Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a manual · part 6 of 11

SOLO Temperature Controller User Manual: Chapter 3: Keypad Operation and Setup Parameters, pages 44 to 51

Pages 44 to 51 of 87, from SOLO Temperature Controller User Manual

The original document is the PDF (5.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

Filed in the catalog under the AutomationDirect SOLO 8484 /SL8484, Konnect-It SOLO 8484 /SL8484 and Koyo SOLO 8484 /SL8484

Page 44

Chapter 3: Keypad Operation and Setup Parameters

Operation Mode Parameters Press the ‘ button to access these parameters.

r-s

Run / Stop

ID Number P2-1

The Run / Stop parameter is used to control the operational status of the SOLO Controller. The available range varies according to the control mode and the status of the EVENT 1 input. The Event 1 input is available only for the SL4896 and SL9696 series controllers.

PID, On / Off and Manual Control Modes Run

Stop

Event 1 input is off. (Event 1 input is open.)

run

Event 1 input is on. (Event 1 input is closed.)

N/A kstp stop,estp

Ramp / Soak Control Mode Event 1 input is off. (Event 1 input is open.) Event 1 input is on. (Event 1 input is closed.)

run kstp stop estp Phod pstp ptrn

Run

Hold

Stop run phod kstp,pstp

N/A

N/A stop,estp

Run mode Stop mode Stop mode (The controller was in Stop mode when the Event 1 input was closed.) Stop mode (The controller was in Run mode when the Event 1 input was closed.) Ramp / Soak control is on hold. The controller keeps the current Ramp / Soak step number and time. Ramp / Soak control continues when the mode is changed to Run. Ramp / Soak control is stopped. The controller restarts the Ramp / Soak control at the first step when the mode is changed to Run.

Starting Ramp / Soak Pattern

ID Number P2-2

Range: 0 to 7 Select the Ramp / Soak pattern number to start the Ramp / Soak control.

sp

Decimal Point Position

ID Number P2-3

Range: (****) 1 (***.*) 2 (**.**) 3 (*.***) This parameter defines the decimal point position on the PV and SV display.

al1h

Alarm 1 High Limit

ID Number P2-4

This parameter is used to set the high limit for Alarm 1. The range varies according to other parameter values. 2nd Ed. Rev D 04/18

SOLO Temperature Controller User Manual

3–17

Page 45

Chapter 3: Keypad Operation and Setup Parameters al1l

Alarm 1 Low Limit

ID Number P2-5

This parameter is used to set the low limit for Alarm 1. The range varies according to other parameter values.

al2h

Alarm 2 High Limit

ID Number P2-6

This parameter is used to set the high limit for Alarm 2. The range varies according to other parameter values.

al2l

Alarm 2 Low Limit

ID Number P2-7

This parameter is used to set the low limit for Alarm 2. The range varies according to other parameter values.

al3h

Alarm 3 High Limit

ID Number P2-8

This parameter is used to set the high limit for Alarm 3. The range varies according to other parameter values.

al3l

Alarm 3 Low Limit

ID Number P2-9

This parameter is used to set the low limit for Alarm 3. The range varies according to other parameter values.

loC

Lock Mode Range:

ID Number P2-10 off The Lock feature is disabled. loC1 Lock Mode 1 LoC2 Lock Mode 2

Lock Mode 1: All key pad operation is ignored. Press the ; key and the ‘ key at the same time to cancel this lock mode. Lock Mode 2: All key pad operation is ignored except changing the SV. Press the ; key and the ‘ key at the same time to cancel this lock mode.

out1

Output 1 Level

ID Number P2-11

Range: 0.0 to 100 (%) The value for this parameter can be changed in the Manual control mode. In other control modes, this parameter is read-only.

out2

Output 2 Level

ID Number P2-12

Range: 0.0 to 100 (%) This parameter is available when Output 2 is used. Refer to the Heating / Cooling parameter (S-HC, P3-7) to disable / enable Output 2. The value for this parameter can be changed in the Manual control mode. In other control modes, this parameter is read-only.

