AC Drive Stop 01 - Warn and Continue Operation
Default Setting: 00
• This parameter sets the operation of the drive when there is a loss of the PID feedback signal. • This parameter only functions with 4-20ma for feedback loss operation.
4–54
GS2 Series AC Drive User Manual
Page 97
Chapter 4: AC Drive Parameters
Display Parameters P8.00
User Defined Display Function Default Setting: 00 Settings:
P8.01
00 01 02 03 04 05 06 07 08 09
Output Frequency (Hz) Motor Speed (RPM) Output Frequency x P8.01 Output Current (A) Motor Output Current (%) Output Voltage(V) DC Bus Voltage (V) PID Setpoint PID Feedback (PV) Frequency Setpoint
Frequency Scale Factor Range: 0.01 to 160.0
Default Setting: 1.0
This parameter can be used to multiply the display unit by a scaling factor so that the display will represent some other user desired unit. For example, the user may want to scale the drive display to represent ft/min for a motor that is driving a conveyor. The coefficient K determines the multiplying factor for the user-defined unit. • The display value is calculated as follows: Display value = output frequency x K • The display window is only capable of showing four digits, but P8.01 can be used to create larger numbers. The display window uses decimal points to signify numbers up to five digits as explained below: DISPLAY
1st Ed. Rev. C
NUMBER REPRESENTED
9999
The absence of a decimal point indicates a four digit integer.
999.9
A single decimal point between the middle and the right-most numbers is a true decimal point; it separates ones and tenths as in “300.5 (three hundred and one-half).
9999.
A single decimal point after the right-most number is not a true decimal point; instead it indicates that a zero follows the right-most numbers. For example, the number 12340 would be displayed as “1234.”.
12/2006
GS2 Series AC Drive User Manual
4–55
Page 98
Chapter 4: AC Drive Parameters
Communication Parameters P9.00
Communication Address Range: 01 to 254
Default Setting: 01
• If the AC drive is controlled by serial communication, the communication address must be set via this parameter.
RS–485 01
02
03
...
Modbus Device
P9.01
Transmission Speed Range: 00 to 03 Setting
Default Setting: 01 00: 4800 baud data transmission speed 01: 9600 baud data transmission speed 02: 19200 baud data transmission speed 03: 38400 baud data transmission speed
• Users can set parameters and control the operation of the AC drive via the RS-485 serial interface of a personal computer. This parameter is used to set the transmission speed between the computer and AC drive.
P9.02
Communication Protocol Default Setting: 00 Settings:
00
MODBUS ASCII mode. <7 data bits, no parity, 2 stop bits>
01
MODBUS ASCII mode <7 data bits, even parity, 1 stop bit> MODBUS ASCII mode <7 data bits, odd parity, 1 stop bit> MODBUS RTU mode <8 data bits, no parity, 2 stop bits> MODBUS RTU mode <8 data bits, even parity, 1 stop bit>
02 03 04 05
4–56
MODBUS RTU mode <8 data bits, odd parity, 1 stop bit>
GS2 Series AC Drive User Manual
Page 99
Chapter 4: AC Drive Parameters
P9.03
Transmission Fault Treatment Default Setting: 00 Settings:
00 - Display fault and continue operating 01 - Display fault and RAMP to stop 02 - Display fault and COAST to stop 03 - No fault displayed and continue operating
P9.04
Time Out Detection Range: 00 - Disable 01 - Enable
Default Setting: 00
•This parameter is used for ASCII mode. When this parameter is set to 01, it indicates that the over-time detection is enabled and the time slot between each character cannot exceed 500 ms.
P9.05
Time Out Duration Range: 0.1 to 60.0 seconds
P9.07
Default Setting: 0.5
Parameter Lock Default Setting: 00 Settings:
P9.08
00 01
All parameters can be set and read All parameters are read only
Restore to Default Settings: 0 or 99 •• Setting 99 restores all parameters to factory defaults. ••
1st Ed. Rev. C
12/2006
Default Setting: 00
GS2 Series AC Drive User Manual
4–57
Page 100
Chapter 4: AC Drive Parameters
P9.11
Block Transfer Parameter 1 Range: P0.00 to P8.01, P9.99 Default Setting: P9.99 The sequential block transfer parameters (P9.11 through P9.25) allow you to "group" various miscellaneous non-sequential parameters, so that only one PLC programming write instruction is required to update those parameters, instead of three separate write instructions. • Example: Writing directly to three non-sequential parameters P1.00, P1.02, and P1.04 requires three separate write instructions from the PLC. However, those drive parameters can be updated with only one PLC write instruction to the sequential transfer blocks P9.11 through P9.13; if P9.11 is set to P1.00, P9.12 is set to P1.02, and P9.13 is set to P1.04.
P9.12
Block Transfer Parameter 2 Range: P0.00 to P8.01, P9.99
P9.13
Block Transfer Parameter 3 Range: P0.00 to P8.01, P9.99
P9.14
Default Setting: P9.99
Block Transfer Parameter 9 Range: P0.00 to P8.01, P9.99
4–58
Default Setting: P9.99
Block Transfer Parameter 8 Range: P0.00 to P8.01, P9.99
P9.19
Default Setting: P9.99
Block Transfer Parameter 7 Range: P0.00 to P8.01, P9.99
P9.18
Default Setting: P9.99
Block Transfer Parameter 6 Range: P0.00 to P8.01, P9.99
P9.17
Default Setting: P9.99
Block Transfer Parameter 5 Range: P0.00 to P8.01, P9.99
P9.16
Default Setting: P9.99
Block Transfer Parameter 4 Range: P0.00 to P8.01, P9.99
P9.15
Default Setting: P9.99
GS2 Series AC Drive User Manual
Default Setting: P9.99