SOLO Temperature Controller User Manual: Chapter 7: Modbus Communication
Pages 73 to 82 of 87, from SOLO Temperature Controller User Manual
The original document is the PDF (5.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
Filed in the catalog under the AutomationDirect SOLO 8484 /SL8484, Konnect-It SOLO 8484 /SL8484 and Koyo SOLO 8484 /SL8484
Page 73
Modbus Communication
Chapter
7
In this Chapter... Modbus
Connection with the DirectLOGIC Connection with the C-more and C-more Micro HMI
Page 74
Chapter 7: Modbus Communication
Modbus Protocol All of the SOLO controllers have a 2-wire RS-485 serial communication port. The supported protocols are Modbus RTU and Modbus ASCII. The following communication port settings are possible.
Protocol
Modbus RTU
Modbus ASCII
1 to 247
Network Address Baud Rate
2400, 4800, 9600, 19200, 38400 bps
Bit Length
8 bits
7, 8 bits
Parity
None, Even, Odd
Stop Bit
1, 2 bits
Bold Italic text above represent default values in the SOLO controller.
Registers The SOLO controllers support two types of registers that are accessible through the Modbus communication. • Data Registers • Bit Registers
These registers support the following Modbus function codes.
Data Registers 03: Read Holding Registers (maximum limit is read of eight registers) 06: Write Single Register 16: Write Multiple Registers (maximum limit is eight)
Bit Registers 01: Read Coils 02: Read Discrete Inputs (Both Function Code 1 & 2 read the same memory area.) 05: Write SIngle Coil (Write FF00H to set the coil or 0000H to reset the coil.) The following tables show all the Modbus addresses that are accessible through the Modbus network. For the details of each parameter, please refer to Chapter 3. Note: Make sure the On-Line Configuration parameter (Cosh, P3-12) is set to ON. The parameters in the SOLO controllers can be changed by the MODBUS network master only when the parameter is ON. (It is OFF as the factory default.)
7–2
SOLO Temperature Controller User Manual
Page 75
Chapter 7: Modbus Communication
Data Registers ID
Parameter Name
N/A Process Value (PV)
Description If this register has one of the following values, it means there is an error:
8002H = Initial process (Temperature value is not yet available.) 8003H - Temperature sensor is not connected. 8004H = Temperature sensor input error 8006H = Cannot get temperature value, ADC input error 8007H Memory read / write error N/A Set Point Value (SV) Unit is 0.1 (°C or °F) P3-3 Input Range High The data content should not be higher than the temperature range. P3-4 Input Range Low The data content should not be lower than the temperature range. P3-1 Input Type Please refer to the “Temperature Sensor Type and Temperature Range” table for details. P3-5 Control Mode 0 = PID control 1 = On / Off control 2 = Manual control 3 = Ramp / Soak P3-7 Heating / Cooling 0 = Heating 1 = Cooling 2 = Heating / Cooling 3 = Cooling / Heating P1-11 Output 1 Heating Period 0 = 0.5 sec 1 - 99 = 1 - 99 sec P1-12 / Output 1 Cooling Period P1-13 Output 2 Period 0 = 0.5 sec 1 - 99 = 1 - 99 sec
R/W Hexadecimal R
1000
R/W R/W
PLC Modbus Address Decimal (Octal) 44097
V10000
1001 1002
44098 44099
V10001 V10002
R/W
1003
44100
V10003
R/W
1004
44101
V10004
R/W
1005
44102
V10005
R/W
1006
44103
V10006
R/W
1007
44104
V10007
R/W
1008
44105
V10010
P1-4 Proportion Band
0.1 - 999.9
R/W
1009
44106
V10011
P1-5 Integral Time
0 - 9999
R/W
100A
44107
V10012
P1-6 Derivative Time
0 - 9999
R/W
100B
44108
V10013
P1-8 Integral Offset
0.0 - 100.0%
R/W
100C
44109
V10014
