Page 51

Chapter 2: Specifications

PX-244-1: Four-point, 0.5 A, 24VDC Discrete Output Terminal The PX-244-1 (type 1) DC Output Terminal provides four 24VDC 0.5 A shortcircuit protected sourcing outputs with LED status. Intended for use with 3-wire and 2-wire devices. General Specifications

LED Output 1

LED Output 2

LED Output 3

LED Output 4

Output 1

L

1

5

2 0V Output 3

PX-244-1

6

3

7

4

8

Output 2 + 24VDC 0V

3Wire

Output 4

Terminal Specifications Outputs Per Terminal Commons Per Terminal Output Type Output Data Bytes Used Output Power Source Current Consumption (from Load Voltage) Operating Voltage Maximum Load Current On Voltage Drop Maximum Leakage Current Maximum Inrush Current Maximum Short-Circuit Voltage Load Type Current Consumption (from I/O Bus) Reverse Voltage Protection

4 2 Sourcing 1/2 byte (4-bits) 24VDC provided via terminal power bus 30mA typical 24VDC ( -15%/+20%) 0.5 A per channel (Short-Circuit Protected) 0.4 VDC @ 0.5 A 300mA 1.5 A

Operating Temp Storage Temp Relative Humidity Environment Air

Mounting/ Orientation Restrictions Vibration Shock Noise Immunity Protection Class Weight Dimensions (WxHxD) Adjacent Mounting on Bus Terminals with Power Contact Adjacent Mounting on Bus Terminals without Power Contact Passes Terminal Bus Power Passes PE Bus Agency Approvals*

32 to 131 °F (0 to 55 °C) -13 to 185 °F (-25 to 85 °C) 5% to 95%, non-condensing No corrosive gases permitted 35mm DIN rail/None Conforms to EN 60068-2-6 Conforms to EN 60068-2-27/ EN 60068-2-29 Conforms to EN 61000-6-2/ EN 61000-6-4 IP20 60g 12 x 100 x 68.8 mm (0.47 x 3.94 x 2.71 in) Yes, DC only

No Yes No UL/cUL File No. E157382, CE

* o obtain the most current agency approval information, see the Agency Approval Checklist section on the specific part number’s web page.

35V Resistive, inductive, lamp 9mA typical

Electrical Isolation

No 500Vms (I/O bus/field potential)

Heat Dissipation OFF to ON Response ON to OFF Response Status Indicators

1W max 100ms max 20ms max 4, indicates output is ON

Protos X Installation and I/O Manual, 1st Edition, Rev. C

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

2–33

Page 52

Chapter 2: Specifications

PX-244-2:

1 Four-point, 2A, 24VDC Discrete Output Terminal The PX-244-2 (type 1) DC Output Terminal provides four 24VDC 2A short-circuit 2 protected sourcing outputs with LED status. General Specifications 3 Operating Temp Storage Temp 4 Relative Humidity Environment Air Mounting/ Orientation 5 Restrictions Vibration Shock 6 Noise Immunity 7 Protection Class Weight Dimensions (WxHxD) 8 Adjacent Mounting on Bus Terminals with Terminal Specifications 9 Outputs Per Terminal Power Contact Adjacent Mounting on Commons Per Terminal Bus Terminals without 10 Output Type Power Contact Passes Terminal Bus Output Data Bytes Used Power 11 Output Power Source Passes PE Bus Current Consumption Agency Approvals* Load Voltage) 12 (from Operating Voltage Load Current 13 Maximum On Voltage Drop Maximum Leakage Current Inrush Current 14 Maximum Maximum Short-Circuit Voltage Type A Load Current Consumption (from I/O Bus) Voltage Protection B Reverse Electrical Isolation Dissipation C Heat OFF to ON Response ON to OFF Response D Status Indicators LED Output 1

LED Output 2

LED Output 3

LED Output 4

Output 1 0V

0V

PX- 244-2

Output 3

1

5

2

6

3

7

4

8

32 to 131 °F (0 to 55 °C) -13 to 185 °F (-25 to 85 °C) 5% to 95%, non-condensing No corrosive gases permitted

