Page 81
Chapter 3: Installation and Wiring
Three Levels of Protection The publications mentioned provide many ideas and requirements for system safety. At a minimum, you should follow these regulations. Also, you should use the following techniques, which provide three levels of system control.
1 • Emergency stop switch for disconnecting system power 2 • Mechanical disconnect for output terminal power • Orderly system shutdown sequence in the control program 3 4 Emergency Stops It is recommended that emergency stop circuits be incorporated into every control system. For maximum safety, these circuits must not be wired into the controller, but should be hardwired 5 externally. The emergency stop switches should be easily accessed by the operator and are generally wired into a master control relay (MCR) or a safety control relay (SCR) that will 6 remove power from the I/O system in an emergency. MCRs and SCRs provide a convenient means for removing power from the I/O system during 7 an emergency situation. By de-energizing an MCR (or SCR) coil, power to the input (optional) and output devices is removed. This event occurs when any emergency stop switch opens. However, the controller continues to receive power and operate even though all its inputs and 8 outputs are disabled. The MCR circuit could be extended by placing a controller fault relay (closed during 9 normal operation) in series with any other emergency stop conditions. This would cause the MCR circuit to drop the I/O power in case of a controller failure (memory error, I/O 10 communications error, etc.). 11 12 13 14 A B C D Guard Line Switch
Emergency Stop
Protos X Installation and I/O Manual, 1st Edition, Rev. D
3–3
Page 82
Chapter 3: Installation and Wiring
Emergency Power Disconnect
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 3–4
A properly rated emergency power disconnect should be used to power the system as a means of removing the power from the entire control system. It may be necessary to install a capacitor across the disconnect to protect against a condition known as “outrush”. This condition occurs when the output Triacs are turned off by powering off the disconnect, thus causing the energy stored in the inductive loads to seek the shortest distance to ground, which is often through the Triacs. After an emergency shutdown or any other type of power interruption, there may be requirements that must be met before the control program can be restarted. For example, there may be specific register values that must be established (or maintained from the state prior to the shutdown) before operations can resume. In this case, you may want to use retentive memory locations, or include constants in the control program to insure a known starting point.
Orderly System Shutdown Ideally, the first level of fault detection is the control program, which can identify machine problems. Certain shutdown sequences should be performed. The types of problems are usually things such as jammed parts, etc. that do not pose a risk of personal injury or equipment damage. WARNING: The control program must not be the only form of protection for any problems that may result in a risk of personal injury or equipment damage.
Jam Detect
Turn off Saw RST RST Retract Arm
Protos X Installation and I/O Manual, 1st Edition, Rev. D
Page 83
Chapter 3: Installation and Wiring
Hardware Installation
1 2 Hardware Configuration A basic Protos X configuration will consist of a bus coupler, discrete or analog I/O terminals, and an end terminal. There are several limitations which must be considered when setting up 3 the hardware. 1) bus coupler has a maximum number of terminals (64) which can be attached to the bus 4 coupler assembly. The PX- MOD and PX-TCP1 allow expansion above the single assembly maximum (64) to the maximum number of terminals (255) by using the bus expansion terminals. The PX-TCP2 does not allow more than the maximum of 64 terminals per 5 assembly. However since the PX-TCP2 has a built in switch, other PX-TCP2 modules can be easily connected for additional terminals. 6 2) bus coupler has 512 Bytes of input mapping and 512 Bytes of output mapping that can be used for terminal I/O points. Each I/O terminal used on the assembly will consume part of the 512 Bytes for I/O mapping. Discrete I/O will consume 1 bit of data per channel. So 7 if you have a two-point input terminal it will consume two bits of one byte of the 512 input bytes allowed. If you have an eight-point output terminal it will consume one byte of the 512 8 output bytes. modules will consume different amounts of I/O mapping depending on which bus coupler is used. For the PX-TCP1 and PX-TCP2, each analog channel will consume four 9 input bytes and four output bytes regardless if it is an input or output terminal. With the PX-MOD bus coupler, each analog channel will only consume 2 input bytes or 2 output bytes. It will consume input bytes if the terminal is an input terminal and output bytes if the terminal 10 is a output terminal. 3) bus coupler has a coupler I/O Bus power budget. This power budget must not be 11 exceeded as there is no internal protection in the coupler and damage to the bus coupler will occur. The specs for each terminal lists the amount of current (in milliamps) it consumes from the I/O Bus. The available I/O Bus power supplied per bus coupler is listed in the individual 12 specs for each bus coupler. Determine the power requirements (power supplied and power consumed) of your system before installing the hardware. See example below. 13 Power Budget Example This example shows how to calculate the power budget for a typical Protos X system. It is 14 constructed using a PX-MOD Bus Coupler and six I/O Terminals. It is recommended you construct a similar table for your system. Follow the steps below to determine your power A budget. 1. a chart similar to the one on the following page, fill in columns 1 and 2. B 2. the specification tables for each module, enter the current supplied and current used by each device (columns 3). C 3. together the current used by the system (row C) for column 3 and put the total in the row labeled “Maximum Current Required” (row D). 4. Subtract the calculated “Maximum Current Required” (row D), from the “Current D Supplied” and place the difference in the row labeled “Remaining Current Available” Before installing the Protos X I/O system, there are several things that need to be taken into consideration. The first of these considerations is the hardware configuration.
