Page 21
Chapter 2: Installation and Wiring
Dimensions (continued) GS2-23P0, GS2-25P0, GS2-27P5, GS2-45P0, GS2-47P5, GS2-4010, GS2-55P0, GS2-57P5, GS2-5010
Units: mm [inches]
1st Ed. Rev. C
12/2006
GS2 Series AC Drive User Manual
2–5
Page 22
Chapter 2: Installation and Wiring
GS2 Circuit Connections DANGER! HAZARDOUS VOLTAGE! Before making any connection to the AC drive, disconnect all power to the AC drive, and wait five minutes for DC bus capacitors to discharge. Warning: Any electrical or mechanical modification to this equipment without prior written consent of AutomationDirect.com, Inc. will void all warranties, may result in a safety hazard, and may void the UL listing. WARNING: Do not connect the AC input power to the T1, T2, and T3 output terminals. This will damage the AC drive WARNING: Tighten all screws to the proper torque rating. See “Main Circuit Wiring” later in this chapter.
Wiring Notes: PLEASE READ PRIOR TO INSTALLATION. 1. During installation, follow all local electrical, construction, and safety codes for the country in which the AC drive is to be installed. 2. Make sure the appropriate circuit protective devices (circuit breaker or fuses) are connected between the power supply and AC drive. 3. Make sure that the leads are connected correctly and the AC drive is properly grounded. (Ground resistance should not exceed 0.1⏲.) 4. Use ground leads that comply with AWG/MCM standards and keep them as short as possible. 5. Do not use a power circuit contactor or disconnect switch for run/stop control of the AC drive and motor. This will reduce the operating life cycle of the AC drive. Cycling a power circuit switching device while the AC drive is in run mode should be done only in emergency situations. 6. Multiple GS2 units can be installed in one location. All of the units should be grounded directly to a common ground terminal, or connected in parallel, as shown in the figure below. Make sure there are no ground loops.
Correct
Incorrect
Forward running (CCW)
7. When the AC drive output terminals T1, T2, and T3 are connected to the motor terminals T1, T2, and T3, respectively, the motor will rotate counterclockwise (as viewed from the shaft end of the motor) when a forward operation command is received. To reverse the direction of motor rotation, switch the connections of any of the two motor leads. 8. Make sure that the power source is capable of supplying the correct voltage and required current to the AC drive.
2–6
GS2 Series AC Drive User Manual
Page 23
Chapter 2: Installation and Wiring
9. Do not attach or remove wiring when power is applied to the AC drive. 10. Do not inspect components unless inside "POWER" lamp is turned off. 11. Do not monitor the signals on the circuit board while the AC drive is in operation. 12. For the 115V single-phase rated AC drives, AC power must be connected to input terminals L1 and L2. For the 230V single-phase rated AC drives, AC power can be connected to any two of the three input terminals L1, L2, and L3. Note: This AC drive is not intended for use with single-phase motors. 13. Route the power and control wires separately, or at 90 degree angle to each other. 14. If a filter is required for reducing EMI (Electro-Magnetic Interference), install it as close as possible to the AC drive. EMI can also be reduced by lowering the Carrier Frequency.