3–18

SOLO Temperature Controller User Manual

Page 46

Chapter 3: Keypad Operation and Setup Parameters

Initial Setting Parameters Press the ; button for more than three seconds to access these parameters.

Inpt

Input Type

ID Number P3-1

This parameter defines the input signal type.

Thermocouple* Type and Temperature Range

Input Temperature Sensor Type Thermocouple TXK type Thermocouple U type Thermocouple L type Thermocouple B type Thermocouple S type Thermocouple R type Thermocouple N type Thermocouple E type Thermocouple T type Thermocouple J type Thermocouple K type

LED Display txk u l b s r n e t j k

Temperature Range -328 ~ 1472°F (-200 ~ 800°C) -328 ~ 932°F (-200 ~ 500°C) -328 ~ 1562°F (-200 ~ 850°C) 212 ~ 3272°F (100 ~ 1800°C) 32 ~ 3092°F (0 ~ 1700°C) 32 ~ 3092°F (0 ~ 1700°C) -328 ~ 2372°F (-200 ~ 1300°C) 32 ~ 1112°F (0 ~ 600°C) -328 ~ 752°F (-200 ~ 400°C) -148 ~ 2192°F (-100 ~ 1200°C) -328 ~ 2372°F (-200 ~ 1300°C)

RTD Type and Temperature Range

Input Temperature Sensor Type LED Display Temperature Range -328 ~ 1112°F (-200 ~ 600°C) Platinum Resistance (Pt100) pt -4 ~ 752°F (-20 ~ 400°C) Platinum Resistance (JPt100) jpt Voltage Input Type and Input Range

Voltage Input Type 0~50mV Analog Input 0V~10V Analog Input 0V~5V Analog Input

LED Display mv v10 v5

Temperature Range -999 ~ 9999 -999 ~ 9999 -999 ~ 9999

Current Input Type and Input Range

Current Input Type 4~20mA Analog Input 0~20mA Analog Input

LED Display ma4 ma0

Temperature Range -999 ~ 9999 -999 ~ 9999

*Note - Use only ungrounded thermocouples tpun

Temperature Unit

ID Number P3-2

Range: C This parameter is available when the parameter Input Type is a thermocouple or RTD. 2nd Ed. Rev D 04/18

SOLO Temperature Controller User Manual

3–19

Page 47

Chapter 3: Keypad Operation and Setup Parameters tp-h

Input Range High

ID Number P3-3

Range: From the value of Input Range Low to 9999. This parameter defines the high limit of the PV. This is the maximum value of the operational temperature range. In operation, if the PV value is higher than the tp-h value, th PV flashes to indicate an error and the controller outputs shut off. The SV value cannot exceed the tp-h value. This parameter cannot be lower than the Input Range Low parameter (tp-l, P3-4).

tp-l

Input Range Low

ID Number P3-4

Range: From -999 to the value of Input Range High. This parameter defines the low limit of the PV. This is the minimum value of the operational temperature range. In operation, if the PV value is lower than the tp-l value, th PV flashes to indicate an error and the controller outputs shut off. The SV value cannot be set lower than the tp-L value. This parameter cannot be higher than the Input Range High parameter (tp-h, P3-3).

Ctrl

Control Mode Range:

pid onof manu pro6

ID Number P3-5

PID control mode On / Off control mode Manual control mode Ramp / Soak control mode

This parameter is used to select one of the control modes. See Chapter 5 for a complete discription of each control mode.

PAtn

Ramp / Soak Pattern

ID Number P3-6

Range: Ramp / Soak pattern is not selected. 0 to 7 Ramp / Soak pattern number. This parameter is used to select the appropriate Ramp / Soak pattern number for setting up it’s individual parameters. Once a Ramp / Soak pattern number (0-7) is selected, the controller only displays the following pattern setup parameters until the ; key is pressed.