(row E).
Protos X Installation and I/O Manual, 1st Edition, Rev. D
3–5
Page 84
Chapter 3: Installation and Wiring
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 3–6
5. “Maximum Current Required” is greater than “Current Supplied” in column 3, the power budget will be exceeded. It will be unsafe to use this configuration, and you will need to restructure your I/O configuration. A
B
Column 1
Column 2
Column 3
Terminal
Terminal Type
I/O Bus (from Coupler)
CURRENT SUPPLIED PX-MOD
C
Bus Coupler
1000mA
4 pt DC Discrete Input 2 pt AC Discrete Input 2 ch RTD Input 2 ch DC Analog Input 4 pt DC Discrete Output 2 ch DC Analog Output
5mA 3mA 60mA 65mA 9mA 75mA
CURRENT REQUIRED PX-144 PX-172-1 PX-322-1 PX-312 PX-244-1 PX-412
D
Maximum Current Required
217mA
E
Remaining Current Available
783mA
Terminal I/O Bus Wiring Options There are different Terminal I/O Bus wiring options per terminal chosen. Some of the terminals offer access to the Terminal I/O Bus power through connection points on the front of the terminals. Usually the lower point count discrete terminals will offer this option. However with terminals having a higher point count, these connection points are not available. If Terminal I/O Bus power is needed for external devices, the PX-949 Power Distribution Terminal provides access through eight connection points to the 24VDC and 0V on the bus. There are also a couple of terminals that can be used to isolate (PX-908) or add an external voltage source to the Terminal I/O Bus. The PX-940 can be used as a 24VDC power supply terminal to connect an external 24VDC power source to the Terminal I/O Bus. The PX-970 can be used as a 120/230 VAC power source to the Terminal I/O Bus. In the assembly, neither of these terminals connect to the terminal power bus on their left side. Instead, they will carry the externally connected power source to the terminals attached on the right as long as the modules support terminal power transfer.
