Page 61

Chapter 2: Specifications

PX-312: Two-channel, -10 to +10 VDC Analog Input Terminal The PX-312 (type 3) Analog Input Terminal provides two electrically isolated -10 to +10 VDC inputs with 12-bit resolution and LED status. PX-312

LED Run 1

24VDC Supply

+In1 +In2

3- + + wire – –

LED Run 2

1

+

5

–In1 –In2

2

6

GND GND

3

Ground reference optional

+ –

2wire +

24VDC Supply

7

Ground reference optional

Shld Shld

4

PX-312

8

+In1

+ –

+

Connect power supply common (–) to same common as terminal power bus

1

4wire

Dimensions (WxHxD)

Shld

Adjacent Mounting on Bus Terminals with Power Contact Adjacent Mounting on Bus Terminals without Power Contact Passes Terminal Bus Power Passes PE Bus Agency Approvals*

4

Terminal Specifications Number of Channels Input Ranges Resolution Input Type Data Format Data Bytes Consumed Input Power Source Current Consumption (from Terminal Power Bus) Input Impedance Absolute Max Ratings Conversion Time Full Scale Calibration Error Current Consumption (from I/O Bus) Electrical Isolation Heat Dissipation Status Indicators

Noise Immunity Protection Class Weight

–In1

2

24VDC Supply

General Specifications

Operating Temp Storage Temp Relative Humidity Environment Air Mounting/ Orientation Restrictions Vibration Shock

2 -10 to +10 VDC 12 bits (11 bits between 0–10 VDC) External ground reference Decimal: -32767 to +32767 PX-MOD: 4-bytes input PX-TCP1/TCP2: 8-bytes in/ 8-bytes out (not used) Voltage source external

32 to 131 °F (0 to 55 °C) -13 to 185 °F (-25 to 85 °C) 5% to 95%, non-condensing No corrosive gases permitted 35mm DIN rail/None Conforms to EN 60068-2-6 Conforms to EN 60068-2-27/ EN 60068-2-29 Conforms to EN 61000-6-2/ EN 61000-6-4 IP20 70g 12 x 100 x 68.8 mm (0.47 x 3.94 x 2.71 in) Yes Yes No No UL/cUL File No. E157382, CE

* obtain the most current agency approval information, see the Agency Approval Checklist section on the specific part number’s web page.

NA > 200kV 35VDC surge Approx. 2ms ± 0.3% of full scale 65mA 500Vms (I/O bus/field potential) 1W max 2, indicates I/O Bus activity

Protos X Installation and I/O Manual, 1st Edition, Rev. C

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

2–43

Page 62

Chapter 2: Specifications

PX-314: 1 Four-channel, -10 to +10 VDC Analog Input Terminal The PX-314 (type 1) Analog Input Terminal provides four electrically isolated -10 to 2 +10 VDC inputs with 12-bit resolution and LED status. 3 General Specifications Operating Temp 4 Storage Temp Relative Humidity 5 Environment Air Mounting/ Orientation Restrictions 6 Vibration Shock 7 Noise Immunity Protection Class 8 Weight Dimensions (WxHxD) 9 Adjacent Mounting on Terminal Specifications Bus Terminals with of Channels Power Contact 10 Number Input Ranges Adjacent Mounting on Bus Terminals without Resolution Power Contact 11 Passes Terminal Bus Input Type Power Passes PE Bus 12 Data Format Agency Approvals* Data Bytes Consumed 13 Input Power Source Consumption 14 Current (from Terminal Power Bus) Input Impedance Max Ratings A Absolute Conversion Time Full Scale Calibration Error Consumption B Current (from I/O Bus) Isolation C Electrical Heat Dissipation D Status Indicators 1

5

Run 1

Run 2

Run 3

Run 4

+ 3- + wire

In1

1

–

2

In2

+

5

+

6

24VDC Supply – +

3

7

4wire

4

8

PX-314

GND GND

+

2

6

In3

In4

3

– Connect power supply common (–) to same common as terminal power bus

7

32 to 131 °F (0 to 55 °C) -13 to 185 °F (-25 to 85 °C) 5% to 95%, non-condensing No corrosive gases permitted

