Manual · AutomationDirect
SOLO Temperature Controller User Manual
Manual87 pagesPDF 5.3 MB
User manual for the AutomationDirect SOLO temperature controllers (SL4824, SL4848, SL4896 and SL9696 series).
Filed with · 3 models
Also filed with these models on the old site
Summary
What is in it
AutomationDirect's user manual for the SOLO single loop, dual output temperature controllers. It covers specifications and model numbers, installation, panel cutouts and terminal wiring for the SL4824, SL4848, SL4896 and SL9696 series, keypad operation and setup parameters, input and output types and alarms, the PID, on/off, ramp/soak and manual control modes, the SL-SOFT configuration software, and Modbus communication with DirectLOGIC PLCs and C-more HMI panels.
Its parts
- Getting Started
- Installation and Wiring
- Keypad Operation and Setup Parameters
- Controller Inputs and Outputs
- Control Modes
- Configuration Software
- Modbus Communication
From the manual
Key facts from this manual
Some pages are scans or cannot be read; this says only what the readable text supports. Each line names its page in the PDF.
AutomationDirect user manual for the SOLO single loop temperature controller, covering the SL4824, SL4848, SL4896 and SL9696 series. It explains installation and wiring, keypad setup, the control modes, the SL-SOFT configuration software and Modbus communication over RS-485. The site files it under SOLO 8484 /SL8484, a designation the manual itself does not print.
- Device
- Single loop, dual output temperature controller for heating and cooling at the same time p. 10
- Control modes
- PID, ON/OFF, Ramp/Soak or Manual, with auto tuning for PID p. 10, 12
- Panel sizes
- 4824: 1/32 DIN 48 x 24 mm; 4848: 1/16 DIN 48 x 48 mm; 4896: 1/8 DIN 48 x 96 mm; 9696: 1/4 DIN 96 x 96 mm (W x H) p. 11
- Inputs
- Thermocouple K, J, T, E, N, R, S, B, L, U, TXK; 3-wire Pt100 or JPt100 RTD; 0-50 mV, 0-5V, 0-10V, 0-20 mA, 4-20 mA p. 12
- Output types
- Relay (R), voltage pulse (V), current (C) or linear voltage (L), by model p. 11, 12
- Relay rating
- SL4824: SPST 3A; SL4848: SPST 5A; SL4896 and SL9696: SPDT 5A; resistive load at 250 VAC or 30 VDC p. 12
- Power
- 100 to 240 VAC 50/60 Hz, or 24 VDC on -D models; 5 VA max p. 11, 12
- Communication
- 2-wire RS-485, Modbus RTU or ASCII slave, 2400 to 38400 bps, address 1 to 247 p. 12, 74
- Display
- 2 line x 4 character 7-segment LED: red process value, green set point p. 10
- Alarm outputs
- Up to three, with 17 alarm types p. 10
- Operating temperature
- 0 to 50 °C (32 to 122 °F); storage -20 to 65 °C; 35% to 80% humidity, non-condensing p. 14
- Input accuracy
- Under ±0.2% of full scale; thermocouple R, S and B max ±3° p. 12
- PC connection
- SL-SOFT software with the USB-485M USB to RS-485 adapter p. 68
- In the box
- Controller, mounting brackets and hardware, 249 ohm resistor, Quick Start Guide p. 10
What this manual walks you through
- Reading the model number (size, outputs, event input, supply) p. 11
- Choosing a mounting location and installation precautions p. 14
- Using the keypad and the three function modes p. 29, 30
- Running manual control of the outputs p. 66
- Understanding error displays and corrective actions p. 66
- Connecting a PC and installing SL-SOFT p. 68, 69
- Setting up Modbus communication and registers p. 74
- Connecting to DirectLOGIC PLCs p. 80
Good to know
- Use only ungrounded thermocouples. p. 12
- The controller is an open-type unit and must be mounted in an enclosure. p. 14
- Current inputs need the supplied 249 ohm resistor installed. p. 12
- A Modbus master can change parameters only when On-Line Configuration (P3-12) is ON; it is OFF from the factory. p. 74
- DL05, D2-250-1, D3-350 and D4-450 PLCs cannot write the bit registers, lacking function code 05. p. 80
Questions this manual answers
What sensors can the SOLO temperature controller read?
Thermocouples (K, J, T, E, N, R, S, B, L, U, TXK), 3-wire Pt100 or JPt100 RTDs, and 0-50 mV, 0-5V, 0-10V, 0-20 mA or 4-20 mA analog signals. p. 12
How do I connect a SOLO controller to a PC?
Use the USB-485M USB to RS-485 adapter with its black 2-wire cable and the SL-SOFT configuration software. p. 68
What does a flashing PV display mean on the SOLO?
The process value is out of range; check the range set by the Input Range High and Input Range Low parameters. p. 66
Which DirectLOGIC PLCs work best with the SOLO?
The DL06 or D2-260, because they have a built-in RS-485 port and support function code 05. p. 80
Contents
Chapters and sections
Each line opens the PDF at its page.
- Chapter 1: Getting Started8
- Chapter 2: Installation and Wiring13
- Chapter 3: Keypad Operation and Setup Parameters28
- Chapter 4: Controller Inputs and Outputs52
- Chapter 5: Control Modes62
- Chapter 6: Configuration Software67
- Chapter 7: Modbus Communication73
61 more lines, from page 83 on
- Appendix: Modbus Address Map for Ramp / Soak Control83
- Manual Overview9
- SOLO Temperature Controller Introduction10
- SOLO Temperature Controller Specifications12
- Ambient Conditions14
- Installation Considerations14
- Mounting Instructions15
- Controller and Panel Cutout Dimensions16
- Safety Information18
- Terminal Identification20
- Display, LED and Keypad29
- Keypad Operation30
- Setup Parameter Listing31
- Regulation Mode Parameters34
- Operation Mode Parameters44
- Initial Setting Parameters46
- Reset to Factory Default51
- Control Input Types53
- Event Inputs54
- Control Output Types55
- Alarm Outputs59
- PID Control63
- On / Off Control64
- Ramp / Soak Control65
- Manual Control66
- Error Display Information66
- PC Connection68
- Software Installation69
- Starting SL-SOFT72
- SL-SOFT Online Help72
- Modbus Protocol74
- Registers74
- Connection with the DirectLOGIC PLC80
- Connection with the C-more and C-more Micro HMI panels82
- Last Step Number84
- Additional Cycles84
- Next Pattern Number84
- Ramp / Soak SV85
- Ramp / Soak Time86
The whole text · 11 parts
Read the manual here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.
- Pages 1 to 71-7
- Chapter 1: Getting Started8-12
- Chapter 2: Installation and Wiring13-27
- Chapter 3: Keypad Operation and Setup Parameters, pages 28 to 3528-35
- Chapter 3: Keypad Operation and Setup Parameters, pages 36 to 4336-43
- Chapter 3: Keypad Operation and Setup Parameters, pages 44 to 5144-51
- Chapter 4: Controller Inputs and Outputs52-61
- Chapter 5: Control Modes62-66
- Chapter 6: Configuration Software67-72
- Chapter 7: Modbus Communication73-82
- Pages 83 to 8783-87
The file