Page 71

Chapter 2: Specifications

PX-404: Four-channel, 4-20 mA Analog Output Terminal The PX-404 (type 1) Analog Output Terminal provides four electrically isolated, 4-20 mA outputs with 12-bit resolution and Run LED status.

1

Run 1

Run 2

Run 3

Run 4

General Specifications

5

Out 1 Out 2

2

6

1

5

0V

0V

2

3

7

4

8

+ Load –

6

Terminate shield at signal source

Out 3 Out 4

3

7

4

8

0V 0V PX-404

PX-404

Terminal Specifications Number of Channels Output Ranges Resolution Output Type Data Format Data Bytes Consumed Output Power Source Current Consumption (from Load Voltage) Source Load Conversion Time Accuracy I/O Bus current Consumption (5V) Electrical Isolation Heat Dissipation Status Indicators

4 4 to 20 mA 12 bit Single-ended Decimal: 0-32767 PX-MOD: 8-bytes output PX-TCP1/TCP2: 16-bytes out/16-bytes in (not used) 24VDC via terminal power bus 60mA + load < 350V (short-circuit protected) Approx. 4ms ± 0.5 LSB linearity error, ± 0.5 LSB offset error ± 0.1% of the full scale value 20mA

Operating Temp Storage Temp Relative Humidity Environment Air Mounting/ Orientation Restrictions Vibration Shock

Noise Immunity Protection Class Weight Dimensions (WxHxD) Adjacent Mounting on Bus Terminals with Power Contact Adjacent Mounting on Bus Terminals without Power Contact Passes Terminal Bus Power Passes PE Bus Agency Approvals*

32 to 131 °F (0 to 55 °C) -13 to 185 °F (-25 to 85 °C) 5% to 95%, non-condensing No corrosive gases permitted 35mm DIN rail/None Conforms to EN 60068-2-6 Conforms to EN 60068-2-27/ EN 60068-2-29 Conforms to EN 61000-6-2/ EN 61000-6-4 IP20 80g 12 x 100 x 68.8 mm (0.47 x 3.94 x 2.71 in) Yes, DC only No Yes No UL/cUL File No. E157382, CE

* obtain the most current agency approval information, see the Agency Approval Checklist section on the specific part number’s web page.

LED Status LED Green LED: RUN

LED ON Normal Operation

LED OFF

Watchdog-timer overflow if no data transmitted within WD set time.

500Vms (I/O Bus/signal voltage) 1W max 4, see LED Status chart

Protos X Installation and I/O Manual, 1st Edition, Rev. C

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

2–53

Page 72

Chapter 2: Specifications

PX-408: 1 Eight-channel, 4-20 mA Analog Output Terminal The PX-408 (type 1) Analog Output Terminal provides eight electrically isolated, 2 4-20 mA outputs with 12-bit resolution and Run LED status. 3 General Specifications Operating Temp 4 Storage Temp Relative Humidity Environment Air 5 Mounting/ Orientation Restrictions 6 Vibration Shock 7 Noise Immunity Protection Class 8 Weight Dimensions (WxHxD) Adjacent Mounting on 9 Terminal Specifications Bus Terminals with Number of Channels Power Contact Ranges Adjacent Mounting on 10 Output Bus Terminals without Resolution Power Contact Output Type Passes Terminal Bus 11 Data Format Power Passes PE Bus 12 Data Bytes Consumed Agency Approvals* Power Source 13 Output Current Consumption (from Load Voltage) 14 Source Load A Conversion Time LED Status Accuracy LED LED ON LED OFF B I/O Bus current Green LED: Consumption (5V) RUN C Electrical Isolation Heat Dissipation D Status Indicators Run 2 Run 4 Run 6 Run 8

