Page 101
Chapter 4: AC Drive Parameters
P9.20
Block Transfer Parameter 10 Range: P0.00 to P8.01, P9.99
P9.21
Default Setting: P9.99
Block Transfer Parameter 11 Range: P0.00 to P8.01, P9.99
P9.22
Default Setting: P9.99
Block Transfer Parameter 12 Range: P0.00 to P8.01, P9.99
P9.23
Default Setting: P9.99
Block Transfer Parameter 13 Range: P0.00 to P8.01, P9.99
P9.24
Default Setting: P9.99
Block Transfer Parameter 14 Range: P0.00 to P8.01, P9.99
P9.25
Default Setting: P9.99
Block Transfer Parameter 15 Range: P0.00 to P8.01, P9.99
P9.26
Default Setting: P9.99
Serial Comm Speed Reference Range: 0.0 to 400.0 Hz
Default Setting: 60.0
• This parameter is used to set the Frequency Command when the AC drive is controlled by communication interface. Note: In order for this parameter to function, the Source of Frequency Command (P4.00) must be set to 05.
P9.27
Comm RUN Command Range: 00 - Stop 01 - Run
P9.28
Serial Comm Direction Command Range: 00 - Forward 01 - Reverse
1st Ed. Rev. C
Default Setting: 00
12/2006
Default Setting: 00
GS2 Series AC Drive User Manual
4–59
Page 102
Chapter 4: AC Drive Parameters
P9.29
Serial Comm External Fault Range: 00 - No action 01 - External fault
P9.30
Serial Comm Fault Reset Range: 00 - No action 01 - Fault Reset
P9.31
Default Setting: 00
Serial Comm JOG Command Range: 00 - Stop 01 - Jog
P9.39
Default Setting: 00
Firmware Version Range: #.##
P9.41
Default Setting: 00
Default Setting: #.##
GS Series Number Default Setting: ## Settings:
4–60
01 02 03 04
GS1 GS2 GS3 GS4
GS2 Series AC Drive User Manual
Page 103
Chapter 4: AC Drive Parameters
P9.42
Manufacturer Model Information Default Setting: ## Settings:
1st Ed. Rev. C
12/2006
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26
GS2-20P5 (230V 1 ph/3ph 0.5hp) GS2-21P0 (230V 1 ph/3ph 1hp) GS2-22P0 (230V 1ph/3ph 2hp) GS2-23P0 (230V 1ph/3ph 3hp) GS2-25P0 (230V 3ph 5hp) GS2-27P5 (230V 3ph 7.5hp) Reserved GS2-41P0 (460V 3ph 1hp) GS2-42P0 (460V 3ph 2hp) GS2-43P0 (460V 3ph 3hp) GS2-45P0 (460V 3ph 5hp) GS2-47P0 (460V 3ph 7.5 hp) GS2-4010 (460V 3ph 10hp) GS2-10P2 (115V 1ph 0.25hp) GS2-10P5 (115V 1ph 0.5hp) GS2-11P0 (115V 1ph 1hp) Reserved Reserved Reserved Reserved Reserved GS2-51P0 (575V 3ph 1hp) GS2-52P0 (575V 3ph 2hp) GS2-53P0 (575V 3ph 3hp) GS2-55P0 (575V 3ph 5hp) GS2-57P5 (575V 3ph 7.5hp) GS2-5010 (575V 3ph 10hp)
GS2 Series AC Drive User Manual
4–61
Page 104
Page 105
GS2 MODBUS COMMUNICATIONS
CHAPTER
5 4
In This Chapter... Communication Parameters Summary . . . . . . . . . .5–2 GS2 Parameter Memory Addresses . . . . . . . . . . . .5–4 GS2 Status Addresses . . . . . . . . . . . . . . . . . . . . . . .5–9 Communicating with DirectLogic PLCs . . . . . . . .5–12 Step 1: Choose the Appropriate CPU. . . . . . . . . . . . . . . . . . . . .5–12 Step 2: Make the Connections . . . . . . . . . . . . . . . . . . . . . . . . .5–12 Step 3: Set AC Drive Parameters . . . . . . . . . . . . . . . . . . . . . . . .5–14 Step 4: Configure the DirectLOGIC CPUs . . . . . . . . . . . . . . . . .5–14 DirectLOGIC Modbus Port Configuration . . . . . . . . . . . . . . . . .5–15 DirectLOGIC Modbus Ladder Programming . . . . . . . . . . . . . . .5–16
Communicating with Third-party Devices . . . . . .5–30 Data Format . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5–31 Communication Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5–32
Page 106
Chapter 5: GS2 Modbus Communications
Communication Parameters Summary A summary of the GS2 Communications Parameters is listed below. For a complete listing of the GS2 Parameter, refer to CHAPTER 4.