15. If the AC drive is installed in a place where a load reactor is needed, install the filter close to the T1, T2, and T3 side of AC drive. Do not use a Capacitor, L-C Filter (Inductance-Capacitance), or R-C Filter (Resistance-Capacitance), unless approved by AutomationDirect. 16. When using a GFCI (Ground Fault Circuit Interrupt), select current sensor with sensitivity of 200 mA, and not less than 0.1-second detection to avoid nuisance tripping. Motor Operation Precautions 1. If the AC drive is used to operate a standard 3-phase induction motor, the energy loss is greater than if using an inverter duty motor. 2. Avoid running a standard induction motor at low speed, which may cause the motor temperature to exceed the motor rating due to limited airflow produced by the motor's fan. 3. When the standard motor operates at low speed, the output load must be decreased. 4. If 100% output torque is desired at low speed, it may be necessary to use a special "inverter-duty" rated motor. Short Circuit Withstand Current Suitable for use on a circuit capable of delivering not more than 5,000 rms symmetrical Amperes. The maximum voltage is 120, 240, 480, and 600V for all 115, 230, 460, and 575V models, respectively. (An optional line reactor can be installed in the incoming power circuit to reduce the available short circuit current.) Applicable Codes All GS2 Series AC drives are Underwriters Laboratories, Inc. (UL) and Canadian Underwriters Laboratories (cUL) listed, and therefore comply with the requirements of the National Electrical Code (NEC) and the Canadian Electrical Code (CEC). Installation intended to meet the UL and cUL requirements must follow the instructions provided in "Wiring Notes" as a minimum standard. Follow all local codes that exceed UL and cUL requirements. Refer to the technical data label affixed to the AC drive and the motor nameplate for electrical data. The "Fuses and Fuse Kits" section in APPENDIX A, lists the recommended fuse part number for each GS2 Series part number. These fuses (or equivalent) must be used on all installations where compliance with U.L. standards is required. 1st Ed. Rev. C
12/2006
GS2 Series AC Drive User Manual
2–7
Page 24
Chapter 2: Installation and Wiring
Main Circuit Wiring Main Circuit Terminals Terminal L1, L2, L3 T1, T2, T3
Description
B1, B2
Dynamic Braking Resistor (optional)
Input Power AC Drive Output
Ground
Output Power Connections
T1 T2 T3 B1 B2
3-phase Input Power Connections L1 L2 L3
1-phase Input Power Connections* L1 L2
1-phase* Input Power 3-phase Input Power 230V Class 200-240V ± 10%; 50/60 Hz ± 5% 460V Class 380-480V ± 10%; 50/60 Hz ± 5% 575V Class 500-600V -15/+10%; 50/60 Hz ± 5%
2–8
GS2 Series AC Drive User Manual
115V Class 230V Class
100-120V ± 10%; 50/60Hz ± 5% 200-240V ± 10%; 50/60Hz ± 5%
* Only models GS2-10P2, GS2-10P5, GS2-11P0, GS2-20P5, GS2-21P0, GS2-22P0, and GS2-23P0 are rated for 1-phase input power
Page 25
Chapter 2: Installation and Wiring
Main Circuit Wiring (continued) Main Circuit Wiring Specifications AC Drive Model
Current Input/Output (A)
GS2-10P2 (1-phase) GS2-10P5 (1-phase) GS2-11P0 (1-phase) GS2-20P5 (1-phase) GS2-20P5 (3-phase) GS2-21P0 (1-phase) GS2-21P0 (3-phase) GS2-22P0 (1-phase) GS2-22P0 (3-phase) GS2-23P0 (1-phase) GS2-23P0 (3-phase) GS2-25P0 GS2-27P5 GS2-41P0 GS2-42P0 GS2-43P0 GS2-45P0 GS2-47P5 GS2-4010 GS2-51P0 GS2-52P0 GS2-53P0 GS2-55P0 GS2-57P5 GS2-5010
6 / 1.6 9 / 2.5 16 / 4.2
Wire Gauge (AWG)
Terminal Screw Torque (in·lbf)
12-14 12
6.3 / 2.5 3.2 / 2.5 11.5 / 5.0
12-14
12
6.3 / 5.0 15.7 / 7.0
12
9 / 7.0
12-14
27 / 10
8
12.5 / 10
8-12
19.6 / 17
8-10
28 / 25
8
13
4.2 / 3.0 5.7 / 4.0
12-14
12
6.0 / 5.0 8.5 / 8.2
8-14
14 / 13
8-12
23 / 18
8-10
13
2.4 / 1.7 4.2 / 3.0
12-14
12
5.9 / 4.2 7.0 / 6.6 10.5 / 9.9 12.9 / 12.2
8-14
13
8-12
NOTE: Use 75°C (or higher) copper wire only.