Run 1 Run 3 Run 5 Run 7

1

5

Out 1 Out 2

1

2

6

Out 3 Out 4

2

3

5

7

6

Out 5 Out 6

3

7

Out 7 Out 8

4

8

PX-408

4

32 to 131 °F (0 to 55 °C) -13 to 185 °F (-25 to 85 °C) 5% to 95%, non-condensing No corrosive gases permitted

+

Load

–

35mm DIN rail/None

Terminate shield at signal source

Conforms to EN 60068-2-6 Conforms to EN 60068-2-27/ EN 60068-2-29 Conforms to EN 61000-6-2/ EN 61000-6-4 IP20 80g 12 x 100 x 68.8 mm (0.47 x 3.94 x 2.71 in)

– Connect to same common as terminal power bus

8

PX-408

8 4 to 20 mA 12 bit Single-ended Decimal: 0-32767 PX-MOD: 16-bytes output PX-TCP1/TCP2: 32-bytes out/32-bytes in (not used) 24VDC via terminal power bus 50mA + load

Yes, DC only No

Yes

No UL/cUL File No. E157382, CE

* obtain the most current agency approval information, see the Agency Approval Checklist section on the specific part number’s web page.

< 150V (short-circuit protected) Approx. 8ms ± 0.5 LSB linearity error, ± 0.5 LSB offset error ± 0.1% of the full scale value 25mA

Normal Operation

500Vms (I/O Bus/signal voltage) 1W max 8, see LED Status chart

2–54

Protos X Installation and I/O Manual, 1st Edition, Rev. C

Watchdog error if no data transmitted within WD set time.

Page 73

Chapter 2: Specifications

PX-412: Two-channel, 0 to 10 VDC Analog Output Terminal

1 The PX-412 (type 3) Analog Output Terminal provides two electrically isolated, 2 0 to 10 VDC outputs with 12-bit resolution, common ground potential, and Run LED status. 3 General Specifications Operating Temp 4 Storage Temp Relative Humidity Environment Air 5 Mounting/ Orientation Restrictions 6 Vibration Shock 7 Noise Immunity Protection Class 8 Weight Dimensions (WxHxD) Adjacent Mounting on 9 Terminal Specifications Bus Terminals with Power Contact Number of Channels Adjacent Mounting on 10 Output Ranges Bus Terminals without Resolution Power Contact Output Type Passes Terminal Bus 11 Data Format Power Passes PE Bus Data Bytes Consumed 12 Agency Approvals* Output Power Source 13 Current Consumption (from Load Voltage) 14 Source Load LED Status Conversion Time LED LED ON LED OFF A Accuracy Green LED: RUN B I/O Bus current Consumption (5V) Electrical Isolation C Heat Dissipation Status Indicators D PX-412

LED Run 1

1

LED Run 2

5

+O1 +O2

1

2

+

5

Load

6

–

2

3

7

8

PX-412

7

Shld Shld

4

35mm DIN rail/None

Conforms to EN 60068-2-6 Conforms to EN 60068-2-27/ EN 60068-2-29 Conforms to EN 61000-6-2/ EN 61000-6-4 IP20 85g 12 x 100 x 68.8 mm (0.47 x 3.94 x 2.71 in)

GND GND

3

4

6

32 to 131 °F (0 to 55 °C) -13 to 185 °F (-25 to 85 °C) 5% to 95%, non-condensing No corrosive gases permitted

8

2 0 to 10 VDC 12 bit Single-ended Decimal: 0-32767 PX-MOD: 4-bytes output PX-TCP1/TCP2: 8-bytes out/8-bytes in (not used) 24VDC via terminal power bus 50mA + load

> 5kV (short-circuit protected) Approx. 1.5 ms ± 0.5 LSB linearity error, ± 0.5 LSB offset error ± 0.1% of the full scale value

Yes Yes No

No UL/cUL File No. E157382, CE

* obtain the most current agency approval information, see the Agency Approval Checklist section on the specific part number’s web page.

Normal Operation

Watchdog error if no data transmitted within WD set time.

