For the AutomationDirect GS2

Page 111

Chapter 5: GS2 Modbus Communications

Parameter Memory Addresses (continued) GS2 Parameter

Description

Hexadecimal

Modbus Decimal

Octal

PID Parameter Addresses P 7.00 P 7.01 P 7.02 쏆 P 7.10 쏆 P 7.11 쏆 P 7.12 쏆 P 7.13 쏆 P 7.14 쏆 P 7.15 쏆 P 7.16 쏆 P 7.17 쏆 P 7.20 쏆 P 7.21 쏆 P 7.22 P 7.23 P 7.24 P 7.25 P 7.26 P 7.27

Input Terminal for PID Feedback

0700

41793

3400

PV 100% Value

0701

41794

3401

PID Setpoint Source

0702

41795

3402

Keypad PID Setpoint

070A

41803

3412

PID Multi-setpoint 1

070B

41804

3413

PID Multi-setpoint 2

070C

41805

3414

PID Multi-setpoint 3

070D

41806

3415

PID Multi-setpoint 4

070E

41807

3416

PID Multi-setpoint 5

070F

41808

3417

PID Multi-setpoint 6

0710

41809

3420

PID Multi-setpoint 7

0711

41810

3421

Proportional Control

0714

41813

3424

Integral Control

0715

41814

3425

Derivative Control

0716

41815

3426

Upper Bound for Integral Control

0717

41816

3427

Derivative Filter Time Constant

0718

41817

3430

PID Output Frequency Limit

0719

41818

3431

Feedback Signal Detection Time

071A

41819

3432

PID Feedback Loss

071B

41820

3433

Display Parameter Addresses 쏆 P 8.00 쏆 P 8.01

User Defined Display Function

0800

42049

4000

Frequency Scale Factor

0801

42050

4001

쏆 Parameter can be set during RUN Mode.

1st Ed. Rev. C

12/2006

GS2 Series AC Drive User Manual

5–7

Page 112

Chapter 5: GS2 Modbus Communications

Parameter Memory Addresses (continued) GS2 Parameter

Description

Hexadecimal

Modbus Decimal

Octal

Communications Parameter Addresses P 9.00 P 9.01 P 9.02 P 9.03 P 9.04 P 9.05 쏆 P 9.07 P 9.08 쏆 P 9.11 쏆 P 9.12 쏆 P 9.13 쏆 P 9.14 쏆 P 9.15 쏆 P 9.16 쏆 P 9.17 쏆 P 9.18 쏆 P 9.19 쏆 P 9.20 쏆 P 9.21 쏆 P 9.22 쏆 P 9.23 쏆 P 9.24 쏆 P 9.25 쏆 P 9.26 쏆 P 9.27 쏆 P 9.28 쏆 P 9.29 쏆 P 9.30 쏆 P 9.31 P 9.41 P 9.42

Communication Address

0900

42305

4400

Transmission Speed

0901

42306

4401

Communication Protocol

0902

42307

4402

Transmission Fault Treatment

0903

42308

4403

Time Out Detection

0904

42309

4404

Time Out Duration

0905

42310

4405

Parameter Lock

0907

42312

4407

Restore to Default

0908

42313

4410

Block Transfer Parameter 1

090B

42316

4413

Block Transfer Parameter 2

090C

42317

4414

Block Transfer Parameter 3

090D

42318

4415

Block Transfer Parameter 4

090E

42319

4416

Block Transfer Parameter 5

090F

42320

4417

Block Transfer Parameter 6

0910

42321

4420

Block Transfer Parameter 7

0911

42322

4421

Block Transfer Parameter 8

0912

42323

4422

Block Transfer Parameter 9

0913

42324

4423

Block Transfer Parameter 10

0914

42325

4424

Block Transfer Parameter 11

0915

42326

4425

Block Transfer Parameter 12

0916

42327

4426

Block Transfer Parameter 13

0917

42328

4427

Block Transfer Parameter 14

0918

42329

4430

Block Transfer Parameter 15

0919

42330

4431

Serial Comm Speed Reference

091A

42331

4432

Serial Comm RUN Command

091B

42332

4433

Serial Comm Direction Command

091C

42333

4434

Serial Comm External Fault

091D

42334

4435

Serial Comm Fault Reset

091E

42335

4436

Serial Comm JOG Command

091F

42336

4437

GS Series Number

0929

42346

4451

Manufacturer Model Information

092A

42347

4452

쏆 Parameter can be set during RUN Mode.

