Page 11
Chapter 1: Getting Started
GS2 AC Drive Introduction Purpose of AC Drives AC drives are generally known by many different names: Adjustable Frequency Drives (AFD), Variable Frequency Drives (VFD), and Inverters. Drives are used primarily to vary the speed of three phase AC induction motors, and they also provide non-emergency start and stop control, acceleration and deceleration, and overload protection. By gradually accelerating the motor, drives can reduce the amount of motor startup inrush current. AC drives function by converting incoming AC power to DC, which is then synthesized back into three phase output power. The voltage and frequency of this synthesized output power is directly varied by the drive, where the frequency determines the speed of the three phase AC induction motor.
Drive Package Contents After receiving the AC motor drive, please check for the following: • Make sure that the package includes an AC drive, the GS2 Series AC Drive User Manual, and the GS2 Series AC Drive Quick Reference. • Inspect the unit to insure it was not damaged during shipment. • Make sure that the part number indicated on the nameplate corresponds with the part number of your order.
Model Explanation: GS2- 4 7P5 Applicable Motor Capacity 0P2: 0.25HP 1P0: 1.0HP 3P0: 3.0HP 7P5: 7.5HP
0P5: 0.5HP 2P0: 2.0HP 5P0: 5.0HP 010: 10HP
Input Voltage 1: 100-120VAC 2: 200-240VAC 4: 380-480VAC 5: 500-600VAC
Series Name
Nameplate Information: MODEL: GS2-47P5
AC Drive Model Input Specification Output Specification Output Frequency Range
INPUT: 380-480V 50/60Hz 3ph OUTPUT: 0-480V 7.5hp 13Amps 9.9kVA FREQUENCY RANGE: 0.1- 400Hz
C
U US ®L
LISTED 19XK IND. CONT. EQ
*
Barcode Serial Number
GS2-47P5+T101001
* 575V models are NOT CE compliant. 1st Ed. Rev. C
12/2006
Automationdirect.com, Inc.
GS2 Series AC Drive User Manual
1–3
Page 12
Chapter 1: Getting Started
External Parts and Labels:
���
���
���
���
���
��� 햲 Nameplate Label
���
햳 Mounting Screw Holes 햴 Ventilation Slots 햵 Upper Cover 햶 Digital Keypad 햷 Lower Cover 햸 DIP Switches 햹 Input Power Terminals 햺 Control Input/Output Terminals 햻 Output Power Terminals
��� 햻
1–4
GS2 Series AC Drive User Manual
���
Page 13
Chapter 1: Getting Started
GS2 AC Drive Specifications 115V Class Model Name: GS2-xxx
10P2
10P5
11P0
HP kW Output Rated Output Current (A) Rating Maximum Output Voltage Rated Output Frequency Rated Voltage/Frequency Rated Input Current (A) Input Rating Voltage/Frequency Tolerance Short Circuit Withstand (A, rms symmetrical) Watt Loss @ 100% I (W) Weight (lbs.)
0.25
0.5
1.0
0.2
0.4
0.75
1.6
2.5
4.2
Maximum Motor Output
Three-phase 200 to 240V (x2 of input voltage) 0.1 to 400 Hz Single-phase, 100 to 120 VAC, 50/60Hz 6
9
16
Voltage: +/- 10%; Frequency: +/- 5% 5kA @ 120 VAC 24
34
46
3.5
3.6
3.7
230V Class Model Name: GS2-xxx
20P5
21P0
22P0
23P0
25P0
27P5
HP kW Output Rated Output Current (A) Rating Maximum Output Voltage Rated Output Frequency
0.5
1.0
2.0
3.0
5.0
7.5
0.4
0.75
1.5
2.2
3.7
5.5
2.5
5.0
7.0
10
17
25
Maximum Motor Output
Rated Voltage/Frequency
Three-phase 200 to 240V (proportional to input voltage) 0.1 to 400 Hz Single/Three-phase, 200/208/220/230/240 VAC, 50/60 Hz
Three-phase, 200/208/220/230/240 VAC, 50/60 Hz
Input Rated Input Current (A) 6.3/3.2 11.5/6.3 15.7/9.0 27/12.5 19.6 28 Rating Voltage: +/- 10%; Frequency: +/- 5% Voltage/Frequency Tolerance Short Circuit Withstand 5kA @ 240 VAC (A, rms symmetrical) 34 57 77 111 185 255 Watt Loss @ 100% I (W) 3.5 3.6 3.7 8.5 8.5 8.5 Weight (lbs.)
1st Ed. Rev. C
12/2006
GS2 Series AC Drive User Manual
1–5
Page 14
Chapter 1: Getting Started
GS2 AC Drive Specifications (continued) 460V Class Model Name: GS2-xxx
41P0
42P0
43P0
45P0
47P5
4010
HP kW Output Rated Output Current (A) Rating Maximum Output Voltage Rated Output Frequency
1.0
2.0
3.0
5.0
7.5
10
0.8
1.5
2.2
4.0
5.5
7.5
3.0
4.0
5.0
8.2
13
18
Maximum Motor Output
Three-phase 380 to 480V (proportional to input voltage) 0.1 to 400 Hz Three-phase 380/400/415/440/460/480 VAC 50/60Hz
Rated Voltage/Frequency Input Rated Input Current (A) Rating Voltage/Frequency Tolerance Short Circuit Withstand (A, rms symmetrical) Watt Loss @ 100% I (W) Weight (lbs.)