Output 2

0V

L

35mm DIN rail/None

L

Conforms to EN 60068-2-6 Conforms to EN 60068-2-27/ EN 60068-2-29 Conforms to EN 61000-6-2/ EN 61000-6-4 IP20 60g 12 x 100 x 68.8 mm (0.47 x 3.94 x 2.71 in)

0V

Output 4

Yes, DC only

4 4 Sourcing 1/2 byte (4-bits) 24VDC provided via terminal power bus

No

Yes

No UL/cUL File No. E157382, CE

30mA typical

24VDC ( -15%/+20%) 2A per channel (Short-Circuit Protected) 0.14 VDC @ 2A 60mA 35A 52V Resistive, inductive, lamp

* obtain the most current agency approval information, see the Agency Approval Checklist section on the specific part number’s web page.

9mA typical

Yes 500Vms (I/O bus/field potential) 1W max 160ms typ, 300ms max 10ms min, 80ms max 4, indicates output is ON

2–34

Protos X Installation and I/O Manual, 1st Edition, Rev. C

Page 53

Chapter 2: Specifications

PX-248: Eight-point, 0.5 A, 24VDC Discrete Output Terminal The PX-248 (type 1) DC Output Terminal provides eight 24VDC 0.5 A short-circuit protected sourcing outputs with LED status. General Specifications

Signal LED

Signal LED

2 4 6 8

1 3 5 7

Output 1 Output 3 Output 5 Output 7 PX-248

1

5

2

6

3

7

4

8

Output 2 Output 4 Output 6 Output 8

(–)

L L Connect common (–) to same common as terminal power bus

Operating Temp Storage Temp Relative Humidity Environment Air Mounting/ Orientation Restrictions Vibration Shock Noise Immunity Protection Class Weight Dimensions (WxHxD)

Terminal Specifications Outputs Per Terminal Commons Per Terminal Output Type Output Data Bytes Used Output Power Source Current Consumption (from Load Voltage) Operating Voltage Maximum Load Current On Voltage Drop Maximum Leakage Current Maximum Inrush Current Max. Short-Circuit Voltage Load Type Current Consumption (from I/O Bus) Reverse Voltage Protection Electrical Isolation Heat Dissipation OFF to ON Response ON to OFF Response Status Indicators

8 Field wired Sourcing 1-byte 24VDC provided via terminal power bus 60mA + load typical 24VDC (-15%/+20%) 0.5 A per channel (Short-Circuit Protected) 0.4 VDC @ 0.5 A 300mA 1.5 A 35V Resistive, inductive, lamp

Adjacent Mounting on Bus Terminals with Power Contact Adjacent Mounting on Bus Terminals without Power Contact Passes Terminal Bus Power Passes PE Bus Agency Approvals*

32 to 131 °F (0 to 55 °C) -13 to 185 °F (-25 to 85 °C) 5% to 95%, non-condensing No corrosive gases permitted 35mm DIN rail/None Conforms to EN 60068-2-6 Conforms to EN 60068-2-27/ EN 60068-2-29 Conforms to EN 61000-6-2/ EN 61000-6-4 IP20 70g 12 x 100 x 68.8 mm (0.47 x 3.94 x 2.71 in) Yes, DC only No Yes No UL/cUL File No. E157382, CE

* o obtain the most current agency approval information, see the Agency Approval Checklist section on the specific part number’s web page.

18mA typical Yes 500Vms (I/O bus/field potential) 1W max 100ms max 20ms max 8, indicates output is ON