2wire

35mm DIN rail/None

Terminate shield at signal source

–

Conforms to EN 60068-2-6 Conforms to EN 60068-2-27/ EN 60068-2-29 Conforms to EN 61000-6-2/ EN 61000-6-4 IP20 75g 12 x 100 x 68.8 mm (0.47 x 3.94 x 2.71 in)

+

24VDC Supply

4

8

GND GND PX-314

4 -10 to +10 VDC 12 bits (11 bits between 0–10 VDC) Single-ended Decimal: -32767 to +32767 PX-MOD: 8-bytes input PX-TCP1/TCP2: 16-bytes in/16-bytes out (not used) Voltage source external

Yes, DC only No

Yes

No UL/cUL File No. E157382, CE

* obtain the most current agency approval information, see the Agency Approval Checklist section on the specific part number’s web page.

NA

> 130kV 30VDC surge Approx. 2ms ± 0.3% of full scale 100mA

500Vms (I/O bus/field potential) 1W max

4, indicates I/O Bus activity

2–44

Protos X Installation and I/O Manual, 1st Edition, Rev. C

Page 63

Chapter 2: Specifications

PX-318: Eight-channel, -10 to +10 VDC Analog Input Terminal

1 The PX-318 (type 1) Analog Input Terminal provides eight electrically isolated -10 to 2 +10 VDC inputs with 12-bit resolution and LED status. 3 General Specifications Operating Temp 4 Storage Temp Relative Humidity 5 Environment Air Mounting/ Orientation Restrictions 6 Vibration Shock 7 Noise Immunity Protection Class 8 Weight Dimensions (WxHxD) 9 Terminal Specifications Adjacent Mounting on Bus Terminals with Number of Channels Power Contact Input Ranges 10 Adjacent Mounting on Bus Terminals without Resolution Power Contact 11 Passes Terminal Bus Input Type Power Data Format Passes PE Bus 12 Agency Approvals* Data Bytes Consumed 13 Input Power Source Current Consumption (from Terminal Pwr Bus) 14 Input Impedance Absolute Max Ratings Conversion Time A Full Scale Calibration Error B Current Consumption (from I/O Bus) Electrical Isolation C Heat Dissipation Status Indicators D Run Run Run Run

1

5

2

6

3

3- + wire + –

7

Run Run Run Run

1 3 5 7

In1

In2

In3

In4

1

8

2wire

In5

In6

Terminate shields at signal source

In7

In8

4

PX-318

+ +

3

4

24VDC Supply + –

5 6

2

24VDC Supply – +

2 4 6 8

7 8

PX-318

Connect power supply common (–) to same common as terminal power bus

8 -10 to +10 VDC 12 bits (11 bits between 0 to 10 VDC) Single-ended Decimal: -32767 to +32767 PX-MOD: 16-bytes input PX-TCP1/TCP2: 32-bytes in/32-bytes out (not used) Voltage source external

32 to 131 °F (0 to 55 °C) -13 to 185 °F (-25 to 85 °C) 5% to 95%, non-condensing No corrosive gases permitted 35mm DIN rail/None

Conforms to EN 60068-2-6 Conforms to EN 60068-2-27/ EN 60068-2-29 Conforms to EN 61000-6-2/ EN 61000-6-4 IP20 75g 12 x 100 x 68.8 mm (0.47 x 3.94 x 2.71 in) Yes, DC only No

Yes

No UL/cUL File No. E157382, CE

* obtain the most current agency approval information, see the Agency Approval Checklist section on the specific part number’s web page.

NA

> 130kV 30VDC surge Approx. 4ms

± 0.3% of full scale

140mA

500Vms (I/O bus/field potential) 1W max 8, indicates I/O Bus activity

Protos X Installation and I/O Manual, 1st Edition, Rev. C

2–45

Page 64

Chapter 2: Specifications

PX-322-1: 1 Two-channel RTD Input Terminal The PX-322-1 (type 3) RTD Input Terminal provides two PT100 RTD inputs with 2 full linearization and LED status. 3 General Specifications Operating Temp 4 Storage Temp Relative Humidity 5 Environment Air Mounting/ Orientation Restrictions 6 Vibration Shock 7 Noise Immunity Protection Class 8 Weight Dimensions (WxHxD) 9 Terminal Specifications Adjacent Mounting on Bus Terminals with Number of Channels Power Contact 10 Range Adjacent Mounting on Resolution Bus Terminals without Input Type Power Contact 11 Passes Terminal Bus Data Bytes Consumed Power Passes PE Bus 12 Agency Approvals* Connection Method 13 Power Supply Conversion Time Current 14 Measuring Linearity Error LED Status Current Consumption LED LED ON LED OFF I/O Bus) A (from Electrical Isolation Green LED: RUN Heat Dissipation B Status Indicators Red LED: ERROR C D PX-322-1