5–8

GS2 Series AC Drive User Manual

Page 113

Chapter 5: GS2 Modbus Communications

GS2 Status Addresses The GS2 Series AC drive has status memory addresses that are used to monitor the AC drive. The status addresses and value definitions are listed below.

Status Addresses (Read Only) GS2 Status Addresses Description Status Monitor 1 Status Monitor 2 Frequency Command F Output Frequency H Output Current A DC Bus Voltage d Output Voltage U Motor RPM Scale Frequency (Low Word) Scale Frequency (High Word) Power Factor Angle % Load Firmware Version

Hexadecimal

Modbus Decimal

Octal

2100

48449

20400

2101

48450

20401

2102

48451

20402

2103

48452

20403

2104

48453

20404

2105

48454

20405

2106

48455

20406

2107

48456

20407

2108

48457

20410

2109

48458

20411

210A

48459

20412

210B

48460

20413

2110

48465

20420

Status Monitor 1 h2100

Error Codes: 00: No fault occurred 01: Over-current(oc) 02: Over-voltage(ov) 03: Overheat (oH) 04: Overload (oL) 05: Overload 1 (oL1) 06: Overload 2 (oL2) 07: External Fault (EF) 08: CPU failure 1 (cF1) 09: CPU failure 2 (cF2) 10: CPU failure 3 (cF3)

1st Ed. Rev. C

12/2006

11: Hardware Protection Failure (HPF) 12: Over-current during accel (ocA) 13: Over-current during decel (ocd) 14: Over-current during steady state (ocn) 15: Ground fault or fuse failure (GFF) 16: Low voltage (Lv) 17: Input power 3-phase loss (PHL) 18: External Base-Block (bb) 19: Auto adjust accel/decel failure (cFA) 20: Software protection code (codE)

GS2 Series AC Drive User Manual

5–9

Page 114

Chapter 5: GS2 Modbus Communications

Status Monitor 2 h2101 GS2 Memory Data (binary)

0

0

0

0

0

0

0

0

1

0

0

0

1

0

10

20

40

81

38

8 76

16

32

1

0

0

2

2101

4

0

8

1

16

2

32

3

64

4

8

5

6

6

12

7

25

8

2

9

51

10

24

11

48

12

96

13

92

14

4

GS2 Memory Address (hexadecimal) 15

Bits

Bit Values (decimal)

Status Monitor 2 - Memory Address h2101 Address Bit(s) Value AC Drive Status Bit(s) Binary (Decimal) 00 (0)

Drive operation stopped (STOP)

01 (1)

Run to Stop transition

10 (2)

Standby

11 (3)

Drive operation running (RUN)

1 (4)

JOG active

00 (0)

Rotational direction forward (FWD)

01 (8)

REV to FWD transition

10 (16)

FWD to REV transition

11 (24)

Rotational direction reverse (REV)

5

1 (32)

Source of frequency determined by serial comm interface (P4.00 = 5)

6

1 (64)

Source of frequency determined by AI terminal (P4.00 = 2, 3, or 4)

7

1 (128)

Source of operation determined by serial comm interface (P3.00 = 3 or 4)

8

1 (256)

Parameters have been locked (9-07 = 1)

9 to 15

N/A

Reserved

0 and 1

2

3 and 4

Frequency Command F (XXX.X)

h2102

Status location for the frequency setting of the AC drive.

Output Frequency H (XXX.X)

h2103

Status location for the actual operating frequency present at the T1, T2, and T3 terminal.

Output Current A h2104

Status location for the output current present at the T1, T2, and T3 terminals.

DC-BUS Voltage d (XXX.X) Status location for the DC Bus Voltage.

5–10

GS2 Series AC Drive User Manual h2105

Page 115

Chapter 5: GS2 Modbus Communications

Output Voltage U (XXX.X)

h2106

Status location for the output voltage present at the T1, T2, and T3 terminals.

Motor RPM h2107

Status location for the present estimated speed of the motor.

Scale Frequency (Low word)

h2108

Status location for result of output frequency x P 8.01 (low word).

Scale Frequency (High word)

h2109

Status location for result of output frequency x P 8.01 (high word).

Power Factor Angle h210A

Status location for the power factor angle.

% Load h210B

Status location for the amount of load on the AC drive. (Output Current ÷ Drive Rated Current) x 100.