75mA

500Vms (I/O Bus/signal voltage) 1W max 2, see LED Status chart

Protos X Installation and I/O Manual, 1st Edition, Rev. C

2–55

Page 74

Chapter 2: Specifications

PX-414: 1 Four-channel, 0 to 10 VDC Analog Output Terminal The PX-414 (type 1) Analog Output Terminal provides four electrically isolated, 0 2 to 10 VDC outputs with 12-bit resolution, common ground potential, and Run LED status. 3 General Specifications Operating Temp 4 Storage Temp Relative Humidity Environment Air 5 Mounting/ Orientation Restrictions 6 Vibration Shock 7 Noise Immunity Protection Class 8 Weight Dimensions (WxHxD) Adjacent Mounting on 9 Bus Terminals with Terminal Specifications Power Contact Adjacent Mounting on 10 Number of Channels Bus Terminals without Output Ranges Power Contact Passes Terminal Bus 11 Resolution Output Type Power Data Format Passes PE Bus 12 Data Bytes Consumed Agency Approvals* 13 Output Power Source Current Consumption 14 (from Load Voltage) Source Load LED Status Conversion Time LED LED ON LED OFF A Green LED: RUN B Accuracy I/O Bus current (5V) C Consumption Electrical Isolation Dissipation D Heat Status Indicators 1

5

Run 1

Run 2

Run 3

Run 4

O1

1

2

O2

5

+

Load

6

0V

2

3

7

6

O3

O4

4

8

3

4

0V

32 to 131 °F (0 to 55 °C) -13 to 185 °F (-25 to 85 °C) 5% to 95%, non-condensing No corrosive gases permitted 35mm DIN rail/None

–

Terminate shield at signal source

Conforms to EN 60068-2-6 Conforms to EN 60068-2-27/ EN 60068-2-29 Conforms to EN 61000-6-2/ EN 61000-6-4 IP20 85g 12 x 100 x 68.8 mm (0.47 x 3.94 x 2.71 in)

7

8

PX-414

0V 0V PX-414

Yes, DC only

4 0 to 10 VDC 12 bit Single-ended Decimal: 0-32767 PX-MOD: 8-bytes output PX-TCP1/TCP2: 16-bytes out/16-bytes in (not used) 24VDC via terminal power bus

Yes No

No UL/cUL File No. E157382, CE

* obtain the most current agency approval information, see the Agency Approval Checklist section on the specific part number’s web page.

50mA + load

> 5kV (short-circuit protected) Approx. 1.5 ms ± 0.5 LSB linearity error, ± 0.5 LSB offset error ± 0.1% of the full scale value

Normal Operation

75mA

500Vms (I/O Bus/signal voltage) 1W max

2, see LED Status chart

2–56

Protos X Installation and I/O Manual, 1st Edition, Rev. C

Watchdog error if no data transmitted within WD set time.

Page 75

Chapter 2: Specifications

PX-418: Eight-channel, -10 to +10 VDC Analog Output Terminal

1 The PX-418 (type 1) Analog Output Terminal provides eight electrically isolated, -10 to +10 VDC outputs with 12-bit resolution, common ground potential, and Run LED 2 status. 3 General Specifications Operating Temp 4 Storage Temp Relative Humidity Environment Air 5 Mounting/ Orientation Restrictions 6 Vibration Shock 7 Noise Immunity Protection Class Weight 8 Dimensions (WxHxD) Adjacent Mounting on 9 Bus Terminals with Terminal Specifications Power Contact Adjacent Mounting on 10 Number of Channels Bus Terminals without Output Ranges Power Contact Resolution Passes Terminal Bus 11 Output Type Power Data Format Passes PE Bus 12 Agency Approvals* Data Bytes Consumed 13 Output Power Source Current Consumption (from Load Voltage) 14 LED Status Source Load LED LED ON LED OFF Conversion Time A Green LED: RUN Accuracy B I/O Bus current Consumption (5V) C Electrical Isolation Heat Dissipation D Status Indicators Run Run Run Run