3Wire RTD

LED Run 1

LED Run 2

LED Error 1

LED Error 2

+R1 +R2

+

1

5

–

+ –

RL1 RL2

2

6

–R1 –R2

3

7

0 to 55 °C -25 to 85 °C 5% to 95%, non-condensing No corrosive gases permitted

2Wire RTD

35mm DIN rail/None

Connect two wires to one side of a 2-wire RTD

Conforms to EN 60068-2-6 Conforms to EN 60068-2-27/ EN 60068-2-29 Conforms to EN 61000-6-2/ EN 61000-6-4 IP20 70g

Shld Shld

4

8

PX-322-1

12 x 100 x 68.8 mm (0.47 x 3.94 x 2.71 in) Yes

2 -200 to 850 °C 0.1 °C per digit PT100 PX-MOD: 4-bytes input

PX-TCP1/TCP2: 8-bytes in/8bytes out (not used) 2-wire or 3-wire (3-wire default) Via I/O Bus Approx. 250ms 5mA typical < ± 1°C

Yes No

No UL/cUL File No. E157382, CE

* obtain the most current agency approval information, see the Agency Approval Checklist section on the specific part number’s web page.

60mA

500Vms (I/O bus/field potential) 1W max 4, see LED Status chart

2–46

Normal Operation Sensor fault, e.g. broken wire

Protos X Installation and I/O Manual, 1st Edition, Rev. C

Watchdog-timer overflow if no data transmitted within WD set time. No Error

Page 65

Chapter 2: Specifications

PX-324-1: Four-channel RTD Input Terminal The PX-324-1 (type 3) RTD Input Terminal provides four PT100 RTD inputs with full linearization and LED status.

PX-324-1

LED Error 1

LED Error 2

LED Error 3

LED Error 4 +R1 +R2

1

+

5

– – R1 – R2

2

6

2Wire RTD

Terminate shields at signal source

+R3 +R4

3

General Specifications

7

Noise Immunity Protection Class Weight

– R3 – R4

4

Operating Temp Storage Temp Relative Humidity Environment Air Mounting/ Orientation Restrictions Vibration Shock

8

PX-324-1

Dimensions (WxHxD)

Terminal Specifications Number of Channels Range Resolution Input Type Data Bytes Consumed Connection Method Power Supply Conversion Time Measuring Current Linearity Error Current Consumption (from I/O Bus)

4 -200 to 850 °C 0.1 °C per digit PT100 PX-MOD: 8-bytes input PX-TCP1/TCP2: 16-bytes in/16-bytes out (not used) 2-wire Via I/O Bus Approx. 250ms 5mA typical < ± 1°C

Adjacent Mounting on Bus Terminals with Power Contact Adjacent Mounting on Bus Terminals without Power Contact Passes Terminal Bus Power Passes PE Bus Agency Approvals*

0 to 55 °C -25 to 85 °C 5% to 95%, non-condensing No corrosive gases permitted 35mm DIN rail/None Conforms to EN 60068-2-6 Conforms to EN 60068-2-27/ EN 60068-2-29 Conforms to EN 61000-6-2/ EN 61000-6-4 IP20 70g 12 x 100 x 68.8 mm (0.47 x 3.94 x 2.71 in) Yes Yes No No UL/cUL File No. E157382, CE

* obtain the most current agency approval information, see the Agency Approval Checklist section on the specific part number’s web page.