Protos X Installation and I/O Manual, 1st Edition, Rev. C

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

2–35

Page 54

Chapter 2: Specifications

PX-249: Sixteen-point, 0.5 A, 24VDC Discrete Output Terminal The PX-249 (type 1) DC Output Terminal provides sixteen 24VDC 0.5 A short1 circuit protected sinking outputs with LED status. 2 General Specifications Operating Temp Storage Temp 3 Relative Humidity Environment Air 4 Mounting/ Orientation Restrictions Vibration 5 Shock Noise Immunity 6 Protection Class Weight 7 Dimensions (WxHxD) Adjacent Mounting on 8 Bus Terminals with Terminal Specifications Power Contact Per Terminal Adjacent Mounting on 9 Outputs Commons Per Terminal Bus Terminals without Output Type Power Contact Passes Terminal Bus 10 Output Data Bytes Used Power Output Power Source Passes PE Bus Consumption Agency Approvals* 11 Current (from Load Voltage) Operating Voltage 12 Maximum Load Current On Voltage Drop Leakage Current 13 Maximum Maximum Inrush Current Short-Circuit Voltage 14 Max. Load Type Current Consumption I/O Bus) A (from Reverse Voltage Protection Isolation B Electrical Heat Dissipation to ON Response C OFF ON to OFF Response Status Indicators D PX-249 1 2 3 4 5 6 7 8

9 10 11 12 13 14 15 16

Output LED

2

3

4

1

9

2

10

3

5

11

4

12

5

13

6

14

7

15

8

16

6

7

Output 1 Output 2

Output 3

Output 4 Output 5 Output 6

Output 7

Output 8

32 to 131 °F (0 to 55 °C) -13 to 185 °F (-25 to 85 °C) 5% to 95%, non-condensing No corrosive gases permitted

Output LED

1

8

1

9

2

10

3

11

4 5

12 13

6

14

7

15

8

16

9 10 11 12 13 14 15 16

Output 9

Output 10

Output 11

Output 12 Output 13 Output 14

(+)

L

35mm DIN rail/None

L

Conforms to EN 60068-2-6 Conforms to EN 60068-2-27/ EN 60068-2-29 Conforms to EN 61000-6-2/ EN 61000-6-4 IP20 70g 12 x 100 x 68.8 mm (0.47 x 3.94 x 2.71 in)

If external power supply, connect common (–) to same common as terminal power bus

Output 15

Output 16

Yes, DC only

16 Field wired Sinking 2-bytes Requires external 24VDC power source

No

Yes

No UL/cUL File No. E157382, CE

35mA + load typical

24VDC ( -15%/+20%) 0.5 A per channel (Short-Circuit Protected) 0.12 VDC @ 0.5 A 75mA 3.5 A 36V Resistive, inductive, lamp

* obtain the most current agency approval information, see the Agency Approval Checklist section on the specific part number’s web page.

45mA typical

Yes 500Vms (I/O bus/field potential) 1W max 0.45 ms 3.3 ms 16, indicates output is ON

2–36

Protos X Installation and I/O Manual, 1st Edition, Rev. C

Page 55

Chapter 2: Specifications

PX-272-1: Two-point, 0-230 VAC/VDC Discrete Solid State Relay Output Terminal The PX-272-1 (type 2) Relay Output Terminal provides two 230 VAC/ VDC 0.3 A outputs with LED status. Intended for use with 4-wire, 3-wire and 2-wire devices.

LED Output 2

LED Output 1

Output 1 230 VAC / VDC

L

3Wire

0V PE

1

5

2

6

3

7

4

8

Output 2 230 VAC / VDC

0V

4Wire

PE

PX-272-1 Note: Terminal PX-908 is recommended to isolate terminal power or use PX-970 to supply and isolate power.

Terminal Specifications Outputs Per Terminal Commons Per Terminal Output Type Output Data Bytes Used Output Power Source Current Consumption (from Terminal Power Bus) Operating Voltage Maximum Load Current Maximum Leakage Current Maximum Inrush Current Contact Resistance Surge Voltage Protection Load Type Current Consumption (from I/O Bus) Electrical Isolation Heat Dissipation Switch-ON Time Switch-OFF Time Switch-ON Delay Switch-OFF Delay Status Indicators

2 2 Solid State Relay (DC sourcing only) 1/4 byte (2-bits) 230 VAC/VDC provided via terminal power bus (ON resistance max 100mV) + load 0 to 230 VAC/VDC (DC 100Hz) 0.3 A per point < 1mA (off state) 0.5 A for 20s, 1.5 A for 100ms 2.1 V, typical 3.2 V, max. From 400VAC Resistive, inductive

