The text of a manual · part 11 of 19

GS2 Series Drives User Manual, pages 101 to 110

Pages 101 to 110 of 190

The original document is the PDF (5.6 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the AutomationDirect GS2

Page 101

Chapter 4: AC Drive Parameters

P9.20

Block Transfer Parameter 10 Range: P0.00 to P8.01, P9.99

P9.21

Default Setting: P9.99

Block Transfer Parameter 11 Range: P0.00 to P8.01, P9.99

P9.22

Default Setting: P9.99

Block Transfer Parameter 12 Range: P0.00 to P8.01, P9.99

P9.23

Default Setting: P9.99

Block Transfer Parameter 13 Range: P0.00 to P8.01, P9.99

P9.24

Default Setting: P9.99

Block Transfer Parameter 14 Range: P0.00 to P8.01, P9.99

P9.25

Default Setting: P9.99

Block Transfer Parameter 15 Range: P0.00 to P8.01, P9.99

P9.26

Default Setting: P9.99

Serial Comm Speed Reference Range: 0.0 to 400.0 Hz

Default Setting: 60.0

• This parameter is used to set the Frequency Command when the AC drive is controlled by communication interface. Note: In order for this parameter to function, the Source of Frequency Command (P4.00) must be set to 05.

P9.27

Comm RUN Command Range: 00 - Stop 01 - Run

P9.28

Serial Comm Direction Command Range: 00 - Forward 01 - Reverse

1st Ed. Rev. C

Default Setting: 00

12/2006

Default Setting: 00

GS2 Series AC Drive User Manual

4–59

Page 102

Chapter 4: AC Drive Parameters

P9.29

Serial Comm External Fault Range: 00 - No action 01 - External fault

P9.30

Serial Comm Fault Reset Range: 00 - No action 01 - Fault Reset

P9.31

Default Setting: 00

Serial Comm JOG Command Range: 00 - Stop 01 - Jog

P9.39

Default Setting: 00

Firmware Version Range: #.##

P9.41

Default Setting: 00

Default Setting: #.##

GS Series Number Default Setting: ## Settings:

4–60

01 02 03 04

GS1 GS2 GS3 GS4

GS2 Series AC Drive User Manual

Page 103

Chapter 4: AC Drive Parameters

P9.42

Manufacturer Model Information Default Setting: ## Settings:

1st Ed. Rev. C

12/2006

00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26

GS2-20P5 (230V 1 ph/3ph 0.5hp) GS2-21P0 (230V 1 ph/3ph 1hp) GS2-22P0 (230V 1ph/3ph 2hp) GS2-23P0 (230V 1ph/3ph 3hp) GS2-25P0 (230V 3ph 5hp) GS2-27P5 (230V 3ph 7.5hp) Reserved GS2-41P0 (460V 3ph 1hp) GS2-42P0 (460V 3ph 2hp) GS2-43P0 (460V 3ph 3hp) GS2-45P0 (460V 3ph 5hp) GS2-47P0 (460V 3ph 7.5 hp) GS2-4010 (460V 3ph 10hp) GS2-10P2 (115V 1ph 0.25hp) GS2-10P5 (115V 1ph 0.5hp) GS2-11P0 (115V 1ph 1hp) Reserved Reserved Reserved Reserved Reserved GS2-51P0 (575V 3ph 1hp) GS2-52P0 (575V 3ph 2hp) GS2-53P0 (575V 3ph 3hp) GS2-55P0 (575V 3ph 5hp) GS2-57P5 (575V 3ph 7.5hp) GS2-5010 (575V 3ph 10hp)

GS2 Series AC Drive User Manual

4–61

Page 104

This page is a scan with no text; see it in the PDF.