Communications Parameters GS2 Description Parameter Communication Address P 9.00
Range 01 to 254
01
Transmission Speed
00: 4800 baud 01: 9600 baud 02: 19200 baud 03: 38400 baud
01
Communication Protocol
00: Modbus ASCII mode 7 data bits,no parity,2 stop bits 01: Modbus ASCII mode 7 data bits,even parity,1 stop bit 02: Modbus ASCII mode 7 data bits,odd parity,1 stop bit 03: Modbus RTU mode 8 data bits,no parity,2 stop bits 04: Modbus RTU mode 8 data bits,even parity,1 stop bit 05: Modbus RTU mode 8 data bits,odd parity,1 stop bit
00
P 9.03
Transmission Fault Treatment
00: Display fault and continue operating 01: Display fault and RAMP to stop 02: Display fault and COAST to stop 03: No fault displayed and continue operating
00
P 9.04
Time Out Detection
00: Disable 01: Enable
00
P 9.05
Time Out Duration
0.1 to 60.0 seconds
0.5
P 9.01
P 9.02
쏆 P 9.07 P 9.08 쏆 P 9.11 쏆 P 9.12 쏆 P 9.13 쏆 P 9.14 쏆 P 9.15 쏆 P 9.16 쏆 P 9.17
Parameter Lock Restore to Default
00: All parameters can be set and read 01: All parameters are read-only 99: Restores all parameters to factory defaults
00 00
Block Transfer Parameter 1
P0.00 to P8.01, P9.99
P 9.99
Block Transfer Parameter 2
P0.00 to P8.01, P9.99
P 9.99
Block Transfer Parameter 3
P0.00 to P8.01, P9.99
P 9.99
Block Transfer Parameter 4
P0.00 to P8.01, P9.99
P 9.99
Block Transfer Parameter 5
P0.00 to P8.01, P9.99
P 9.99
Block Transfer Parameter 6
P0.00 to P8.01, P9.99
P 9.99
Block Transfer Parameter 7
P0.00 to P8.01, P9.99
P 9.99
쏆 Parameter can be set during RUN Mode.
5–2
Default
GS2 Series AC Drive User Manual
Page 107
Chapter 5: GS2 Modbus Communications
Communications Parameters (continued) GS2 Parameter 쏆 P 9.18 쏆 P 9.19 쏆 P 9.20 쏆 P 9.21 쏆 P 9.22 쏆 P 9.23 쏆 P 9.24 쏆 P 9.25 쏆 P 9.26
Description
Range
Default
Block Transfer Parameter 8
P0.00 to P8.01, P9.99
P 9.99
Block Transfer Parameter 9
P0.00 to P8.01, P9.99
P 9.99
Block Transfer Parameter 10
P0.00 to P8.01, P9.99
P 9.99
Block Transfer Parameter 11
P0.00 to P8.01, P9.99
P 9.99
Block Transfer Parameter 12
P0.00 to P8.01, P9.99
P 9.99
Block Transfer Parameter 13
P0.00 to P8.01, P9.99
P 9.99
Block Transfer Parameter 14
P0.00 to P8.01, P9.99
P 9.99
Block Transfer Parameter 15
P0.00 to P8.01, P9.99
P 9.99
Serial Comm Speed Reference