4.2
5.7
6.0
8.5
14
23
Voltage: +/- 10%; Frequency: +/- 5% 5kA @ 480 VAC 73
86
102
170
240
255
3.5
3.6
3.7
8.5
8.5
8.5
575V Class Model Name: GS2-xxx
51P0
52P0
53P0
55P0
57P5
5010
HP kW Output Rated Output Current (A) Rating Maximum Output Voltage Rated Output Frequency Rated Voltage/Frequency Rated Input Current (A) Input Rating Voltage/Frequency Tolerance Short Circuit Withstand (A, rms symmetrical) Watt Loss @ 100% I (W) Weight (lbs.)
1.0
2.0
3.0
5.0
7.5
10
0.75
1.5
2.2
3.7
5.5
7.5
1.7
3.0
4.2
6.6
9.9
12.2
Maximum Motor Output
1–6
Three-phase 500 to 600V (proportional to input voltage) 0.1 to 400 Hz Three-phase 500 to 600V 2.4
4.2
5.9
7.0
10.5
12.9
Voltage: -15 to +10% ; Frequency: +/- 5% 5kA @ 600 VAC 30
58
83
132
191
211
3.3
3.3
4.4
7.0
7.0
7.3
GS2 Series AC Drive User Manual
Page 15
Chapter 1: Getting Started
General Specifications Control Characteristics Control System Rated Output Frequency Output Frequency Resolution Overload Capacity
Pulse Width Modulation, Carrier frequency 1-12 kHz 1.0 to 400.0 Hz 0.1 Hz 150% of rated current for 1 minute Includes auto-torque boost, auto-slip compensation, starting torque 125% @ 0.5 Hz / 150% @ 5.0 Hz 20% without dynamic braking, 125% with optional braking resistor - braking transistor built-in Operation frequency 60-0 Hz, 0 - 100% rated current, Start time 0.0 - 5.0 seconds, Stop time 0.0 - 25.0 seconds
Torque Characteristics Braking Torque DC Braking to 600 seconds (linear or non-linear acceleration/deceleration), Acceleration/Deceleration Time 0.1 second acceleration/deceleration available
Voltage/Frequency Pattern
Settings available for Constant Torque - low & high starting torque, Variable Torque - low & high starting torque, and user configured
Stall Prevention Level
20 to 200% or rated current
Operation Specification Keypad Setting by <UP> or <DOWN> buttons or potentiometer Frequency Potentiometer - 3-5 k⏲, 0 to 10 VDC (input impedance 10 k⏲), Setting External Signal 0 to 20 mA / 4 to 20 mA (input impedance 250⏲). Multi-Speed Inputs 1 to 3, RS-232C/RS-485 communication interface
Inputs
Keypad Setting by <RUN>, <FWD/REV>, <STOP/RESET> buttons Operation Forward/Stop, Reverse/Stop (run/stop, fwd/rev), 3-wire control, Setting External Signal Serial Communication RS-232C & RS-485 (Modbus RTU)
Digital
6 user-programmable: FWD/STOP, REV/STOP, RUN/STOP, REV/FWD, RUN momentary (N.O.), STOP momentary (N.C.), External Fault (N.O./N.C.), External Reset, Multi-Speed Bit (1-3), Jog, External Base Block (N.O./N.C.), Second Accel/Decel Time, Speed Hold, Increase Speed, Decrease Speed, Reset Speed to Zero, PID Disable (N.O.), PID Disable (N.C.), Input Disable
Analog
1 user-configurable, 0 to 10 VDC (input impedance 10 k⏲), 0 to 20 mA / 4 to 20 mA (input impedance 250⏲), 10 bit resolution
Digital
2 user-programmable: Inverter Running, Inverter Fault, At Speed, Zero Speed, Above Desired Frequency, Below Desired Frequency, At Maximum Speed, Over Torque Detected, Above Desired Current, Below Desired Current, PID Deviation Alarm
Analog
1 user-programmable, 0 to 10 VDC (max load 2mA), 8 bit resolution frequency, current, process variable PV
Operating Functions
Automatic voltage regulation, voltage/frequency characteristics selection, non-linear acceleration/deceleration, upper and lower frequency limiters, 7-stage speed operation, adjustable carrier frequency (1 to 12 kHz), PID control, skip frequencies, analog gain & bias adjustment, jog, electronic thermal relay, automatic torque boost, trip history, software protection
Input Terminals
Output Terminals
Outputs
1st Ed. Rev. C
12/2006
GS2 Series AC Drive User Manual
1–7
Page 16
Chapter 1: Getting Started
General Specifications (continued)
Protective Functions
Operator Interface
Operator Devices
8-key, 4-digit, 7-segment LED, 14 status LEDs, potentiometer
Programming
Parameter values for setup and review, fault codes
Status Display Key Functions
Environment
Actual Operating Frequency, RPM, Scaled Frequency, Amps, % Load, Output Voltage, DC Bus Voltage, Process Variable, Set-point Frequency RUN, STOP/RESET, FWD/REV, PROGRAM, DISPLAY, <UP>, <DOWN>, ENTER
Enclosure Rating
Protected Chassis, IP20
Ambient Temperature
-10°C to 50°C (14°F to 122°F) -10°C to 40°C (14°F to 104°F) for models 7.5 hp (5.5 kW) and higher
Storage Temperature