60mA

Electrical Isolation

500Vms (I/O bus/field potential)

Heat Dissipation Status Indicators

1W max 4, red, sensor fault

Protos X Installation and I/O Manual, 1st Edition, Rev. C

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

2–47

Page 66

Chapter 2: Specifications

PX-332-J: 1 Two-channel Type J Thermocouple Input Terminal The PX-332-J (type 3) Thermocouple Input Terminal provides two Type J 2 thermocouple inputs with full linearization, cold-junction compensation, and LED status. 3 General Specifications Operating Temp Storage Temp 4 Relative Humidity Environment Air 5 Mounting/ Orientation Restrictions Vibration 6 Shock Noise Immunity 7 Protection Class Weight 8 Dimensions (WxHxD) Adjacent Mounting on 9 Bus Terminals with Terminal Specifications Power Contact Number of Channels Adjacent Mounting on 10 Range Bus Terminals without Power Contact Resolution Passes Terminal Bus 11 Input Type Power Passes PE Bus Data Bytes Consumed Agency Approvals* 12 Connection Method 13 Power Supply Conversion Time LED Status 14 Measuring Current LED LED ON LED OFF Linearity Error Green LED: Consumption A Current RUN (from I/O Bus) Electrical Isolation Red LED: B Heat Dissipation ERROR Status Indicators C D PX-332-J

+

0 to 55 °C -25 to 85 °C 5% to 95%, non-condensing No corrosive gases permitted

–

35mm DIN rail/None

LED Run 1

LED Run 2

LED Error 1

LED Error 2

+TC1 +TC2

1

5

–TC2 –TC2

2

6

3

7

Conforms to EN 60068-2-6 Conforms to EN 60068-2-27/ EN 60068-2-29 Conforms to EN 61000-6-2/ EN 61000-6-4 IP20 70g 12 x 100 x 68.8 mm (0.47 x 3.94 x 2.71 in)

For grounded thermocouples differential should not exceed ±2V

Shld Shld

4

8

Thermocouple extension wire recommended

PX-332-J

Yes

2 -100 to 1200 °C 0.1 °C per digit Type J thermocouple PX-MOD: 4-bytes input PX-TCP1/TCP2: 8-bytes in/8-bytes out (not used) 2-wire (Thermocouple extension wire recommended) Via I/O Bus Approx. 250ms 5mA typical ± 0.5% (relative to full scale value) 65mA

500Vms (I/O bus/field potential) 1W max 4, see LED Status chart

2–48

Yes No

No UL/cUL File No. E157382, CE

* obtain the most current agency approval information, see the Agency Approval Checklist section on the specific part number’s web page.

Normal Operation Sensor fault, e.g. broken wire

Protos X Installation and I/O Manual, 1st Edition, Rev. C

Watchdog-timer overflow if no data transmitted within WD set time. No Error

Page 67

Chapter 2: Specifications

PX-334-J: Four-channel Type J Thermocouple Input Terminal The PX-334-J (type 3) Thermocouple Input Terminal provides four Type J thermocouple inputs with full linearization, cold-junction compensation, and LED status.

1

5

LED Error 1

LED Error 2

LED Error 1

LED Error 2 +TC1 +TC2

1

2

5

–TC2 –TC2

2

3

6

+TC3 +TC4

7

3

4

+ –

6

7

–TC3 –TC4

4

8

PX-334-J

8

PX-334-J

Terminate shield at signal source

For grounded thermocouples differential should not exceed ±2V Thermocouple extension wire recommended

Terminal Specifications Number of Channels Range Resolution Input Type Data Bytes Consumed Connection Method Power Supply Conversion Time Measuring Current Linearity Error Current Consumption (from I/O Bus)

4 -100 to 1200 °C 0.1 °C per digit Type J thermocouple PX-MOD: 8-bytes input PX-TCP1/TCP2: 16-bytes in/16-bytes out (not used) 2-wire (Thermocouple extension wire recommended) Via I/O Bus Approx. 250ms 5mA typical ± 0.5% (relative to full scale value)

General Specifications

Operating Temp Storage Temp Relative Humidity Environment Air Mounting/ Orientation Restrictions Vibration Shock Noise Immunity Protection Class Weight Dimensions (WxHxD)

Adjacent Mounting on Bus Terminals with Power Contact Adjacent Mounting on Bus Terminals without Power Contact Passes Terminal Bus Power Passes PE Bus Agency Approvals*

0 to 55 °C -25 to 85 °C 5% to 95%, non-condensing No corrosive gases permitted 35mm DIN rail/None Conforms to EN 60068-2-6 Conforms to EN 60068-2-27/ EN 60068-2-29 Conforms to EN 61000-6-2/ EN 61000-6-4 IP20 70g 12 x 100 x 68.8 mm (0.47 x 3.94 x 2.71 in) Yes Yes No No UL/cUL File No. E157382, CE

* obtain the most current agency approval information, see the Agency Approval Checklist section on the specific part number’s web page.