P1-7 PD Control Offset P1-14 Proportion Band Coefficient
0.0 - 100.0% 0.01 - 99.99
R/W R/W
100D 100E
44110 44111
V10015 V10016
P1-15 Dead Band
-999 - 9999
R/W
100F
44112
V10017
2nd Ed. Rev D 04/18
SOLO Temperature Controller User Manual
7–3
Page 76
Chapter 7: Modbus Communication
Data Registers cont. ID
Parameter Name
Description
P1-9 Heating Hysteresis P1-10 Cooling Hysteresis P2-11 Output 1 Level
R/W Hexadecimal
0 - 9999 0 - 9999 Unit is 0.1%, write operation is valid under manual tuning mode only. P2-12 Output 2 Level Unit is 0.1%, write operation is valid under manual tuning mode only. P1-17 Analog High 1 Unit = 2.8uA (Current Adjustment Output) 1 Unit = 1.3 mV (Linear Voltage Output) P1-18 Analog Low Adjustment 1 Unit = 2.8uA (Current Output) 1 Unit = 1.3 mV (Linear Voltage Output)
R/W R/W R/W
1010 1011 1012
R/W
P1-16 PV Offset P2-3 Decimal Point Position P1-2 PID Parameter Group
P1-3 Target SV P3-8 Alarm 1 P3-9 Alarm 2 P3-10 Alarm 3 P3-11 System Alarm
P2-4 Alarm 1 High Limit
P2-5 Alarm 1 low Limit
P2-6 Alarm 2 High Limit
P2-7 Alarm 2 Low Limit
7–4
-999 - 999 0-3 0 - 3 = PID parameter group 0 - 3. 4 = PID paramter group auto select Only valid within available range, unit: 0.1 scale 0 = Alarm 1 is disabled. 1- 18 = Alarm type number 0 = Alarm 1 is disabled. 1- 18 = Alarm type number 0 = Alarm 1 is disabled. 1- 18 = Alarm type number 0 = System Alarm is disabled. (default) 1 - 3 = Alarm number to also be used as system alarm. Please refer to the contents of the “Alarm Outputs” for details. Please refer to the contents of the “Alarm Outputs” for details. Please refer to the contents of the “Alarm Outputs” for details. Please refer to the contents of the “Alarm Outputs” for details.
PLC Modbus Address Decimal (Octal) 44113 44114 44115
V10020 V10021 V10022
1013
44116
V10023
R/W
1014
44117
V10024
R/W
1015
44118
V10025
R/W R/W R/W
1016 1017 101C
44119 44120 44125
V10026 V10027 V10034
R/W
101D
44126
V10035
R/W
1020
44129
V10040
R/W
1021
44130
V10041
R/W
1022
44131
V10042
R/W
1023
44132
V10043
R/W
1024
44133
V10044
R/W
1025
44134
V10045
R/W
1026
44135
V10046
R/W
1027
44136
V10047
SOLO Temperature Controller User Manual
Page 77
Chapter 7: Modbus Communication
Data Registers cont. ID
Parameter Name
P2-8 Alarm 3 High Limit
P2-9 Alarm 3 Low Limit
N/A LED Status
N/A Pushbutton Status
P2-10 Lock Mode
N/A Firmware Version P2-2 Starting Ramp / Soak Pattern P3-21 Last Step Number P3-22 Additional Cycles P3-23 Next Pattern Number P3-19 Ramp / Soak SV P3-20 Ramp / Soak Time
Description
R/W Hexadecimal
Please refer to the contents of the “Alarm Outputs” for details. Please refer to the contents of the “Alarm Outputs” for details. Bit 0 = ALM3 Bit 1 = ALM2 Bit 2 = °F Bit 3 = °C Bit 4 = ALM1 Bit 5 = OUT2 Bit 6 = OUT1 Bit 7 = AT Bit 0 = SET Bit 1 = Rotate Bit 2 = Up Bit 3 = Down If the button is pressed, the bit is off. 0 = OFF 1 = Lock Mode 1 11 - Lock Mode 2
R/W
1028
R/W
V1.00 indicates 0x100 0-7
PLC Modbus Address Decimal (Octal) 44137
V10050
1029
44138
V10051
R
102A
44139
V10052
R
102B
44140
V10053
R/W
102C
44141
V10054
R R/W
102F 1030
44144 44145
V10057 V10060
0 - 7 = The last step number R/W of the pattern 0 - 199 R/W
1040~ 1047* 1050~ 1057* 1060~ 1067* 2000~ 203F* 2080~ 20BF*
44161~ 44168* 44177~ 44184* 44193~ 44200* 48193~ 48256* 48321~ 48384*
V10100~ V10107* V10120~ V10127* V10140~ V10147* V20000~ V20077* V20200~ V20277*
0 - 7 = Next pattern number 8 = There is no next pattern. -999 - 9999
R/W
0 - 1500 (15 hours 0 minutes)
R/W
R/W
*Note: The Appendix covers the Modbus address map for the Ramp / Soak Control.