Page 105

GS2 MODBUS COMMUNICATIONS

CHAPTER

5 4

In This Chapter... Communication Parameters Summary . . . . . . . . . .5–2 GS2 Parameter Memory Addresses . . . . . . . . . . . .5–4 GS2 Status Addresses . . . . . . . . . . . . . . . . . . . . . . .5–9 Communicating with DirectLogic PLCs . . . . . . . .5–12 Step 1: Choose the Appropriate CPU. . . . . . . . . . . . . . . . . . . . .5–12 Step 2: Make the Connections . . . . . . . . . . . . . . . . . . . . . . . . .5–12 Step 3: Set AC Drive Parameters . . . . . . . . . . . . . . . . . . . . . . . .5–14 Step 4: Configure the DirectLOGIC CPUs . . . . . . . . . . . . . . . . .5–14 DirectLOGIC Modbus Port Configuration . . . . . . . . . . . . . . . . .5–15 DirectLOGIC Modbus Ladder Programming . . . . . . . . . . . . . . .5–16

Communicating with Third-party Devices . . . . . .5–30 Data Format . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5–31 Communication Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5–32

Page 106

Chapter 5: GS2 Modbus Communications

Communication Parameters Summary A summary of the GS2 Communications Parameters is listed below. For a complete listing of the GS2 Parameter, refer to CHAPTER 4.

Communications Parameters GS2 Description Parameter Communication Address P 9.00

Range 01 to 254

01

Transmission Speed

00: 4800 baud 01: 9600 baud 02: 19200 baud 03: 38400 baud

01

Communication Protocol

00: Modbus ASCII mode 7 data bits,no parity,2 stop bits 01: Modbus ASCII mode 7 data bits,even parity,1 stop bit 02: Modbus ASCII mode 7 data bits,odd parity,1 stop bit 03: Modbus RTU mode 8 data bits,no parity,2 stop bits 04: Modbus RTU mode 8 data bits,even parity,1 stop bit 05: Modbus RTU mode 8 data bits,odd parity,1 stop bit

00

P 9.03

Transmission Fault Treatment

00: Display fault and continue operating 01: Display fault and RAMP to stop 02: Display fault and COAST to stop 03: No fault displayed and continue operating

00

P 9.04

Time Out Detection

00: Disable 01: Enable

00

P 9.05

Time Out Duration

0.1 to 60.0 seconds

0.5

P 9.01

P 9.02

쏆 P 9.07 P 9.08 쏆 P 9.11 쏆 P 9.12 쏆 P 9.13 쏆 P 9.14 쏆 P 9.15 쏆 P 9.16 쏆 P 9.17

Parameter Lock Restore to Default

00: All parameters can be set and read 01: All parameters are read-only 99: Restores all parameters to factory defaults

00 00

Block Transfer Parameter 1

P0.00 to P8.01, P9.99

P 9.99

Block Transfer Parameter 2

P0.00 to P8.01, P9.99

P 9.99

Block Transfer Parameter 3

P0.00 to P8.01, P9.99

P 9.99

Block Transfer Parameter 4

P0.00 to P8.01, P9.99

P 9.99

Block Transfer Parameter 5

P0.00 to P8.01, P9.99

P 9.99

Block Transfer Parameter 6

P0.00 to P8.01, P9.99

P 9.99

Block Transfer Parameter 7

P0.00 to P8.01, P9.99

P 9.99

쏆 Parameter can be set during RUN Mode.

5–2

Default

GS2 Series AC Drive User Manual

Page 107

Chapter 5: GS2 Modbus Communications

Communications Parameters (continued) GS2 Parameter 쏆 P 9.18 쏆 P 9.19 쏆 P 9.20 쏆 P 9.21 쏆 P 9.22 쏆 P 9.23 쏆 P 9.24 쏆 P 9.25 쏆 P 9.26