75mA

Electrical Isolation

500Vms (I/O bus/field potential)

Heat Dissipation Status Indicators

1W max 4, red, sensor fault/broken wire

Protos X Installation and I/O Manual, 1st Edition, Rev. C

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

2–49

Page 68

Chapter 2: Specifications

PX-332-K: 1 Two-channel Type K Thermocouple Input Terminal The PX-332-K (type 3) Thermocouple Input Terminal provides two Type K 2 thermocouple inputs with full linearization, cold-junction compensation, and LED status. 3 General Specifications Operating Temp Storage Temp 4 Relative Humidity Environment Air 5 Mounting/ Orientation Restrictions Vibration 6 Shock Noise Immunity 7 Protection Class Weight 8 Dimensions (WxHxD) Adjacent Mounting on 9 Bus Terminals with Terminal Specifications Power Contact Number of Channels Adjacent Mounting on 10 Range Bus Terminals without Power Contact Resolution Passes Terminal Bus 11 Input Type Power Passes PE Bus Data Bytes Consumed Agency Approvals* 12 Connection Method 13 Power Supply Conversion Time 14 Measuring Current LED Status Linearity Error LED LED ON LED OFF Current Consumption A (from I/O Bus) Green LED: RUN Electrical Isolation B Heat Dissipation Red LED: ERROR Status Indicators C D 0 to 55 °C -25 to 85 °C 5% to 95%, non-condensing No corrosive gases permitted

PX-332-K

LED Run 1

LED Run 2

LED Error 1

LED Error 2

+TC1 +TC2

1

5

+

35mm DIN rail/None

–

–TC2 –TC2

2

6

3

7

Conforms to EN 60068-2-6 Conforms to EN 60068-2-27/ EN 60068-2-29 Conforms to EN 61000-6-2/ EN 61000-6-4 IP20 70g 12 x 100 x 68.8 mm (0.47 x 3.94 x 2.71 in)

For grounded thermocouples differential should not exceed ±2V

Shld Shld

4

PX-332-K

8

Thermocouple extension wire recommended

Yes

2 -100 to 1370 °C 0.1 °C per digit Type K thermocouple PX-MOD: 4-bytes input PX-TCP1/TCP2: 8-bytes in/8-bytes out (not used) 2-wire (Thermocouple extension wire recommended) Via I/O Bus Approx. 250ms 5mA typical ± 0.5% (relative to full scale value) 65mA

500Vms (I/O bus/field potential) 1W max

4, see LED Status chart

2–50

Yes No

No UL/cUL File No. E157382, CE

* o obtain the most current agency approval information, see the Agency Approval Checklist section on the specific part number’s web page.

Normal Operation Sensor fault, e.g. broken wire

Protos X Installation and I/O Manual, 1st Edition, Rev. C

Watchdog-timer overflow if no data transmitted within WD set time. No Error

Page 69

Chapter 2: Specifications

PX-334-K: Four-channel Type K Thermocouple Input Terminal The PX-334-K (type 3) Thermocouple Input Terminal provides four Type K thermocouple inputs with full linearization, cold-junction compensation, and LED status.