2nd Ed. Rev D 04/18
SOLO Temperature Controller User Manual
7–5
Page 78
Chapter 7: Modbus Communication
Bit Registers ID N/A N/A N/A N/A N/A N/A
Parameter Name AT LED status Output 1 LED status Output 2 LED status Alarm 1 LED status °F LED status °C LED status
N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
Alarm 2 LED status Alarm 3 LED status SET key status Function key status UP key status DOWN key status Event 1 input status Event 2 input status System Alarm Status Ramp / Soak Control status P3-12 On-Line Configuration
N/A Temperature Unit Display Selection P2-3 Decimal Point Display Selection
P1-1 Auto Tuning P2-1 Run / Stop the Control P2-1 Stop the Ramp / Soak Control P2-1 Hold the Ramp / Soak Control
7–6
Description 0 = Off, 1 = On 0 = Off, 1 = On 0 = Off, 1 = On 0 = Off, 1 = On 0 = Off, 1 = On 0 = Off, 1 = On
R/W Hexadecimal R R R R R R
0800 0801 0802 0803 0804 0805
0 = Off, 1 = On R 0 = Off, 1 = On R 0 = Pressed, 1 = Not Pressed R 0 = Pressed, 1 = Not Pressed R 0 = Pressed, 1 = Not Pressed R 0 = Pressed, 1 = Not Pressed R 0 = Disabled, 1 = Enabled R 0 = Disabled, 1 = Enabled R 0 = Off, 1 = On R 0 = Ramp / Soak disabled R 1 = Ramp / Soak enabled 0 = On-Line Configuration is R/W disabled (default) 1 = On-Line Configuration is enabled 0 = °F R/W 1 = °C / Linear input (default) R/W 0 = No decimal 1 = 10ths digit decimal (B, S and R type thermocouples use only 0 decimal display. 0 = Off (default) 1 = On 0 = STOP 1 = RUN (default) 0 = RUN (default) 1 = STOP 0 = RUN (default) 1 = HOLD
PLC Modbus Address Decimal (Octal) 2049 2050 2051 2052 2053 2054
Y0 Y1 Y2 Y3 Y4 Y5
0806 0807 0808 0809 080A 080B 080C 080D 080E 080F
2055 2056 2057 2058 2059 2060 2061 2062 2063 2064
Y6 Y7 Y10 Y11 Y12 Y13 Y14 Y15 Y16 Y17
0810
2065
Y20
0811
2066
Y21
0812
2067
Y22
R/W
0813
2068
Y23
R/W
0814
2069
Y24
R/W
0815
2070
Y25
R/W
0816
2071
Y26
SOLO Temperature Controller User Manual
Page 79
Chapter 7: Modbus Communication
Temperature Sensor Type and Temperature Range Hex - Address 1004 Input Sensor type
Register Value
0 ~ 50 mV Analog Input
17
4 ~ 20 mA Input
16
0 ~ 20 mA Input
15
0 ~ 10 VDC Input
14
0 ~ 5 VDC Input
13
RTD (Pt100) type
12
RTD (JPt100) type
11
Thermocouple TXK type
10
Thermocouple U type
9
Thermocouple L type
8
Thermocouple B type
7
Thermocouple S type
6
Thermocouple R type
5
Thermocouple N type
4
Thermocouple E type
3
Thermocouple T type
2
Thermocouple J type
1
Thermocouple K type
0
2nd Ed. Rev D 04/18
Display
Temperature Range mv ma4 ma0 v10 vs pt jpt txy u l b s r n e t j k
-999 ~ 9999 -999 ~ 9999 -999 ~ 9999 -999 ~ 9999 -999 ~ 9999 -328 ~ 1112°F (-200 ~ 600°C) -4 ~ 752°F (-20 ~ 400°C) -328 ~ 1472°F (-200 ~ 800°C) -328 ~ 932°F (-200 ~ 500°C) -328 ~ 1562°F (-200 ~ 850°C) 212 ~ 3272°F (100 ~ 1800°C) 32 ~ 3092°F (0 ~ 1700°C) 32 ~ 3092°F (0 ~ 1700°C) -328 ~ 2372°F (-200 ~ 1300°C) 32 ~ 1112°F (0 ~ 600°C) -328 ~ 752°F (-200 ~ 400°C) -148 ~ 2192°F (-100 ~ 1200°C) -328 ~ 2372°F (-200 ~ 1300°C)
SOLO Temperature Controller User Manual
7–7
Page 80
Chapter 7: Modbus Communication
Connection with the DirectLOGIC PLC The following DirectLOGIC PLCs can communicate with the SOLO controller. The DL06 or D2-260 PLCs are preferred for connection with the SOLO controller because they have a built in RS-485 communication port support function code 05.