-20°C to 60°C (-4°F to 140°F) – during short term transportation period
Ambient Humidity
20 to 90% RH (non-condensing)
Vibration
9.8 m/s^2 (1G) less than 10 Hz, 5.9 m/s^2 (0.6G) 10 to 60 Hz
Installation Location
Options Agency Approvals
1–8
Electronic Thermal, Overload Relay, Auto Restart after Fault, Momentary Power Loss, Reverse Operation Inhibit, Auto Voltage Regulation, Over-Voltage Trip Prevention, Auto Adjustable Accel/Decel, Over-Torque Detection Mode, Over-Torque Detection Level, Over-Torque Detection Time, Over-Current Stall Prevention during Acceleration, Over-Current Stall Prevention during Operation
Altitude 1000m or lower above sea level, keep from corrosive gas, liquid and dust Noise filter, input AC reactor, output AC reactor, cable for remote operator, programming software, Dynamic braking resistor, input fuses UL & cUL listed; CE* *CE certification applies only to 115V, 230V, 460V class drives.
GS2 Series AC Drive User Manual
Page 17
INSTALLATION AND WIRING
CHAPTER
2
In This Chapter... Ambient Conditions . . . . . . . . . . . . . . . . . . . . . . . .2–2 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2–3 Minimum Clearances and AirFlow . . . . . . . . . . . . . . . . . . . . . . . .2–3
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2–4 GS2 Circuit Connections . . . . . . . . . . . . . . . . . . . .2–6 Danger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2–6 Main Circuit Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2–8 Control Terminal Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2–10 Basic Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2–11
External Accessories . . . . . . . . . . . . . . . . . . . . . . .2–12
Page 18
Chapter 2: Installation and Wiring
Ambient Conditions The AC drive should be kept in the shipping carton before installation. In order to retain the warranty coverage, the AC drive should be stored properly when it is not to be used for an extended period of time. Some storage suggestions are: • Store in a clean and dry location free from direct sunlight or corrosive fumes. • Store within an ambient temperature range of -20°C to +60°C. • Store within a relative humidity range of 0% to 90% and non-condensing environment. • Store within an air pressure range of 86 kPA to 106 kPA.
Ambient Conditions to 50°C (14°F to 122°F) for models below 7.5 hp (5.5 kW), Ambient Temperature -10°C -10°C to 40°C (14°F to 104°F) for models 7.5 hp (5.5 kW) and higher Storage Temperature -20° to 60°C (-4°F to 140°F) 0 to 90% (non-condensing) Relative Humidity Atmosphere Pressure 86 kPA to 106 kPA 9.8 m/s2 (1G) less than 10 Hz, 5.9 m/s2 (0.6G) 10 to 60 Hz Vibration
2–2
Installation Location
Altitude 1000m or lower above sea level, keep from corrosive gas, liquid and dust
Enclosure Rating
IP20: Protection against contact by fingers. Protection against medium-size foreign objects
GS2 Series AC Drive User Manual
Page 19
Chapter 2: Installation and Wiring
Installation Improper installation of the AC drive will greatly reduce its life. Be sure to observe the following precautions when selecting a mounting location: WARNING: Failure to observe these precautions may damage the drive and void the warranty!
• Do not mount the AC drive near heat-radiating elements or in direct sunlight. • Do not install the AC drive in a place subjected to high temperature, high humidity, excessive vibration, corrosive gases or liquids, or airborne dust or metallic particles. • Mount the AC drive securely on a flat, rigid, non-flammable surface. • Mount the AC drive vertically and do not restrict the air flow to the heat sink fins. WARNING: AC drives generate a large amount of heat which may damage them. Auxiliary cooling methods are typically required in order not to exceed maximum ambient temperatures.
Minimum Clearances and Air Flow MAXIMUM AMBIENT TEMPERATURES MUST NOT EXCEED 50°C (122°F), OR 40°C (104°F) FOR MODELS 7.5 HP (5.5 KW) AND HIGHER!
Fan
6" 150mm min
Air Flow
2",50mm min
2" 50mm min
6" 150mm min
Input Power
1st Ed. Rev. C
12/2006
To Motor
GS2 Series AC Drive User Manual
2–3
Page 20
Chapter 2: Installation and Wiring
Dimensions GS2-10P2, GS2-10P5, GS2-11P0, GS2-20P5, GS2-21P0, GS2-22P0, GS2-41P0, GS2-42P0, GS2-43P0, GS2-51P0, GS2-52P0, GS2-53P0
Units: mm [inches]
2–4
GS2 Series AC Drive User Manual