1st Ed. Rev. C
12/2006
GS2 Series AC Drive User Manual
2–9
Page 26
Chapter 2: Installation and Wiring
Control Terminal Wiring
Control Circuit Terminals Terminal Symbol Description Remarks Relay Output 1 Normally Open R1O Relay Output 1 Normally Closed R1C Relay Output 1 Common R1 120 VAC / 24 VDC @ 5A Relay Output 2 Normally Open 230 VAC @ 2.5A R2O Relay Output 2 Normally Closed R2C Relay Output 2 Common R2 Digital Input 1 DI1 Digital Input 2 DI2 Input Voltage: Internally Supplied (see WARNING below) Digital Input 3 DI3 Input Voltage Range: 4-12V Digital Input 4 Minimum ON Current: 22 mA max DI4 Maximum OFF Current: 1.1 mA Digital Input 5 DI5 also see “Basic Wiring Diagram” on next page. Digital Input 6 DI6 Digital Common DCM AI
Analog Input
0 to +10 V Input 0 to 20 mA Input, or 4 to 20 mA Input
+10V AO ACM
Internal Power Supply
+10 VDC (10 mA maximum load)
Analog Output
0 to +10V Output (2mA maximum load)
Analog Common
Warning: Do NOT connect external voltage sources to the Digital Inputs. Permanent damage may result. Note: Use twisted-shielded, twisted-pair, or shielded-lead wires for the control signal wiring. It is recommended to run all signal wiring in a separate steel conduit. The shield wire should be connected only at the AC drive. Do not connect shield wire on both ends.
2–10
GS2 Series AC Drive User Manual
Page 27
Chapter 2: Installation and Wiring
Basic Wiring Diagram Note: Users must connect wiring according to the circuit diagram shown below. Power Source* 100-120V ±10% 200-240V ±10% 380-480V ±10% 500-600V -15%;+10%
L1
(50,60Hz ±5%)
L3
L2
AC Motor T1
GS2-xxxx T2
IM
T3
* Use terminals L1, L2 for 115V 1-phase models; use any two of L1, L2, L3 for 230V 1-phase models. Grounding resistance less than 0.1⏲
B1
Braking resistor (optional)
B2 R1 R1C
Multi-function output contacts 120VAC/24VDC @5A 230VAC @2.5A
R1O
앲Inverter Running
DI1 앲Forward/Stop DI2 앲Reverse/Stop
R2 DI3
앲External Fault (N.O.)
Multi-function output contacts 120VAC/24VDC @5A 230VAC @2.5A
R2C R2O
DI4
앲Inverter Fault
앲Multi-Speed 1 DI5 Analog AO output 0 to +10 VDC 2mA max
앲Multi-Speed 2 DI6 앲Multi-Speed 3
Potentiometer (3-5 k⏲) (may be required for some meters) + Voltmeter -
ACM 앲Output Frequency
DCM
Analog voltage 0-10 VDC Potentiometer 3-5 k⏲ Analog current 0-20 mA 4-20 mA
RJ-12 (6P4C) +10V (10mA max) AI
앲앲
6
RJ-12 Serial Comm Port Interface (see note below)
1
ACM
RS-485 2: GND 3: SG4: SG+ 5: +5V
RS-232 2: GND 3: RXD 4: TXD 5: +5V
앲Factory default setting 앲앲Factory default source of frequency command is via the keypad potentiometer Main circuit (power) terminals
Control circuit terminal
Shielded leads
WARNING: Do not plug a modem or telephone into the GS2 RJ-12 Serial Comm Port, or permanent damage may result. Terminals 2 and 5 should not be used as a power source for your communication connection. 1st Ed. Rev. C
12/2006
GS2 Series AC Drive User Manual
2–11
Page 28
Chapter 2: Installation and Wiring Supply External Accessories ��� Power Please follow the specific power supply requirements Refer to Appendix A for information regarding external accessories.
��� From power supply Disconnect switch
��� ��� shown in CHAPTER 1
��� Fuses Input fuses protect the AC drive from excessive input current due to line surges, short circuits, and ground faults. They are recommended for all installations and may be required for UL-listed installations.
��� Contactor (Optional) Do not use a contactor or disconnect switch for run/stop control of the AC drive and motor. This will reduce the operating life cycle of the AC drive. Cycling a power circuit switching device while the AC drive is in run mode should be done only in emergency situations.
��� AC Line Reactor (Optional)
���
Input line reactors protect the AC drive from transient overvoltage conditions typically caused by utility capacitor switching. Input line reactors also reduce the harmonics associated with AC drives, and are recommended for all installations.