0.0 to 400.0 Hz 00: Stop 01: Run 00: Forward 01: Reverse 00: No fault 01: External fault 00: No action 01: Fault Reset 00: Stop 01: Jog #.## 01: GS1 02: GS2 03: GS3 00: GS2-20P5 (230V 1ph/3ph 0.5hp) 01: GS2-21P0 (230V 1ph/3ph 1hp) 02: GS2-22P0 (230V 1ph/3ph 2hp) 03: GS2-23P0 (230V 1ph/3ph 3hp) 04: GS2-25P0 (230V 3ph 5hp) 05: GS2-27P5 (230V 3ph 7.5hp) 06: Reserved 07: GS2-41P0 (460V 3ph 1hp) 08: GS2-42P0 (460V 3ph 2hp) 09: GS2-43P0 (460V 3ph 3hp) 10: GS2-45P0 (460V 3ph 5hp) 11: GS2-47P5 (460V 3ph 7.5hp) 12: GS2-4010 (460V 3ph 10hp) 13: GS2-10P2 (115V 1ph 0.25hp) 14: GS2-10P5 (115V 1ph 0.5hp) 15: GS2-11P0 (115V 1ph 1hp) 16~20: Reserved 21: GS2-51P0 (575V 3ph 1hp) 22: GS2-52P0 (575V 3ph 2hp) 23: GS2-53P0 (575V 3ph 3hp) 24: GS2-55P0 (575V 3ph 5hp) 25: GS2-57P5 (575V 3ph 7.5hp) 26: GS2-5010 (575V 3ph 10hp)
60.0
쏆 P 9.27
Serial Comm RUN Command
쏆 P 9.28
Serial Comm Direction Command
쏆 P 9.29
Serial Comm External Fault
쏆 P 9.30
Serial Comm Fault Reset
쏆 P 9.31
Serial Comm JOG Command
P 9.39
Firmware Version
P 9.41
GS Series Number
P 9.42
Manufacturer Model Information
00 00 00 00 00 #.## ##
##
쏆 Parameter can be set during RUN Mode. 1st Ed. Rev. C
12/2006
GS2 Series AC Drive User Manual
5–3
Page 108
Chapter 5: GS2 Modbus Communications
GS2 Parameter Memory Addresses Parameter Memory Addresses GS2 Parameter
Description
Hexadecimal
Modbus Decimal
Octal
Motor Parameter Addresses P 0.00 P 0.01 P 0.02 P 0.03 P 0.04
Motor Nameplate Voltage
0000
40001
0
Motor Nameplate Amps
0001
40002
1
Motor Base Frequency
0002
40003
2
Motor Base RPM
0003
40004
3
Motor Maximum RPM
0004
40005
4
Ramp Parameter Addresses P 1.00 쏆 P 1.01 쏆 P 1.02 P 1.03 P 1.04 쏆 P 1.05 쏆 P 1.06 P 1.07 P 1.08 P 1.09 P 1.10 P 1.11 P 1.12 P 1.17 P 1.18 P 1.20 P 1.21 P 1.22
Stop Methods
0100
40257
400
Acceleration Time 1
0101
40258
401
Deceleration Time 1
0102
40259
402
Accel S-curve
0103
40260
403
Decel S-curve
0104
40261
404
Acceleration Time 2
0105
40262
405
Deceleration Time 2
0106
40263
406
Select method to use 2nd Accel/Decel
0107
40264
407
Accel 1 to Accel 2 frequency transition
0108
40265
410
Decel 2 to Decel 1frequency transition
0109
40266
411
Skip Frequency 1
010A
40267
412
Skip Frequency 2
010B
40268
413
Skip Frequency 3
010C
40269
414
Skip Frequency Band
0111
40274
421
DC Injection Current Level
0112
40275
422
DC Injection during Start-up
0114
40277
424
DC Injection during Stopping
0115
40278
425
Start-point for DC Injection
0116
40279
426
40513
1000
40514
1001
40515
1002
40517
1004
40518
1005
40519
1006
40520
1007
40521
1010
Volts/Hertz Parameter Addresses Volts/Hertz Settings 0200 P 2.00 Slip Compensation 0201 쏆 P 2.01 Auto-torque Boost 0202 쏆 P 2.02 Mid-point Frequency 0204 P 2.04 Mid-point Voltage 0205 P 2.05 Min. Output Frequency 0206 P 2.06 Min. Output Voltage 0207 P 2.07 PWM Carrier Frequency 0208 P 2.08 쏆 Parameter can be set during RUN Mode.