Protos X Installation and I/O Manual, 1st Edition, Rev. D
Page 85
Chapter 3: Installation and Wiring
Terminal Placement It is very important to understand the placement of the terminals in an assembly. Always start the assembly with a Bus Coupler and add terminals from left to right, ending with a Bus End Terminal or Bus Expansion End Terminal, attaching each terminal as shown in the System Installation section which follows. In an assembly there is an I/O Bus, which passes data and power from the Bus Coupler to the Bus End Terminal via six I/O Bus contacts. There is also a Terminal Power Bus, which can provide power to the terminals and/or field devices via the terminal connections. Power is passed via two TM or three contacts located on the sides of the terminals. Not all terminals pass Terminal Bus Power, and the voltages on the bus can vary. Because of this, there are four conditions to take into consideration. These conditions can be found in the General Specifications table for each Chapter 2 for3terminal specifications). TYPE 2 terminal unit (SeeTYPE TYPE 4
1 2 3 Protos X Five Basic Terminal Ty 4 TYPE 1 General Specifications 5 Operating Temp Storage Temp 6 Relative Humidity Environment Air 7 Mounting/ Orientation Restrictions Vibration 8 Shock 9 Noise Immunity Protection Class 10 Weight Dimensions (WxHxD) 11 Adjacent Mounting on Bus Terminals with Power Contact 12 Adjacent Mounting on Bus Terminals without Power Contact a. A djacent Mounting on Bus 13 Terminals with Power Contact: Passes Terminal Bus Power Terminals where Yes is shown 14 can be mounted to the right of a Passes PE Bus terminal that passes power. Some Agency Approvals* terminals will specify DC Only or A AC Only and should only be mounted adjacent to a terminal that passes the same voltage. b. Adjacent Mounting on Bus Terminals without Power Contact: Terminals where Yes is shown B do not use power from the Terminal Power Bus. These would be the Power Feed Terminals, Power Separation Terminal, and some of the Analog I/O Terminals. c. Passes Terminal Bus Power: Terminals where No is indicated, do not pass power through the C Terminal Power Bus. These would be the End Terminals, Power Separation Terminal, and some of the Analog I/O Terminals. D d. Passes PE Bus: Terminals where Yes is shown use PE (earth ground) from the Terminal Power 32 to 131 °F (0 to 55 °C)
13 to 185 °F (-25 to 85 °C)
I/O Bus contacts
I/O Bus contacts
1
5
2
6
3
7
4
Terminal power bus pass thorugh
Terminal power bus contact
Terminal power bus pass thorugh
Terminal power bus contact
8 s terminal passes the wer bus from the precedl to the next terminal and must be mounted to a erminal that passes bus
Terminal PE bus contact
1
5
2
6
3
7
4
8
Terminal power bus pass thorugh Terminal power bus pass thorugh Terminal PE bus pass thorugh
Type 2: This terminal passes the terminal power bus and PE from the preceding terminal to the next terminal and therefore it must be preceded by a terminal that passes both terminal power bus and PE.
I/O Bus contacts
1
5
2
6
3
7
4
8
5% to 95%, non-condensing
No corrosive gases permitted 35mm DIN rail/None 1
5
Conforms to EN 60068-2-6 Conforms to EN 60068-2-27/ 6 2 EN 60068-2-29 Conforms to EN 61000-6-2/ Note, bus EN 61000-6-4 contacts do not exist on
IP20 this module
Note, bus and pass through contacts do not exist on this module
Type 3: This terminal does not pass the terminal power bus or PE and can be preceded by any terminal, however it will interruapt the terminal power bus and PE.
3
7
4
8
55g 12 x 100 x 68.8 mm (0.47 x 3.94 x 2.71 in) Yes, DC only
I/O B cont
PX-970
No
Termi powe bus s
Termi powe bus s
Termi powe bus s
Type 4: This terminal requires exte nal voltage connection and suppli the terminal power bus to termina Yes located to its right. The terminals t right must support the same powe No bus of 120/230 VAC or 24VDC. Th UL/cUL File will No. not E157382, terminal pass CE terminal pow or PE from any preceding termina mark of Automationdirect.com Incorporated
Bus. These would be the Power Feed Terminals and any Discrete I/O Terminals that support 4-wire field devices.
