Page 36
Chapter 3: Keypad Operation and Setup Parameters Event 2 input. This parameter is only displayed when the Event 2 input is on. The Event 2 input is only available on the SL4896 and SL9696 series controllers.
In
Integral Time
ID Number P1-5
This parameter name will be displayed as one of the following. Only the Integral Time for the selected PID Parameter Group (PID0, P1-2) will be displayed when accessing this parameter.
i0 i1 i2 i3 i
Integral Time of PID Parameter Group 0 Integral Time of PID Parameter Group 1 Integral Time of PID Parameter Group 2 Integral Time of PID Parameter Group 3 Integral Time of PID Parameter Group for Event 2 Input
Range: 0 to 9999 (Sec) (For more information about the parameter groups, refer to P1-2 PID Parameter Group.) The Integral Time is a parameter group used for PID control. The controller can store up to four PID parameter groups (PID0, - PID3) for regular operation. One of the PID parameter groups can be selected manually, or the controller selects the PID parameter group that has a Target SV that is the nearest to the SV set by the operator. The parameter i is the Integral Time of the PID parameter group for Event 2 input. This parameter is only displayed when the Event 2 input is on. The Event 2 input is only available on the SL4896 and SL9696 series controllers.
dn
Derivative Time
ID Number P1-6
This parameter name will be displayed as one of the following. Only the Derivative Time for the selected PID Parameter Group (PID0, P1-2) will be displayed when accessing this parameter.
d0 d1 d2 d3 d
Derivative Time of PID Parameter Group 0 Derivative Time of PID Parameter Group 1 Derivative Time of PID Parameter Group 2 Derivative Time of PID Parameter Group 3 Derivative Time of PID Parameter Group for Event 2 Input
Range: 0 to 9999 (Sec) (For more information about the parameter groups, refer to P1-2 PID Parameter Group.) The Derivative Time is a parameter group used for PID control. The controller can store up to four PID parameter groups (PID0, - PID3) for regular operation. One of the PID parameter groups can be selected manually, or the controller selects the PID parameter group that has a
2nd Ed. Rev D 04/18
SOLO Temperature Controller User Manual
3–9
Page 37
Chapter 3: Keypad Operation and Setup Parameters Target SV that is the nearest to the SV set by the operator. The parameter d is the Derivative Time of the PID parameter group for Event 2 input. This parameter is only displayed when the Event 2 input is on. The Event 2 input is only available on the SL4896 and SL9696 series controllers.
pdof
PD Control Offset
ID Number P1-7
Range: 0.0 to 100.0 (%) The PD Control Offset parameter is available when the P or PD control is selected [Integral Time parameter (In, P1-5) is zero]. This parameter defines the offset of the output. When the P or PD control is used, the control cannot stabilize the PV at the SV because the output is zero when the PV is equal to the SV. This parameter modifies the output level when the PV is equal to the SV.
iofn
Integral Offset
ID Number P1-8
This parameter name will be displayed as one of the following.
iof0 iof1 iof2 iof3 iof
Integral Offset of PID Parameter Group 0 Integral Offset of PID Parameter Group 1 Integral Offset of PID Parameter Group 2 Integral Offset of PID Parameter Group 3 Integral Offset of PID Parameter Group for Event 2 Input
Range: 0.0 to 100.0 (%) (For more information about the parameter groups, refer to PID Parameter Group, P1-2.) The Integral Offset parameter is available when the PI or PID control is selected. [Integral Time parameter (In, P1-5) is not zero.] The Auto Tuning process will decide the offset value automatically. If this parameter is not used (iof = 0), the output is zero when the PV is equal to the SV. If the Integral Time parameter (In, P1-5) is used only to eliminate the steady error, it may take a long time to reach the SV because it needs time to accumulate the error. In this case, this parameter is useful. This parameter defines the default output level on start up. It will inprove the speed that the PV reaches the SV. The parameter iof is the Integral Offset of the PID parameter group for Event 2 input. This parameter is only displayed when the Event 2 input is on. The Event 2 input is only available on the SL4896 and SL9696 series controllers.
3–10
SOLO Temperature Controller User Manual
Page 38
Chapter 3: Keypad Operation and Setup Parameters hts
Heating Hysteresis
ID Number P1-9
Range: 0.0 to 999.9 The Heating Hysteresis parameter defines the amount that the PV must go below the SV before the output turns on. This parameter is available only for On / Off control with an output programmed for heating. Output ON hts Heating Hysteresis
OFF
PV SV
Cts
Cooling Hysteresis
ID Number P1-10
Range: 0.0 to 999.9 The Cooling Hysteresis parameter defines the amount that the PV must go above the SV before the output turns on. This parameter is available only for On / Off control with an output programmed for cooling. Output ON
Cts Cooling Hysteresis
OFF
PV SV htpd
Output 1 Heating Period
ID Number P1-11
Range: 0.5 to 99 seconds The Output 1 Heating parameter defines one output period or the duration of one on / off cycle for Output 1.
HTPD Output 1 Heating Period
This parameter is available when Output 1 is programmed as a heating output in the PID or Ramp / Soak mode.
Clpd
Output 1 Cooling Period
ID Number P1-12
Range: 0.5 to 99 seconds The Output 1 Cooling parameter defines one output period or the duration of one on / off cycle for Output 1.
ClPD Output 1 Cooling Period
This parameter is available when Output 1 is programmed as a cooling output in the PID or Ramp / Soak mode. 2nd Ed. Rev D 04/18
SOLO Temperature Controller User Manual
3–11
Page 39
Chapter 3: Keypad Operation and Setup Parameters
Output 2 Period
HCpd
ID Number P1-13
Range: 0.5 to 99 seconds The Output 1 Cooling parameter defines one output period or the duration of one on / off cycle for Output 2.
hCPD Output 2 Period This parameter is available when Output 2 is programmed as a heating or cooling output in the PID or Ramp / Soak mode.