General Specifications

Operating Temp Storage Temp Relative Humidity Environment Air Mounting/ Orientation Restrictions Vibration Shock Noise Immunity Protection Class Weight

Dimensions (WxHxD) Adjacent Mounting on Bus Terminals with Power Contact Adjacent Mounting on Bus Terminals without Power Contact Passes Terminal Bus Power Passes PE Bus Agency Approvals*

32 to 131 °F (0 to 55 °C) -13 to 185 °F (-25 to 85 °C) 5% to 95%, non-condensing No corrosive gases permitted 35mm DIN rail/None Conforms to EN 60068-2-6 Conforms to EN 60068-2-27/ EN 60068-2-29 Conforms to EN 61000-6-2/ EN 61000-6-4 IP20 55g 12 x 100 x 68.8 mm (0.47 x 3.94 x 2.71 in) Yes, 230 VAC/VDC only No Yes Yes UL/cUL File No. E157382, CE

* o obtain the most current agency approval information, see the Agency Approval Checklist section on the specific part number’s web page.

10mA 500Vms (I/O bus/field potential) 2500VDC (1 min.) 1W max 4 to 6 ms 0.05 to 0.1 ms 320ms 6.2 ms 2, indicates output is ON

Protos X Installation and I/O Manual, 1st Edition, Rev. C

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

2–37

Page 56

Chapter 2: Specifications

PX-272-2: Two-point, 230VAC / 30VDC Discrete Relay Output Terminal The PX-272-2 (type 2) Relay Output Terminal provides two 230VAC / 30VDC 5A 1 outputs with LED status. Intended for use with 4-wire, 3-wire and 2-wire devices. 2 Terminal Specifications Outputs Per Terminal 3 Commons Per Terminal Output Type 4 Output Data Bytes Used Output Power Source Current Consumption 5 (from Terminal Power Bus) Operating Voltage 6 Maximum Load Current Maximum Load Current with Resistive Load 7 Maximum Load Current with Inductive Load, cosine = 0.4, L/R=7ms 8 General Specifications Operating Temp Minimum Load (approximate) Temp 9 Storage Relative Humidity Load Type Environment Air 10 Mounting/ Orientation Switching Times Contact Material 11 Restrictions Vibration Current Consumption (from I/O Bus) Shock Electrical Isolation 12 Noise Immunity Heat Dissipation Class Switching Frequency at 13 Protection Weight Maximum Contact Load Maximum Contact Resistance Dimensions (WxHxD) 14 Adjacent Mounting on Minimum Insulation Resistance Bus Terminals with Mechanical Operating Life Power Contact A Adjacent Mounting on Electrical Operating Life Bus Terminals without Test Voltage Between Open Contact B Power Contacts Passes Terminal Bus Status Indicators Power C Passes PE Bus Agency Approvals* D LED Output 1

1

LED Output 2

2 2 SPST Relay, normally open contact (DC sourcing only) 1/4 byte (2-bits) 230VAC/30VDC provided via terminal power bus (ON resistance typ 2.4 V, max 3.2 V) + load 230VAC/30VDC 5A per point AC: 5A @230VAC, 1250VA DC: 5A @ 30VDC, 150W

5

Output 1

2

6

L

230VAC or 30VDC

3Wire

3

7

4

8

0V

PE

1

5

2

6

3

7

4

8

Output 2

230VAC or 30VDC

0V

4Wire

PE

PX- 272-2

AC: 2A @230VAC DC: 2A @ 30VDC

Note: Terminal PX-908 is recommended to isolate terminal power or use PX-970 to supply and isolate power.

10mA @ 5VDC (as supplied) 100mA @ 20VDC (after approx. ≥ 100mA has been switched at least once) Resistive, inductive, lamp Reaction Time: 10ms max. Release Time; 4ms max. Bounce Time: 5ms max. Silver Cadmium Oxide

32 to 131 °F (0 to 55 °C) -13 to 185 °F (-25 to 85 °C) 5% to 95%, non-condensing No corrosive gases permitted 35mm DIN rail/None

Conforms to EN 60068-2-6 Conforms to EN 600682-27/ EN 60068-2-29 Conforms to EN 61000-6-2/ EN 61000-6-4 IP20 85g 12 x 100 x 68.8 mm (0.47 x 3.94 x 2.71 in)

80mA

500Vms (I/O bus/field potential) 2500VDC (1 min.) 1W max 10/minute < 30mV

100MV @ 500VDC

Yes, 230VAC or 30VDC only

20,000,000 switching operations Minimum 100,000 switching operations with resistive loads

No

750V for 1 minute

Yes

Yes UL/cUL File No. E157382, CE

2–38

2, indicates output is ON

* obtain the most current agency approval information, see the Agency Approval Checklist section on the specific part number’s web page.