Description

Range

Default

Block Transfer Parameter 8

P0.00 to P8.01, P9.99

P 9.99

Block Transfer Parameter 9

P0.00 to P8.01, P9.99

P 9.99

Block Transfer Parameter 10

P0.00 to P8.01, P9.99

P 9.99

Block Transfer Parameter 11

P0.00 to P8.01, P9.99

P 9.99

Block Transfer Parameter 12

P0.00 to P8.01, P9.99

P 9.99

Block Transfer Parameter 13

P0.00 to P8.01, P9.99

P 9.99

Block Transfer Parameter 14

P0.00 to P8.01, P9.99

P 9.99

Block Transfer Parameter 15

P0.00 to P8.01, P9.99

P 9.99

Serial Comm Speed Reference

0.0 to 400.0 Hz 00: Stop 01: Run 00: Forward 01: Reverse 00: No fault 01: External fault 00: No action 01: Fault Reset 00: Stop 01: Jog #.## 01: GS1 02: GS2 03: GS3 00: GS2-20P5 (230V 1ph/3ph 0.5hp) 01: GS2-21P0 (230V 1ph/3ph 1hp) 02: GS2-22P0 (230V 1ph/3ph 2hp) 03: GS2-23P0 (230V 1ph/3ph 3hp) 04: GS2-25P0 (230V 3ph 5hp) 05: GS2-27P5 (230V 3ph 7.5hp) 06: Reserved 07: GS2-41P0 (460V 3ph 1hp) 08: GS2-42P0 (460V 3ph 2hp) 09: GS2-43P0 (460V 3ph 3hp) 10: GS2-45P0 (460V 3ph 5hp) 11: GS2-47P5 (460V 3ph 7.5hp) 12: GS2-4010 (460V 3ph 10hp) 13: GS2-10P2 (115V 1ph 0.25hp) 14: GS2-10P5 (115V 1ph 0.5hp) 15: GS2-11P0 (115V 1ph 1hp) 16~20: Reserved 21: GS2-51P0 (575V 3ph 1hp) 22: GS2-52P0 (575V 3ph 2hp) 23: GS2-53P0 (575V 3ph 3hp) 24: GS2-55P0 (575V 3ph 5hp) 25: GS2-57P5 (575V 3ph 7.5hp) 26: GS2-5010 (575V 3ph 10hp)

60.0

쏆 P 9.27

Serial Comm RUN Command

쏆 P 9.28

Serial Comm Direction Command

쏆 P 9.29

Serial Comm External Fault

쏆 P 9.30

Serial Comm Fault Reset

쏆 P 9.31

Serial Comm JOG Command

P 9.39

Firmware Version

P 9.41

GS Series Number

P 9.42

Manufacturer Model Information

00 00 00 00 00 #.## ##

##

쏆 Parameter can be set during RUN Mode. 1st Ed. Rev. C

12/2006

GS2 Series AC Drive User Manual

5–3

Page 108

Chapter 5: GS2 Modbus Communications

GS2 Parameter Memory Addresses Parameter Memory Addresses GS2 Parameter

Description

Hexadecimal

Modbus Decimal

Octal

Motor Parameter Addresses P 0.00 P 0.01 P 0.02 P 0.03 P 0.04

Motor Nameplate Voltage

0000

40001

0

Motor Nameplate Amps

0001

40002

1

Motor Base Frequency

0002

40003

2

Motor Base RPM

0003

40004

3

Motor Maximum RPM

0004

40005

4

Ramp Parameter Addresses P 1.00 쏆 P 1.01 쏆 P 1.02 P 1.03 P 1.04 쏆 P 1.05 쏆 P 1.06 P 1.07 P 1.08 P 1.09 P 1.10 P 1.11 P 1.12 P 1.17 P 1.18 P 1.20 P 1.21 P 1.22

Stop Methods

0100

40257

400

Acceleration Time 1

0101

40258

401

Deceleration Time 1

0102

40259

402

Accel S-curve

0103

40260

403

Decel S-curve

0104

40261

404

Acceleration Time 2

0105

40262

405

Deceleration Time 2

0106

40263

406

Select method to use 2nd Accel/Decel

0107

40264

407

Accel 1 to Accel 2 frequency transition

0108

40265

410

Decel 2 to Decel 1frequency transition

0109

40266

411

Skip Frequency 1

010A

40267

412

Skip Frequency 2

010B

40268

413

Skip Frequency 3

010C

40269

414

Skip Frequency Band

0111

40274

421

DC Injection Current Level

0112

40275

422

DC Injection during Start-up

0114

40277

424

DC Injection during Stopping

0115

40278

425

Start-point for DC Injection

0116

40279

426

40513

1000

40514

1001

40515

1002

40517

1004

40518

1005

40519

1006

40520

1007

40521

1010

Volts/Hertz Parameter Addresses Volts/Hertz Settings 0200 P 2.00 Slip Compensation 0201 쏆 P 2.01 Auto-torque Boost 0202 쏆 P 2.02 Mid-point Frequency 0204 P 2.04 Mid-point Voltage 0205 P 2.05 Min. Output Frequency 0206 P 2.06 Min. Output Voltage 0207 P 2.07 PWM Carrier Frequency 0208 P 2.08 쏆 Parameter can be set during RUN Mode.