Protos X Installation and I/O Manual, 1st Edition, Rev. D
3–7
Page 86
Chapter 3: Installation and Wiring
System Installation and Removal
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 3–8
Bus Coupler Installation ttach a Bus Coupler onto a 35mm DIN rail and secure it into position using the DIN rail A locking wheel (where applicable) located on the left side of the coupler. Bus Terminal Installation To add a bus terminal, insert unit onto right side of Bus Coupler using the tongue and groove at the top and bottom of the unit, pressing gently until it snaps onto the DIN rail. NOTE: A proper connection cannot be made by sliding the units together on the DIN rail. When correctly installed, no significant gap can be seen between the attached units. Bus connection is made through the six slide contacts located on the upper right side of the units. Add up to 64 bus terminals per Bus Coupler, including a bus end terminal. Insert unit using tongue and groove molded guide and press gently until it becomes firmly seated on DIN rail. Where applicable, rotate Locking Wheel to lock Bus Coupler
Align tab with molded guide
Wiring Connections Wire connection is made through a spring clamp style terminal. This terminal is designed for a single-conductor solid or stranded wire. Wire connection is made by firmly pushing the screwdriver into the screwdriver slot, inserting the wire into the wire slot and removing the screwdriver, locking the wire into position. Screwdriver Slot Wire Slot
Wiring Specifications Spring Clamp Terminals Connection Type Wire Gauge/Wire Cross 28–14 AWG / 0.08–2.5 mm2 Section* Wire Stripping Length 8mm * For Thermocouple terminals, a thermocouple extension wire is recommended
Protos X Installation and I/O Manual, 1st Edition, Rev. D
Page 87
Chapter 3: Installation and Wiring Removing the Bus Coupler and Bus Terminals A locking mechanism prevents individual units from being pulled off. For bus terminal removal, pull the orange DIN rail release tab firmly to unlatch the unit from the rail. If attached to other terminal units, slide unit forward until released. For Bus Couplers with locking wheels, release the DIN rail locking wheel, then pull firmly on DIN rail release tab. Where applicable, rotate Locking Wheel to unlock Bus Coupler
Firmly pull DIN Rail Release Tab to unlatch unit from rail.
Terminal Dimensions and Spacing Requirements Use the following diagrams to make sure the Protos X system can be installed in your application. Protos X terminals require 35mm DIN rail for mounting and there are no orientation restrictions. It is important to check the Protos X dimensions against the conditions required for your application.
PX-TCP2
PX-TCP1, PX-EIP1, PX-MOD
PX-903
PX-902
Standard Terminal
Ethernet TCP/IP COM
1 2 3 4
ERROR WDG
24V 0V
24V 0V Us GNDs
100 mm [3.94”]
I/O RUN I/O ERR
5
1
5
Up
2
6
2
6
GNDp
3
7
3
7
4
8
4
8
TM
DIP
1 2 3 4 5 6 7 8
PE PE
PE PE
.PE
1 2
ON
51 mm [2.01”]
100 mm [3.94”]
+ +
ON
1 2 3 4 5 6 7 8 9 10 ON
TM
PX-TCP2
1
+ +
PX-TCP1
44 mm [1.73”]
PX-903
24.5 mm [.96”]
PX-902
27.5 mm [.96”]
12 mm [.47”]
68.8 mm [2.71”]
Protos X Installation and I/O Manual, 1st Edition, Rev. D
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
3–9
Page 88
Chapter 3: Installation and Wiring
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 3–10
Also, to ensure proper airflow for cooling purposes, units should be spaced, at a minimum, as shown below.
1.4” 35mm min 0.8” 20mm min 1.4” 35mm min
1.4” 35mm min
1.4” 35mm min
Protos X Installation and I/O Manual, 1st Edition, Rev. D
0.8” 20mm min
Page 89
Protos X Configuration
Chapter
4
In This Chapter... Protos X Software Configuration Tool (PG-CFGSW)................................................ 4–2 Protos X Discrete and Analog I/O Mapping ............................................................ 4–9
Page 90
Chapter 4: Protos X Configuration
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
Protos X Software Configuration Tool (PG-CFGSW)
4–2
The PX-CFGSW software configuration tool is used to identify the Modbus addressing, Modbus function codes, and change some of the bus coupler settings. The software tool is a free download from our website or it can be purchased separately on a CD. The Protos X configuration software is a very simple tool to easily manage connections to the Protos X hardware. When the software opens, the Main Screen will have everything you need. The Main Screen graphic below provides a quick overview of the features included with the Protos X configuration software.
Once the Protos X configuration software is open, three menu choices (File, Tools and Help), are available from the Main Menu bar. Some of the items within the menu drop-downs have a keyboard short-cut associated with them that permit quick access. The Main Menu items also have short-cuts for easy access by holding down the “ALT” key on your keyboard and pressing the first letter of the Menu item (i.e., ALT+ F will open the File Menu).
Protos X Installation and I/O Manual, 1st Edition, Rev. D