1

5

2

6

Run Run Run Run

1 3 5 7

Out 1 Out 2

1

5

Out 3 Out 4

2

3

7

Out 5 Out 6

3

4

8

PX-418

6 7

Out 7 Out 8

4

2 4 6 8

+

Load

–

Terminate shield at signal source

– Connect to same common as terminal power bus

8

PX-418

32 to 131 °F (0 to 55 °C) -13 to 185 °F (-25 to 85 °C) 5% to 95%, non-condensing No corrosive gases permitted 35mm DIN rail/None

Conforms to EN 60068-2-6 Conforms to EN 60068-2-27/ EN 60068-2-29 Conforms to EN 61000-6-2/ EN 61000-6-4 IP20 85g 12 x 100 x 68.8 mm (0.47 x 3.94 x 2.71 in) Yes, DC only

8 -10 to +10 VDC 12 bit Single-ended Decimal: 0-32767 PX-MOD: 16-bytes output PX-TCP1/TCP2: 32-bytes out/32-bytes in (not used) 24VDC via terminal power bus

No

Yes

No UL/cUL File No. E157382, CE

* obtain the most current agency approval information, see the Agency Approval Checklist section on the specific part number’s web page.

20mA

> 5kV (short-circuit protected) Approx. 8ms ± 0.5 LSB linearity error, ± 0.5 LSB offset error ± 0.1% of the full scale value

Normal Operation

Watchdog error if no data transmitted within WD set time.

20mA

500Vms (I/O Bus/signal voltage) 1W max 8, see LED Status chart

Protos X Installation and I/O Manual, 1st Edition, Rev. C

2–57

Page 76

Chapter 2: Specifications

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

Protos X Modbus Communication

2–58

The Protos X system is designed as a Modbus Server/Client configuration, with Bus Coupler Terminals serving as Servers, and a PLC or PC controller as the Client. Control is through the Client using standard Modbus RTU or TCP protocol via serial or Ethernet communications. Configuration is done through the Protos X Configuration Software. Modbus addresses are automatically assigned based on I/O Terminal type and placement within an assembly. The following Modbus functions are supported with the Protos X Bus Couplers. Supported Modbus Function Codes Function Code

Function

Description

Read Input Status

Read input and output bits as an octet string. Read input bit as an octet string.

Read Holding Registers

Read number of input words.

Read Input Registers

Read number of input words.

5

Force Single Coil

Write output bit.

6 15

Preset Single Register

Writes a value in an output word.

Force Multiple Coils

Writes a number of output bits.

16

Preset Multiple Registers

Writes a number of output words.

1 2 3 4

Read Coil Status

Protos X Installation and I/O Manual, 1st Edition, Rev. C

Page 77

Chapter 2: Specifications

Protos X EtherNet/IP Communication

1 2 3 4 5 6 7 8 9 10 11 12 13 Communication Format Integer 8 bit Unsigned, Integer 16 bit, or Integer 32 bit 14 Assembly Instance Size Input: 100 A Output: 102 Configuration: 100 • IO Messaging: IO Messaging (also called “Implicit Messaging”) is a method of reading B and writing blocks of data without defining the Connection Point and size for each block transfer. The Connection Point, size and transfer rate (RPI) are defined at the beginning C and then the data blocks are transferred at the specified intervals. D