5–4
GS2 Series AC Drive User Manual
Page 109
Chapter 5: GS2 Modbus Communications
Parameter Memory Addresses (continued) GS2 Parameter
Description
Hexadecimal
Modbus Decimal
Octal
Digital Parameter Addresses P 3.00
Source of Operation Command
0300
40769
1400
P 3.01
Multi-function Input Terminals (DI1 - DI2)
0301
40770
1401
Multi-function Input (DI3)
0302
40771
1402
Multi-function Input (DI4)
0303
40772
1403
Multi-function Input (DI5)
0304
40773
1404
Multi-function Input (DI6)
0305
40774
1405
Multi-Function Output Terminal 1
030B
40780
1413
Multi-Function Output Terminal 2
030C
40781
1414
Desired Frequency
0310
40785
1420
Desired Current
0311
40786
1421
PID Deviation Level
0312
40787
1422
PID Deviation Time
0313
40788
1423
P 3.02 P 3.03 P 3.04 P 3.05 P 3.11 P 3.12 쏆 P 3.16 쏆 P 3.17 쏆 P 3.18 쏆 P 3.19
Analog Parameter Addresses P 4.00 P 4.01 쏆 P 4.02 쏆 P 4.03 P 4.04 P 4.05 쏆 P 4.11 쏆 P 4.12
Source of Frequency Command
0400
41025
2000
Analog Input Offset Polarity
0401
41026
2001
Analog Input Offset
0402
41027
2002
Analog Input Gain
0403
41028
2003
Analog Input Reverse Motion Enable
0404
41029
2004
Loss of ACI Signal (4-20mA)
0405
41030
2005
Analog Output Signal
040B
41036
2013
Analog Output Gain
040C
41037
2014
Presets Parameter Addresses 쏆 P 5.00 쏆 P 5.01 쏆 P 5.02 쏆 P 5.03 쏆 P 5.04 쏆 P 5.05 쏆 P 5.06 쏆 P 5.07
Jog
0500
41281
2400
Multi-Speed 1
0501
41282
2401
Multi-Speed 2
0502
41283
2402
Multi-Speed 3
0503
41284
2403
Multi-Speed 4
0504
41285
2404
Multi-Speed 5
0505
41286
2405
Multi-Speed 6
0506
41287
2406
Multi-Speed 7
0507
41288
2407
쏆 Parameter can be set during RUN Mode.
1st Ed. Rev. C
12/2006
GS2 Series AC Drive User Manual
5–5
Page 110
Chapter 5: GS2 Modbus Communications
Parameter Memory Addresses (continued) GS2 Parameter
Description
Hexadecimal
Modbus Decimal
Octal
Protection Parameter Addresses P 6.00 P 6.01 P 6.02 P 6.03 P 6.04 P 6.05 P 6.06 P 6.07 P 6.08 P 6.09 P 6.10 P 6.11 P 6.12 P 6.13 P 6.14 P 6.15 P 6.16 P 6.31 P 6.32 P 6.33 P 6.34 P 6.35 P 6.36
Electronic Thermal Overload Relay
0600
41537
3000
Auto Restart after Fault
0601
41538
3001
Momentary Power Loss
0602
41539
3002
Reverse Operation Inhibit
0603
41540
3003
Auto Voltage Regulation
0604
41541
3004
Over-VoltageTrip Protection
0605
41542
3005
Auto Adjustable Accel/Decel
0606
41543
3006
Over-Torque Detection Mode
0607
41544
3007
Over-Torque Detection Level
0608
41545
3010
Over-Torque Detection Time
0609
41546
3011
060A
41547
3012
060B
41548
3013
Maximum Allowable Power Loss Time
060C
41549
3014
Base-Block Time for Speed Search
060D
41550
3015
Maximum Speed Search Current Level
060E
41551
3016
Upper Bound of Output Frequency
060F
41552
3017
Lower Bound of Output Frequency
0610
41553
3020
Present Fault Record
061F
41568
3037
Second Most Recent Fault Record
0620
41569
3040
Third Most Recent Fault Record
0621
41570
3041
Fourth Most Recent Fault Record
0622
41571
3042
Fifth Most Recent Fault Record
0623
41572
3043
Sixth Most Recent Fault Record
0624
41573
3044
Over-Current Stall Prevention during Acceleration Over-Current Stall Prevention during Operation
쏆 Parameter can be set during RUN Mode.
5–6
GS2 Series AC Drive User Manual