Protos X Installation and I/O Manual, 1st Edition, Rev. C

Page 57

Chapter 2: Specifications

PX-549: Eight inputs/Eight outputs, 24VDC Discrete Input/Output Terminal The PX-549 (type 1) DC Input/Output Terminal provides eight 24VDC inputs and eight 24VDC 0.5 A outputs with reverse polarity protection and LED status.

PX-549 1 2 3

Input LED

9 10

4 5 6 7

3

13 14

5

1

4 6

7

Input 1

1

Input 2

2

2

3

3

Input 3

4

4

5

5

Input 4 Input 5 Input 6 Input 7

6

6

7

7

8

8

Input 8

Terminal Specifications

9 10 11 12 13 14 15 16

2

15 16

8

Output LED

1

11 12

8

1

9

2

10

3

11

4 5

12 13

6

14

7

15

8

16

Inputs/Outputs Per Terminal Data Bytes Used

Output 1 Output 2

Input/Output Power Source

Output 3 Output 4 Output 5 Output 6 Output 7 Output 8

L L

24VDC Power Supply

+

–

Connect power supply common (–) to same common as terminal power bus

General Specifications

Operating Temp Storage Temp Relative Humidity Environment Air Mounting/ Orientation Restrictions Vibration Shock Noise Immunity Protection Class Weight

Dimensions (WxHxD) Adjacent Mounting on Bus Terminals with Power Contact Adjacent Mounting on Bus Terminals without Power Contact Passes Terminal Bus Power Passes PE Bus Agency Approvals*

32 to 131 °F (0 to 55 °C) -13 to 185 °F (-25 to 85 °C) 5% to 95%, non-condensing No corrosive gases permitted 35mm DIN rail/None Conforms to EN 60068-2-6 Conforms to EN 60068-2-27/ EN 60068-2-29 Conforms to EN 61000-6-2/ EN 61000-6-4 IP20 60g 12 x 100 x 68.8 mm (0.47 x 3.94 x 2.71 in) Yes, DC only

8 sinking inputs / 8 sourcing outputs 1-byte (inputs) / 1-byte (outputs) Requires external 24VDC power source 24VDC (-15%/+20%)

Operating Voltage Rating Current Consumption 25mA typical (from I/O Bus) Current Consumption 15mA + load typical (from Terminal Power Bus) 500Vms Electrical Isolation (I/O bus/field potential) 1W max Heat Dissipation 8 input and 8 output, Status Indicators indicates ON Input Specifications 30VDC Peak Voltage Rating 15 to 30 VDC ON Voltage Level -3 to +5 VDC OFF Voltage Level 2mA Minimum ON Current 40mA Minimum OFF Current Current Consumption 3mA typical (from I/O Bus) 3ms OFF to ON Response 3ms ON to OFF Response Output Specifications 0.5 A (Short-Circuit Max. Load Current per Output Protected) 0.14 VDC @ 2A On Voltage Drop 5mA Maximum Leakage Current 2A Maximum Inrush Current Maximum Short-Circuit 45V Voltage Resistive, inductive, Load Type lamp

Yes

Reverse Voltage Protection OFF to ON Response ON to OFF Response

No UL/cUL File No. E157382, CE

* obtain the most current agency approval information, see the Agency Approval Checklist section on the specific part number’s web page.