3–20

SOLO Temperature Controller User Manual

Page 48

Chapter 3: Keypad Operation and Setup Parameters

0

Ramp / Soak Pattern Number 2 3 4 5

1

6 7 Step 0 SV sp00 sp10 sp20 sp30 sp40 sp50 sp60 sp70 Step 0 Time ti00 ti10 ti20 ti30 ti40 ti50 ti60 ti70 Step 1 SV sp01 sp11 sp21 sp31 sp41 sp51 sp61 sp71 Step 1 Time ti01 ti11 ti21 ti31 ti41 ti51 ti61 ti71 Step 2 SV sp02 sp12 sp22 sp32 sp42 sp52 sp62 sp72 Step 2 Time ti02 ti12 ti22 ti32 ti42 ti52 ti62 ti72 Step 3 SV sp03 sp13 sp23 sp33 sp43 sp53 sp63 sp73 Step 3 Time ti03 ti13 ti23 ti33 ti43 ti53 ti63 ti73 Step 4 SV sp04 sp14 sp24 sp34 sp44 sp54 sp64 sp74 Step 4 Time ti04 ti14 ti24 ti34 ti44 ti54 ti64 ti74 Step 5 SV sp05 sp15 sp25 sp35 sp45 sp55 sp65 sp75 Step 5 Time ti05 ti15 ti25 ti35 ti45 ti55 ti65 ti75 Step 6 SV sp06 sp16 sp26 sp36 sp46 sp56 sp66 sp76 Step 6 Time ti06 ti16 ti26 ti36 ti46 ti56 ti66 ti76 Step 7 SV sp07 sp17 sp27 sp37 sp47 sp57 sp67 sp77 Step 7 Time ti07 ti17 ti27 ti37 ti47 ti57 ti67 ti77 Last Step Number spx0 spx1 spx2 spx3 spx4 spx5 spx6 spx7 Additional Cycles CyC0 CyC1 CyC2 CyC3 CyC4 CyC5 CyC6 CyC7 Next Pattern Number Lin0 Lin1 Lin2 Lin3 Lin4 Lin5 Lin6 Lin7 Below is an example of a typical Ramp / Soak Pattern. Ramp

08.00

100°

70° 03.00 50° 30°

Soak

POS0

05.00

03.00

02.00

05.00 03.00

POS1

POS2

POS3

POS4

POS5

POS6

SP00 Step00 = 50° SP06 Step06 = 30° SP03 Step03 = 100° ti00 Time00 = 3 hrs 00 min. ti03 Time03 = 3 hrs 00 min. ti06 Time06 = 3 hrs 00 min. SP01 Step01 = 70° psx0 Process Step = 6 SP04 Step04 = 100° ti01 Time01 = 2 hrs 00 min. ti04 Time04 = 8 hrs 00 min. CyCO Cycle times = 0 SP02 Step02 = 70° lin0 Link = OFF SP05 Step05 = 30° ti02 Time02 = 5 hrs 00 min. ti05 Time05 = 5 hrs 00 min.

s-hC

2nd Ed. Rev D 04/18

Heating / Cooling

ID Number P3-7

SOLO Temperature Controller User Manual

3–21

Page 49

Chapter 3: Keypad Operation and Setup Parameters Range:

Heat Output 1 = Heating, Output 2 = Unused Cool Output 1 = Cooling, Output 2 = Unused H1C2 Output 1 = Heating, Output 2 = Cooling h2C1 Output 1 = Cooling, Output 2 = Heating

The Heating / Cooling parameter defines whether one or two outputs will be controlled and what type of control they will perform. Note: Unused Ouput 2 can be used as an Alarm.

ala1 ala2 ala3

Alarm 1 Alarm 2 Alarm 3

ID Number P3-8 ID Number P3-9 ID Number P3-10

Range: 0 to 18 The SOLO controllers support 3 alarm outputs. (The SL4824 series supports only one alarm output.) The Alarm1, Alarm2 and Alarm3 parameters are used to select the alarm type. Refer to Chapter 4 for details.

sala

System Alarm Range:

ID Number P3-11 off System Alarm feature is disabled ala1 Alarm 1 ala2 Alarm 2 ala3 Alarm 3

This parameter defines which Alarm output is used for the system alarm. The System Alarm parameter defines an alarm output if there is an input error or process control failure. Refer to Chapter 4 for complete details.