��� L1
L2
L3 GND
��� EMI filter (Optional)
B1
���
GS2-xxxx AC Drive
B2 GND
T1
T2
T3
Input EMI filters reduce electromagnetic interference or noise on the input side of the AC drive. They are required for CE compliance and recommended for installations prone to or sensitive to electromagnetic interference.
��� Braking Resistors (Optional) Dynamic braking allows the AC drive to produce additional braking (stopping) torque. AC drives can typically produce between 15% & 20% braking torque without the addition of any external components. The addition of optional braking may be required for applications that require rapid deceleration or high inertia loads.
��� AC Line Reactor (Optional)
���
Motor
Output line (load) reactors protect the motor insulation against AC drive short circuits and IGBT reflective wave damage, and also allow the motor to run cooler by smoothing the motor current waveform. They are recommended for operating “non-inverter-duty” motors, and for any motors when the length of wiring between the AC drive and motor exceeds 75 feet.
Note: Please refer to Appendix A for specifications on GS2 AC Drive Accessories.
2–12
GS2 Series AC Drive User Manual
Page 29
KEYPAD OPERATION AND QUICKSTART
CHAPTER
3
In This Chapter... The GS2 Digital Keypad . . . . . . . . . . . . . . . . . . . . .3–2 LED Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3–2 LED Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3–2 Function Keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3–3 Displaying the Status of the GS2 AC Drive . . . . . . . . . . . . . . . . .3–4 Programming the GS2 AC Drive . . . . . . . . . . . . . . . . . . . . . . . . .3–5
GS2 Quickstart . . . . . . . . . . . . . . . . . . . . . . . . . . . .3–6 Example 1: Constant torque (e.g. conveyors, compressors, etc.) .3–6 Example 2: Variable torque (e.g. fans, centrifugal pumps, etc.) .3–11
Page 30
Chapter 3: Keypad Operation and Quickstart
The GS2 Digital Keypad The digital keypad includes a 4-digit LED display, 14 LED Indicators, 8 function keys, and a potentiometer. The diagram below shows all of the features of the digital keypad and an overview of their functions. LED Display
LED Indicators Up/Down Keys Program Key
Enter Key
Display Key
Potentiometer
Fwd/Rev Key Stop/Reset Key Run Key
LED Display The LED display shows the AC drive operation values and parameter settings.
LED Indicators RUN RUN
The RUN LED indicates the AC drive isFWD in Run Mode. The RUN LED blinks when the drive is decelerating to stop.FWD
STOP STOP
The STOP LED indicates the AC drive REV is not in Run Mode. The STOP LED blinks REV when the drive is in Run Mode, but has zero speed reference. V/Hz ANLG The RAMP FWD LED indicates theDIGT AC drive is running the motor in the forward V/Hz DIGT ANLG RAMP direction. FWD PROT DISP PID COMM PROT DISP PID COMM The REV LED indicates the AC drive is running the motor in the reverse REV direction. FWD The MTR LED indicates the AC drive is in Program Mode and is displaying the V/Hz DIGT ANLG RAMP Motor Parameters group (PREV 0.xx). FWD The PROT RAMP LEDPID indicates the is in Program Mode and is displaying the DISPAC driveCOMM V/Hz DIGT ANLG REV Ramp Parameters group (P 1.xx). FWD
MTR MTR FW D FWD RUN PSET PSET REV REV STOP
N D D P
RUN DIGT DIGT STOP DISP DISP MTR
R
PSET RAMP
PROT V/Hz FWD
The PID V/Hz LED indicates the AC drive is in Program Mode and displays the DISP COMM DIGT ANLG REV Volts/Hertz Parameters group (P 2.xx).
T P
PROT V/Hz
PID DIGT REV
The DISP DIGT LED COMM indicates the AC drive is in Program Mode and displays the ANLG Digital Parameters group (P 3.xx).
T z
PID DIGT
DISP ANLG
The COMM ANLG LED indicates the AC drive is in Program Mode and displays the Analog Parameters group (P 4.xx).
D
DISP
COMM zz
3–2
ANLG ANLG MTR COMM COMM PSET RAMP
GS2 Series AC Drive User Manual