5–4

GS2 Series AC Drive User Manual

Page 109

Chapter 5: GS2 Modbus Communications

Parameter Memory Addresses (continued) GS2 Parameter

Description

Hexadecimal

Modbus Decimal

Octal

Digital Parameter Addresses P 3.00

Source of Operation Command

0300

40769

1400

P 3.01

Multi-function Input Terminals (DI1 - DI2)

0301

40770

1401

Multi-function Input (DI3)

0302

40771

1402

Multi-function Input (DI4)

0303

40772

1403

Multi-function Input (DI5)

0304

40773

1404

Multi-function Input (DI6)

0305

40774

1405

Multi-Function Output Terminal 1

030B

40780

1413

Multi-Function Output Terminal 2

030C

40781

1414

Desired Frequency

0310

40785

1420

Desired Current

0311

40786

1421

PID Deviation Level

0312

40787

1422

PID Deviation Time

0313

40788

1423

P 3.02 P 3.03 P 3.04 P 3.05 P 3.11 P 3.12 쏆 P 3.16 쏆 P 3.17 쏆 P 3.18 쏆 P 3.19

Analog Parameter Addresses P 4.00 P 4.01 쏆 P 4.02 쏆 P 4.03 P 4.04 P 4.05 쏆 P 4.11 쏆 P 4.12

Source of Frequency Command

0400

41025

2000

Analog Input Offset Polarity

0401

41026

2001

Analog Input Offset

0402

41027

2002

Analog Input Gain

0403

41028

2003

Analog Input Reverse Motion Enable

0404

41029

2004

Loss of ACI Signal (4-20mA)

0405

41030

2005

Analog Output Signal

040B

41036

2013

Analog Output Gain

040C

41037

2014

Presets Parameter Addresses 쏆 P 5.00 쏆 P 5.01 쏆 P 5.02 쏆 P 5.03 쏆 P 5.04 쏆 P 5.05 쏆 P 5.06 쏆 P 5.07

Jog

0500

41281

2400

Multi-Speed 1

0501

41282

2401

Multi-Speed 2

0502

41283

2402

Multi-Speed 3

0503

41284

2403

Multi-Speed 4

0504

41285

2404

Multi-Speed 5

0505

41286

2405

Multi-Speed 6

0506

41287

2406

Multi-Speed 7

0507

41288

2407

쏆 Parameter can be set during RUN Mode.

1st Ed. Rev. C

12/2006

GS2 Series AC Drive User Manual

5–5

Page 110

Chapter 5: GS2 Modbus Communications

Parameter Memory Addresses (continued) GS2 Parameter

Description

Hexadecimal

Modbus Decimal

Octal

Protection Parameter Addresses P 6.00 P 6.01 P 6.02 P 6.03 P 6.04 P 6.05 P 6.06 P 6.07 P 6.08 P 6.09 P 6.10 P 6.11 P 6.12 P 6.13 P 6.14 P 6.15 P 6.16 P 6.31 P 6.32 P 6.33 P 6.34 P 6.35 P 6.36

Electronic Thermal Overload Relay

0600

41537

3000

Auto Restart after Fault

0601

41538

3001

Momentary Power Loss

0602

41539

3002

Reverse Operation Inhibit

0603

41540

3003

Auto Voltage Regulation

0604

41541

3004

Over-VoltageTrip Protection

0605

41542

3005

Auto Adjustable Accel/Decel

0606

41543

3006

Over-Torque Detection Mode

0607

41544

3007

Over-Torque Detection Level

0608

41545

3010

Over-Torque Detection Time

0609

41546

3011

060A

41547

3012

060B

41548

3013

Maximum Allowable Power Loss Time

060C

41549

3014

Base-Block Time for Speed Search

060D

41550

3015

Maximum Speed Search Current Level

060E

41551

3016

Upper Bound of Output Frequency

060F

41552

3017

Lower Bound of Output Frequency

0610

41553

3020

Present Fault Record

061F

41568

3037

Second Most Recent Fault Record

0620

41569

3040

Third Most Recent Fault Record

0621

41570

3041

Fourth Most Recent Fault Record

0622

41571

3042

Fifth Most Recent Fault Record

0623

41572

3043

Sixth Most Recent Fault Record

0624

41573

3044

Over-Current Stall Prevention during Acceleration Over-Current Stall Prevention during Operation

쏆 Parameter can be set during RUN Mode.

5–6

GS2 Series AC Drive User Manual