Initial Setting Communication Parameters

Cosh

On-Line Configuration Range:

port.

on

C-sl C-no

Allow changes to the parameters through the RS-485 port.

Modbus Protocol Range:

ID Number P3-12 off Do not allow changes to the parameters through the RS-485

ID Number P3-13 asC~ Modbus ASCII rtU Modbus RTU

Network Address

ID Number P3-14

Range: 1 to 247 This is the Modbus network address of the SOLO Controller. Note: Each controller on the same network must have a unique Modbus network address

3–22

SOLO Temperature Controller User Manual

Page 50

Chapter 3: Keypad Operation and Setup Parameters

Baud Rate bps

Range:

Bit Length len

ID Number P3-15

2400 2400 bps 4800 4800 bps 9600 9600 bps 19kz 19200 bps 38kz 38400 bps ID Number P3-16

Range: 7, 8

Parity

Prty

ID Number P3-17

Range: None, Even, Odd

Stop Bit

Stop

ID Number P3-18

Range: 1, 2

Initial Setting Ramp / Soak Parameters

SPmn

Ramp / Soak SV

ID Number P3-19

Range: -99.9 to 999.9 This parameter is the set point value (SV) of each Ramp / Soak step. This parameter can be displayed as sp00 to sp77. The third character indicates the Ramp / Soak pattern number (m) and the last digit indicates the step number (n). e.g. sp35 = SV set point value of Step 5 of the Ramp / Soak pattern 3.

timn

Ramp / Soak Time

ID Number P3-20

Range: 00.00 to 15.00 (0 to 15 hours) [Format: hours.minutes] This parameter is the time duration of each Ramp / Soak step. This parameter can be displayed as ti00 to ti77. The third character indicates the Ramp / Soak pattern number (m) and the last digit indicates the step number (n). e.g. TI35 = SV set point value of Step 5 of the Ramp / Soak pattern 3.

PSxn

Last Step Number

ID Number P3-21

Range: 0 to 7 Each Ramp / Soak pattern can have up to seven steps. This parameter is the last step number that is to be used in the Ramp / Soak pattern. When the parameter value is set to 0, the SOLO controller executes only step 0 when the Ramp / Soak pattern is selected. When the value is 7, the controller executes step 0 through step 7 when the Ramp / Soak pattern is selected.

2nd Ed. Rev D 04/18

SOLO Temperature Controller User Manual

3–23

Page 51

Chapter 3: Keypad Operation and Setup Parameters

CYCn

Additional Cycles

ID Number P3-22

Range: 0 to 199 As the default, the SOLO controller executes a Ramp /Soak pattern only once. Use this parameter to set the number of additional times a Ramp / Soak pattern will execute. When the parameter value is set to 0, the SOLO controller executes the Ramp / Soak pattern one time. When this parameter value is 2, the Ramp / Soak pattern will execute two additional times for a total of three executions.

Next Pattern Number linn

ID Number P3-22

Range: 0 to 7, OFF This parameter is used to select a Ramp / Soak pattern that will execute after the current Ramp / Soak pattern is completed. If the parameter value is set to OFF, the SOLO controller will not begin another Ramp / Soak pattern after the current pattern.

Reset to Factory Default Note: Resetting the Temperature Controller back to factory default erases all of the values entered by the user. Record any necessary settings before proceeding Warning: Erasing the user entered values may result in a safety hazard and system malfunction.

The following instructions reset the controller to the factory default.

1 the ‘ button until the parameter loC appears. Use the . button to select loC1. Press the ; button.

2 and hold the , and . buttons simultaneously for one second and release.

3 the ‘ button until the PV display shows pass. Use the , button to change the value on the SV display to 1357. Press the ; button.

4 power on the Controller to reset to factory default mode. All user set values are erased.

3–24

SOLO Temperature Controller User Manual