Firmware Version h2110

Status location for the firmware version of the AC drive.

1st Ed. Rev. C

12/2006

GS2 Series AC Drive User Manual

5–11

Page 116

Chapter 5: GS2 Modbus Communications

Communicating with DirectLOGIC PLCs The following steps explain how to connect to and communicate with the GS2 Series AC drives using DirectLOGIC PLCs.

Step 1: Choose the Appropriate CPU. The GS2 Series AC drives will communicate with the following DirectLOGIC CPUs using Modbus communications: • DL05 • DL260

• DL06 • DL350

• DL250(-1) • DL450

Step 2: Make the Connections First you must decide what type of interface will work best for your application. The GS2 Comm Port can accomodate an RS-232C or an RS-485 connection. RS-232C An RS-232C connection is somewhat limited. The maximum RS-232C network cable length is 15 meters (50 feet). In addition, using the RS-232C interface will allow you to connect an AC drive to only one PLC. For an RS-232C connection, set the GS2 DIP switches SW2 and SW3 to RS232. RJ-12 (6P4C) Serial Comm Port

6

1

RS-232C Interface 2: GND 3: RXD 4: TXD 5: +5V

RS485

SW3

Switches SW2 and SW3 must be set to RS232 for an RS-232C connection.

SW2

RS232

Use the following wiring diagrams to connect your DirectLOGIC PLC to a GS2 Series AC drive with an RS-232C interface: DL05: RS-232C Connection Wiring DL05 PORT 2

1 0V

2 GND

3 RXD

4 TXD

4 TXD

3 RXD

GS2 Comm Port

DL350/DL450: RS-232C Connection Wiring DL350 PORT 2 DL450 PORT 1

GS2 Comm Port

1

DL06/DL250/DL260: RS-232C Connection Wiring PORT 2 1

6

2 TXD

3 RXD

3 RXD

4 TXD

5 CTS

2 GND

4 RTS 15

5–12

GS2 Comm Port

7 GND

GS2 Series AC Drive User Manual

2 TXD

3 RXD

3 RXD

4 TXD

5 CTS

2 GND

4 RTS 7 GND 25

Page 117

Chapter 5: GS2 Modbus Communications

RS-232C to RS-485 Conversion An RS-485 network cable can span up to 1000 meters (4000 feet). However, most DirectLOGIC PLCs require an FA-ISOCON (RS-232C to RS-422/485 network adapter) in order to make this type of connection. For an RS-485 connection, set the GS2 DIP switches SW2 and SW3 to RS485. RJ-12 (6P4C) Serial Comm Port

6

1

RS-485 Interface 2: GND 3: SG4: SG+ 5: +5V

RS485

SW3

SW2

Switches SW2 and SW3 must be set to RS485 for an RS-485 connection.

RS232

Use the following wiring diagrams to connect your DirectLOGIC PLC to a GS2 Series AC drive with an RS-485 interface: Note: If an FA-ISOCON module is used in your connection, set the module dipswitches S21 = ON; S22 - S27 = OFF; TERMINATE, BIAS, and DPX = ON. Refer to FA-ISOCON manual for more detailed information. DL05: RS-485 Connection Wiring DL05 PORT 2

1 0V 2 5V

6 COM A 5 +5VDC

3 RXD

4 TXD

4 TXD

3 RXD

5 RTS

2 CTS

6 0V

1 COM A

C

+V COM A

A D

No connection (for DL05)