The Protos X EtherNet/IP module uses IO Messaging to communicate as an adapter device. The data that is transported is defined as Input data and Output data. Don’t confuse this type of data with what most PLCs define as Inputs and Outputs. In most PLCs, Inputs are typically associated with an Input module that reads values from real word devices. Outputs are typically associated with an Output module that turns real word devices off and on. In IO Messaging, Input data is data that is sent from the target device back to the Scanner (Originator) or to multiple devices that are listening (multicast messages). Output data is data that is sent from the Adapter (Target) device. This data may or may not be connected to real word devices. That is completely dependent upon the Adapter device. For example, since Protos X is an EtherNet/IP Adapter device, the Input data and Output data is defined in internal registers and does not directly tie to any Input and Output point to the real world. If it is desired to tie these elements to real word devices, that must be accomplished in code in the Scanner device. Protos X EtherNet/IP Communication The terminology associated with EtherNet/IP may be confusing. To better understand this nomenclature, some of the frequently used terms are listed below with a brief descriptive definition. • Scanner: This is the term used to describe the device that initiates the EtherNet/IP sessions. The Scanner is sometimes referred to as the “Originator” as well. In more standard Ethernet terms, the Scanner would often be called the “Client”. • Adapter: This is the device that responds to the EtherNet/IP communications that are initiated by the Scanner. The Adapter is also known as the “Target” as well. Typically, the Adapter is an Ethernet“Server”. • Connection Point (Assembly Instance): A Connection Point value is the “Class Code” reference for a data block. This value is required for access to input and output data in IO Messaging. It is typically defined for each input and output data block by the Adapter device manufacturer.

(4xINT 8 (Byte) or 2xINT 16 or 1xINT 32) + terminals (4xINT 8 (Byte) or 2xINT 16 or 1xINT 32) + terminals 0

Protos X Installation and I/O Manual, 1st Edition, Rev. C

2–59

Page 78

Chapter 2: Specifications

NOTES:

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 2–60

Protos X Installation and I/O Manual, 1st Edition, Rev. C

Page 79 read from a scan by OCR; it may hold reading errors

INSTALLATION AND WIRING

In This Chapter...

Safety Guidelines .......... lec csseteccseeeccsseseeessseesesscsscesssseesesssssesessossesssesesesssseeeeeees

Hardware Installation .................cccccsssssecccccssscccccnssccecsssesecccenesccecesceccecaceesecesensscceeeneses

Page 80

Chapter 3: Installation and Wiring

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

Safety Guidelines

3–2

NOTE: Products with CE marks perform their required functions safely and adhere to relevant standards as specified by CE directives provided they are used according to their intended purpose and that the instructions in this manual are adhered to. The protection provided by the equipment may be impaired if this equipment is used in a manner not specified in this manual. A listing of our international affiliates is available on our Web site: http://www.automationdirect.com WARNING: Providing a safe operating environment for personnel and equipment is your responsibility and should be your primary goal during system planning and installation. Automation systems can fail and may result in situations that can cause serious injury to personnel or damage to equipment. Do not rely on the automation system alone to provide a safe operating environment. You should use external electromechanical devices, such as relays or limit switches, that are independent of the PLC application to provide protection for any part of the system that may cause personal injury or damage. Every automation application is different, so there may be special requirements for your particular application. Make sure you follow all national, state, and local government requirements for the proper installation and use of your equipment.

Plan for Safety The best way to provide a safe operating environment is to make personnel and equipment safety part of the planning process. You should examine every aspect of the system to determine which areas are critical to operator or machine safety. If you are not familiar with PLC system installation practices, or your company does not have established installation guidelines, you should obtain additional information from the following sources. •, The National Electrical Manufacturers Association, located in Washington, D.C. publishes many different documents that discuss standards for industrial control systems. You can order these publications directly from NEMA. Some of these include: 1, General Standards for Industrial Control and Systems

ICS 3, Industrial Systems

ICS 6, Enclosures for Industrial Control Systems

•, The National Electrical Code provides regulations concerning the installation and use of various types of electrical equipment. Copies of the NEC Handbook can often be obtained from your local electrical equipment distributor or your local library. • and State Agencies, many local governments and state governments have additional requirements above and beyond those described in the NEC Handbook. Check with your local Electrical Inspector or Fire Marshall office for information.

Protos X Installation and I/O Manual, 1st Edition, Rev. D