No

Yes 50ms 75ms

Protos X Installation and I/O Manual, 1st Edition, Rev. C

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

2–39

Page 58

Chapter 2: Specifications

Analog Terminals PX-302: 1 Two-channel, 4-20 mA Analog Input Terminal The PX-302 (type 3) Analog Input Terminal provides two electrically isolated 4-20 2 mA inputs with 12-bit resolution and Run and Error LED status. 3 General Specifications Operating Temp Storage Temp 4 Relative Humidity Environment Air 5 Mounting/ Orientation Restrictions 6 Vibration Shock 7 Noise Immunity 8 Protection Class Weight 9 Dimensions (WxHxD) Adjacent Mounting on 10 Terminal Specifications Bus Terminals with Power Contact Number of Channels 11 Input Ranges Adjacent Mounting on Resolution Bus Terminals without Type Power Contact 12 Input Data Format Passes Terminal Bus Power 13 Data Bytes Consumed Passes PE Bus Input Power Source Agency Approvals* 14 Current Consumption (from Terminal Power Bus) A Input Impedance Absolute Max Ratings LED Status Time B Conversion LED LED ON LED OFF Full Scale Calibration Error Consumption C Current Green LED: RUN (from I/O Bus) Isolation D Electrical Red LED: ERROR Heat Dissipation PX-302

1

LED Run 1

LED Run 2

LED Error 1

LED Error 2

5

24VDC Supply

2

3- + + wire – –

+

6

+In1 +In2

1

5

–In1 –In2

2

32 to 131 °F (0 to 55 °C)

-13 to 185 °F (-25 to 85 °C)

5% to 95%, non-condensing

–

2+ wire +

–

24VDC Supply

No corrosive gases permitted

6

35mm DIN rail/None

GND GND

3

3

4

Ground reference optional

7

7

Shld Shld

4

8

Ground reference optional

Conforms to EN 60068-2-6 Conforms to EN 60068-2-27/ EN 60068-2-29 Conforms to EN 61000-6-2/ EN 61000-6-4 IP20

8

PX-302

+In1

+ –

4wire

24VDC Supply

1

–In1

70g

Shld

12 x 100 x 68.8 mm (0.47 x 3.94 x 2.71 in)

2 4

Yes

2 4 to 20 mA 12 bits External ground reference

Yes

Decimal: 0-32767

PX-MOD: 4-bytes input PX-TCP1/TCP2: 8-bytes in/ 8-bytes out (not used) Loop power external NA

No No

UL/cUL File No. E157382, CE

* To obtain the most current agency approval information, see the Agency Approval Checklist section on the specific part number’s web page.

50V internal resistor 35VDC surge Approx. 2ms

± 0.3% of full scale

60mA

500Vms (I/O bus/field potential) 1W max

Status Indicators

2–40

4, see LED Status chart

Normal Operation

Broken wire or current is > 21.5 mA

Protos X Installation and I/O Manual, 1st Edition, Rev. C

Watchdog-timer overflow if no data transmitted within WD set time. Normal Operation

Page 59

Chapter 2: Specifications

PX-304: Four-channel, 4-20 mA Analog Input Terminal The PX-304 (type 1) Analog Input Terminal provides four electrically isolated 4–20 mA inputs with 12-bit resolution and Run and Error LED status. General Specifications 1

5

–

2

6

3

3- + wire +

In1

24VDC Supply – +

+24V +24V

4wire

PX-304

5

–

+

–

2

6

In3

In4

4

8

3

2wire

Terminate shields at signal source

7

+

Connect power supply common (–) to same common as terminal power bus

8

In2

1

7

4

Run 2 Error 2 Run 4 Error 4

Run 1 Error 1 Run 3 Error 3

Data Bytes Consumed Input Power Source Current Consumption (from Terminal Power Bus) Input Impedance Absolute Max Ratings Conversion Time Full Scale Calibration Error Current Consumption (from I/O Bus) Electrical Isolation Heat Dissipation Status Indicators

32 to 131 °F (0 to 55 °C) -13 to 185 °F (-25 to 85 °C) 5% to 95%, non-condensing No corrosive gases permitted

Mounting/ Orientation Restrictions

35mm DIN rail/None

Vibration

Conforms to EN 60068-2-6 Conforms to EN 60068-2-27/ EN 60068-2-29 Conforms to EN 61000-6-2/ EN 61000-6-4