1

5

LED Error 1

LED Error 2

LED Error 1

LED Error 2 +TC1 +TC2

1

2

+

5

–

6

–TC2 –TC2

2

3

7

+TC3 +TC4

3

4

Terminate shield at signal source

6

For grounded thermocouples differential should not exceed ±2V

7

–TC3 –TC4

8

4

PX-334-K

8

Thermocouple extension wire recommended

PX-334-K

Terminal Specifications Number of Channels Range Resolution Input Type Data Bytes Consumed Connection Method Power Supply Conversion Time Measuring Current Linearity Error Current Consumption (from I/O Bus) Electrical Isolation Heat Dissipation Status Indicators

4 -100 to 1370 °C 0.1 °C per digit Type K thermocouple PX-MOD: 8-bytes input PX-TCP1/TCP2: 16-bytes in/16-bytes out (not used) 2-wire (Thermocouple extension wire recommended) Via I/O Bus Approx. 250ms 5mA typical ± 0.5% (relative to full scale value)

General Specifications

Operating Temp Storage Temp Relative Humidity Environment Air Mounting/ Orientation Restrictions Vibration Shock Noise Immunity Protection Class Weight Dimensions (WxHxD)

Adjacent Mounting on Bus Terminals with Power Contact Adjacent Mounting on Bus Terminals without Power Contact Passes Terminal Bus Power Passes PE Bus Agency Approvals*

0 to 55 °C -25 to 85 °C 5% to 95%, non-condensing No corrosive gases permitted 35mm DIN rail/None Conforms to EN 60068-2-6 Conforms to EN 60068-2-27/ EN 60068-2-29 Conforms to EN 61000-6-2/ EN 61000-6-4 IP20 70g 12 x 100 x 68.8 mm (0.47 x 3.94 x 2.71 in) Yes Yes No No UL/cUL File No. E157382, CE

* obtain the most current agency approval information, see the Agency Approval Checklist section on the specific part number’s web page.

75mA 500Vms (I/O bus/field potential) 1W max 4, red, sensor fault/broken wire

Protos X Installation and I/O Manual, 1st Edition, Rev. C

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

2–51

Page 70

Chapter 2: Specifications

PX-402: 1 Two-channel, 4-20 mA Analog Output Terminal The PX-402 (type 1) Analog Output Terminal provides two electrically isolated, 4-20 2 mA outputs with 12-bit resolution and Run LED status. 3 General Specifications Operating Temp 4 Storage Temp Relative Humidity Environment Air 5 Mounting/ Orientation Restrictions 6 Vibration Shock 7 Noise Immunity Protection Class 8 Weight Dimensions (WxHxD) 9 Adjacent Mounting on Terminal Specifications Bus Terminals with Number of Channels Power Contact 10 Output Ranges Adjacent Mounting on Resolution Bus Terminals without Power Contact Output Type 11 Data Format Passes Terminal Bus Power Passes PE Bus 12 Data Bytes Consumed Agency Approvals* Output Power Source 13 Current Consumption (from Load Voltage) 14 Source Load LED Status Conversion Time LED LED ON LED OFF A Accuracy Green LED: RUN B I/O Bus current Consumption (5V) C Electrical Isolation Heat Dissipation D Status Indicators LED Run 1

1

LED Run 2

32 to 131 °F (0 to 55 °C) -13 to 185 °F (-25 to 85 °C) 5% to 95%, non-condensing No corrosive gases permitted

5

+O1 +O2

1

2

5

+ –

6

Load

35mm DIN rail/None

+24V +24V

3

7

2

6

0V

0V

3

4

Conforms to EN 60068-2-6 Conforms to EN 60068-2-27/ EN 60068-2-29 Conforms to EN 61000-6-2/ EN 61000-6-4 IP20 80g

7

Shld Shld

8

4

8

PX-402

12 x 100 x 68.8 mm (0.47 x 3.94 x 2.71 in)

2 4 to 20 mA 12 bit Single-ended Decimal: 0-32767 PX-MOD: 4-bytes output PX-TCP1/TCP2: 8-bytes out/8-bytes in (not used) 24VDC via terminal power bus 50mA + load

< 500V (short-circuit protected) Approx. 1.5 ms ± 0.5 LSB linearity error, ± 0.5 LSB offset error ± 0.1% of the full scale value

Yes, DC only No

Yes

No UL/cUL File No. E157382, CE

* obtain the most current agency approval information, see the Agency Approval Checklist section on the specific part number’s web page.

Normal Operation

60mA

500Vms (I/O Bus/signal voltage) 1W max

2, see LED Status chart

2–52

Protos X Installation and I/O Manual, 1st Edition, Rev. C

Watchdog-timer overflow if no data transmitted within WD set time.