GS2 Comm Port

TXD+ TXD-

4 SG+

RXD-

3 SG-

RXD+

2 COM

COM B

FA-ISOCON

DL250: RS-485 Connection Wiring C

DL250 PORT 2 1

6

2 TXD

3 RXD

3 RXD

4 TXD

A

D

24VDC + 24VDC -

GS2 Comm Port

TXD+ TXD-

5 CTS

15

+V COM A

4 SG+

RXD-

4 RTS

2 CTS

7 GND

6 GND

3 SG-

RXD+

2 COM

COM B

FA-ISOCON

DL350/DL450: RS-485 Connection Wiring DL350 PORT 2 DL450 PORT 1

C

1

2 TXD

3 RXD

3 RXD

4 TXD

5 CTS

25

1st Ed. Rev. C

12/2006

A

D

+V

24VDC +

COM A

24VDC -

TXDRXD-

4 RTS

2 CTS

7 GND

6 GND

GS2 Comm Port

TXD+

RXD+ COM B

4 SG+ 3 SG2 COM

FA-ISOCON

GS2 Series AC Drive User Manual

5–13

Page 118

Chapter 5: GS2 Modbus Communications

RS-485 DL06/DL260: RS-485 Connection Wiring

120⏲ Termination Resistor at both ends of network

TXD+ / RXD+

4 SG +

TXD– / RXD–

3 SG 2 GND Connect shield to signal ground

Signal GND RXD– 1

6

GS2 Comm Port

11 RTS+

0V TXD+ RXD+

RTS– CTS+

10 15

CTS–

DL06/DL260 CPU Port 2

TXD–

5

Note: The Termination Resistor is necessary only on large runs.

Step 3: Set AC Drive Parameters The following parameters need to be set as shown in order to communicate properly. P 3.00: 03 or 04 – Operation Determined by RS-232C/RS-485 interface. Keypad STOP is enabled (03) or disabled (04). P 4.00: 05 – Frequency determined by RS-232/RS-485 communication interface P 9.00: xx – Communication address 1-254 (unique for each device, see P 9.00) P 9.01: 01 – 9600 baud data transmission speed P 9.02: 05 – Modbus RTU mode <8 data bits, odd parity, 1 stop bit> Note: The previous list of parameter settings is the minimum required to communicate with a DirectLOGIC PLC. There may be other parameters that need to be set to meet the needs of your application.

Step 4: Configure the DirectLOGIC CPUs The DirectLOGIC CPUs must be configured to communicate with the GS2 Series AC drives. This set up includes setting up the communication port and adding instructions to your logic program. The set up for all of the DirectLOGIC CPUs is very similar. However, there may be some subtle differences between CPUs. Refer to the appropriate CPU User Manual for the specifics on your DirectLOGIC CPU. Note: For instructions on Modbus Configuration for your specific CPU, refer to the appropriate CPU User Manual.

5–14

GS2 Series AC Drive User Manual

Page 119

Chapter 5: GS2 Modbus Communications

DirectLOGIC Modbus Port Configuration The following configuration example is specific to the DL250(-1) CPU. Refer to the appropriate CPU User Manual for the specifics on your DirectLOGIC CPU. • In DirectSOFT, choose the PLC menu, then Setup, then “Secondary Comm Port”. • From the Port list box, choose “Port 2”. • For the protocol, select “Modbus”.

• In the Timeout list box, select “800 ms”. • Response Delay Time should be “0 ms”. • The Station Number should be set to “1” to make the DL250(-1) CPU a Modbus master. Note: The DL250(-1) network instructions used in Master mode will access only slaves 1 to 90. Each slave must have a unique number. • The Baud Rate should be set at “9600”. • In the Stop Bits list box, choose “1”. • In the Parity list box, choose “Odd”.

1st Ed. Rev. C

12/2006

GS2 Series AC Drive User Manual

5–15

Page 120

Chapter 5: GS2 Modbus Communications

DirectLOGIC Modbus Ladder Programming The set up for all of the DirectLOGIC CPUs is very similar. However, there may be some subtle differences between CPUs. Refer to the appropriate CPU User Manual for the specifics on your DirectLOGIC CPU. The following ladder program shows some examples of how to control the GS2 AC drive through Modbus RTU. The drive should be setup and tested for communications before it is connected to a load. WARNING: A drive should never be connected to a load until any applicable communication programs have been proven. Note: This program is for illustration purposes only, and is not intended for a true application.

In many drive applications, electromagnetic interference can sometimes cause frequent, short duration communication errors. Unless the application environment is perfect, an occasional communication error will occur. In order to distinguish between these non-fatal transients and a genuine communication failure, you may want to use the instructions as shown in Rungs 1 through 4. Rung 1 monitors the number of times that the PLC attempts to communicate with the AC drive. When the PLC’s communication attempts are successful, SP116 will count up, and SP117 will not count. Once the count reaches 9999, the counter will reset and resume counting. Note: SP116 and SP117 are special relays in the DirectLOGIC CPUs that monitor the PLC’s communications. SP116 is on when Port 2 is communicating with another device. SP117 is on when Port 2 has encountered a communication error. This rung counts every time Port 2 is busy communicating. DL250-1/260 Comm SP116 1 Comm Transaction Count CT0

(Continued next page)

5–16

GS2 Series AC Drive User Manual

CNT Comm Transaction Count CT0 K9999