Shock +24V +24V PX-304

Terminal Specifications Number of Channels Input Ranges Resolution Input Type Data Format

Operating Temp Storage Temp Relative Humidity Environment Air

4 4 to 20 mA 12 bits Single-ended Decimal: 0-32767 PX-MOD: 8-bytes input PX-TCP1/TCP2: 16-bytes in/16-bytes out (not used) 24VDC provided via terminal power bus Load < 85V 30VDC surge Approx. 2ms

Noise Immunity Protection Class Weight

IP20

Dimensions (WxHxD)

12 x 100 x 68.8 mm (0.47 x 3.94 x 2.71 in)

Adjacent Mounting on Bus Terminals with Power Contact

Yes, DC only

Adjacent Mounting on Bus Terminals without Power Contact

No

Passes Terminal Bus Power Passes PE Bus Agency Approvals*

1W max 8, see LED Status chart

No UL/cUL File No. E157382, CE

LED Status LED

500Vms (I/O bus/field potential)

Yes

* o obtain the most current agency approval information, see the Agency Approval Checklist section on the specific part number’s web page.

± 0.3% of full scale 85mA

75g

Green LED: RUN

LED ON Normal Operation Broken wire or

Red LED: ERROR current is

> 20.8 mA

LED OFF Watchdog-timer overflow if no data transmitted within WD set time. Normal Operation

Protos X Installation and I/O Manual, 1st Edition, Rev. C

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

2–41

Page 60

Chapter 2: Specifications

PX-308: 1 Eight-channel, 4-20 mA Analog Input Terminal The PX-308 (type 1) Analog Input Terminal provides eight electrically isolated 4-20 2 mA inputs with 12-bit resolution and Error LED status. 3 General Specifications Operating Temp 4 Storage Temp Relative Humidity 5 Environment Air Mounting/ Orientation Restrictions 6 Vibration Shock 7 Noise Immunity Protection Class 8 Weight Dimensions (WxHxD) Specifications 9 Number ofTerminal Adjacent Mounting on Channels Bus Terminals with Input Ranges Power Contact 10 Resolution Adjacent Mounting on Bus Terminals without Input Type Power Contact Data Format 11 Passes Terminal Bus Power Passes PE Bus 12 Data Bytes Consumed Agency Approvals* Power Source 13 Input Current Consumption Terminal Power 14 (from Bus) Input Impedance Max Ratings A Absolute Conversion Time Full Scale Calibration B Error Current Consumption (from I/O Bus) C Electrical Isolation Heat Dissipation D Status Indicators Run Run Run Run

1

5

2

6

Run Run Run Run

1 3 5 7

In1

1

3

7

In5

In6

In7

8

PX-308

4

–

5

In4

3

4

In2

In3

2

2 4 6 8

+

2Wire

35mm DIN rail/None

Terminate shield at signal source

6 7

32 to 131 °F (0 to 55 °C) -13 to 185 °F (-25 to 85 °C) 5% to 95%, non-condensing No corrosive gases permitted

+

Conforms to EN 60068-2-6 Conforms to EN 60068-2-27/ EN 60068-2-29 Conforms to EN 61000-6-2/ EN 61000-6-4 IP20 75g 12 x 100 x 68.8 mm (0.47 x 3.94 x 2.71 in)

–

24VDC Supply

In8

8

PX-308

Connect power supply common to same common (–) as terminal power bus

8 4 to 20 mA 12 bits Single-ended Decimal: 0-32767 PX-MOD: 16-bytes input PX-TCP1/TCP2: 32-bytes in/32-bytes out (not used) Requires external 24VDC power source

Yes, DC only No

Yes

No UL/cUL File No. E157382, CE

* obtain the most current agency approval information, see the Agency Approval Checklist section on the specific part number’s web page.

Load

< 85V 30VDC surge Approx. 4ms

± 0.3% of full scale 105mA

500Vms (I/O bus/field potential) 1W max 8, Red: Error, broken wire or current is > 20.8 mA

2–42

Protos X Installation and I/O Manual, 1st Edition, Rev. C