DirectLogic PLC
DL05
Restriction
Port 2 + FA-ISOCON
Can’t write to the bit registers because the DL05 does not support the function code 05. Modbus RTU only Can’t write to the bit registers if installed in the DL05 because the DL05 does not support the function code 05. Modbus RTU only. Modbus RTU only
D0-DCM Port2
DL06
Port 2
D2-250-1
D0-DCM Port2 Port 2 + FA-ISOCON +FA-15HD
D2-260
Port 2
D3-350
Port 2 + FA-ISOCON
D4-450
Port 1 + FA-ISOCON
Figure 1
Instructions Wiring to use Diagram
Com port
Modbus RTU only Can’t write to the bit registers because the D2-250-1 does not support the function code 05.
RX, WX
Figure 1
RX, WX
Figure 2
MRX, MWX
Figure 2
MRX, MWX RX, WX
Figure 2 Figure 3
MRX, MWX Modbus RTU only RX, WX Can’t write to the bit registers because the D3-350 does not support the function code 05. Modbus RTU only. RX, WX Can’t write to the bit registers because the D4-450 does not support the function code 05. Modbus RTU only.
See Chapter 6 for wiring and setup of the FA-ISOCON. This cable is included in the FA-ISCON
FA-ISOCON
FA-24PS +
SOLO controller
-
Belden 8102/9841 RS422/485 cable or equivalent
Figure 2
Solo controller
D0-DCM/D2-260/DL06 Port 2
You will need to make this custom cable Belden 8102/9841 RS422/485 cable or equivalent
7–8
SOLO Temperature Controller User Manual
Figure 2 Figure 4
Figure 5
Page 81
Chapter 7: Modbus Communication
Figure 3
FA-ISOCON
D2-250-1 CPU
+
-
FA-24PS
Connect FA-ISOCON port B to Solo controller using Belden 8102/9841 RS422/485 cable or equivalent
Connect FA-15HD 15-pin connector to D2-250-1 port 2
Connect FA-ISOCON port A to FA-15HD using RJ12 modular cable supplied with FA-ISOCON
SOLO controller
FA-15HD (order seperately)
Figure 4 D3-350 CPU
FA-ISOCON
+
Connect 25-pin connector to D3-350 port 2
-
FA-24PS
Connect FA-ISOCON port B to Solo controller using Belden 8102/9841 RS422/485 cable or equivalent Connect FA-ISOCON port A to 25-pin connector’s RJ12 jack using modular cable supplied with FA-ISOCON
SOLO controller
Universal 25-pin D-sub connector (included with FA-ISOCON)
Figure 5 D4-450 CPU
FA-ISOCON
+
Connect 25-pin connector to D4-450 port 2
-
FA-24PS
Connect FA-ISOCON port B to Solo controller using Belden 8102/9841 RS422/485 cable or equivalent Connect FA-ISOCON port A to 25-pin connector’s RJ12 jack using modular cable supplied with FA-ISOCON
SOLO controller
Universal 25-pin D-sub connector (included with FA-ISOCON)
2nd Ed. Rev D 04/18
SOLO Temperature Controller User Manual
7–9
Page 82
Chapter 7: Modbus Communication
Connection with the C-more and C-more Micro HMI panels Any of the C-more and C-more Micro-Graphic HMI panels can be connected to the SOLO controllers. The C-more HMI panels have a built in RS-485 port. The C-more 3” Micro-Graphic panels require an optional module (EA-MG-SP1). C-more Touch Panel
SOLO Controller
Belden 8102/9841 RS422/485 cable or equivalent
Belden 8102/9841 RS422/485 cable or equivalent EA-MG-SP1
Expansion Connector
C-more Micro-Graphic Panel EA1-S3ML or EA1-S3ML-N and 8 Button Keypad Bezel EA-MG-BZ1
Serial Communications
SOLO Controller
Pin
Signal
Pin
8
1
1
Frame GND
6
LE
Signal
Pin 11
Signal
2
TXD (232C)
7
CTS (232C)
12 TXD– (422/485)
15
9
3
RXD (232C)
8
RTS (232C)
13 Term. Resistor
4
Vcc
9
RXD+ (422/485)
14 do not use
5
Logic GND
10 RXD– (422/485)
15 do not use
TXD+ (422/485)
C-more and C-more Micro-Graphic Panel RS-485 port
7–10
SOLO Temperature Controller User Manual