Proportion Band Coefficient
Coef
ID Number P1-14
Range: 0.01 to 99.99 This Proportion Band Coefficient parameter is available when a dual output mode (heating and cooling) is selected. This parameter allows the second output control to have a different proportional setting than the first output control. The first output control proportional band setting is multiplied by this parameter to create a proportional band setting for the second output control. (First Output) Proportion Band * Proportion Band Coefficient = Second Proportional Band (P n, P1-4)
dead
(Coef , P1-14)
Dead Band
ID Number P1-15
Range: The range varies according to the Decimal Point Position (SP, P2-3). 0 -99 to 999 sp dead
1 2 3 -99.9 to 999.9 -9.99 to 99.99 -.999 to 9.999
The dead band zone is the area around the SV where the output is not effected by the proportional control value (PV). For PID control, as long as the PV remains within the dead band zone, the output is not affected by the proportional control. The integral and derivative controls ignore the dead band setting and may cause the output to be on within the dead band zone. dead Dead band: dead band width=positive
Output
Heating 0
Cooling dead
Output
PV
Set point
Dual Control PID control positive dead band
Dead band: dead band width=negative
Heating 0
Cooling
PV
Set point
Dual Control PID control negative dead band
For On / Off type control the Dead Band parameter defines the area around the SV where the output remains off. The PV must go beyond the dead band range in order for either output 1 or output 2 to turn on.
3–12
SOLO Temperature Controller User Manual
Page 40
Chapter 3: Keypad Operation and Setup Parameters dead Dead band hts Heating hysteresis
Cts
Cooling hysteresis
ON Heating
Cooling
OFF
PV Set point
Dual Loop On / Off control output operation tpof
PV Offset
ID Number P1-16
Range: The range varies according to the Decimal Point Position (SP , P2-3).
SL4824 tpof 0~50 mV 4~20 mA 0~20 mA 0V~10V 0V~5V (Pt100) (JPt100) Thermocouple type TXK Thermocouple type U Thermocouple type L Thermocouple type B Thermocouple type S Thermocouple type R Thermocouple type N Thermocouple type E Thermocouple type T Thermocouple type J Thermocouple type K
2nd Ed. Rev D 04/18
0 (****) 0 0 0 0 0 0 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Decimal Position 1 (*.***) 2 (**.**) 0.0 00.00 0.0 00.00 0.0 00.00 0.0 00.00 0.0 00.00 0.0 n/a 0.0 n/a 0.0 n/a 0.0 n/a 0.0 n/a n/a n/a n/a n/a n/a n/a 0.0 n/a 0.0 n/a 0.0 n/a 0.0 n/a 0.0 n/a
SOLO Temperature Controller User Manual
3 (***.*) 0.000 n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a
3–13
Page 41
Chapter 3: Keypad Operation and Setup Parameters SL4848 / SL4896 / SL9696 tpof 0~50 mV 4~20 mA 0~20 mA 0V~10V 0V~5V (Pt100) (JPt100) Thermocouple type TXK Thermocouple type U Thermocouple type L Thermocouple type B Thermocouple type S Thermocouple type R Thermocouple type N Thermocouple type E Thermocouple type T Thermocouple type J Thermocouple type K
0 (****) 0 0 0 0 0 0 0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
Decimal Position 1 (*.***) 2 (**.**) 0.0 00.00 0.0 00.00 0.0 00.00 0.0 00.00 0.0 00.00 0.0 n/a 0.0 n/a 0.0 n/a 0.0 n/a 0.0 n/a n/a n/a n/a n/a n/a n/a 0.0 n/a 0.0 n/a 0.0 n/a 0.0 n/a 0.0 n/a
3 (***.*) 00.00 00.00 00.00 00.00 00.00 n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a
This parameter is used to add an offset value to the PV.
CrHi
Analog High Adjustment
ID Number P1-17
The Analog High Adjustment parameter is used to adjust the actual analog output value when the output is 100%. To set up this parameter, place the SOLO controller in the Manual control mode and set the Output 1 Level (out1, P2-11) to 100% then increase / decrease the parameter value to get the desired analog output value. The tables below show the approximate Analog High Adjustment values needed to obtain the desired output value. The actual controller output will vary. Check and adjust the values until the desired output level is achieved.
3–14
SOLO Temperature Controller User Manual
Page 42
Chapter 3: Keypad Operation and Setup Parameters Current Output 0mA 1mA 2mA 3mA 4mA 5mA 6mA 7mA Crhi -7198 -6838 -6478 -6118 -5758 -5398 -5038 -4678 8mA 9mA 10mA 11mA 12mA 13mA 14mA 15mA Crhi -4319 -3959 -3599 -3239 -2879 -2519 -2159 -1799 16mA 17mA 18mA 19mA 20mA Crhi -1440 -1080 -720 -360 0
Voltage Output
Crhi Crhi
0V 1V 2V 3V 4V 5V 6V 7V -7589 -6830 -6071 -5312 -4553 -3795 -3036 -2277 8V 9V 10V -1518 -758 0
Note: When decreasing the parameter value for Analog High Adjustment below -1999, the SOLO display will “roll over” to -0, indicating a value of -2000. Two “roll overs” equal a value of -4000 and so forth. For example, to enter a value of -5312 for Analog High Adjustment, hold the , button until the SOLO display “rolls over” two times and the display reads -1312. Note: The output may be saturated before it reaches the minimum or maximum value.
This parameter is available when Output 1 is Current or Linear Voltage.
Crlo
Analog Low Adjustment
ID Number P1-18
The Analog Low Adjustment parameter is used to adjust the actual analog output value when the output is 0%. To set up this parameter, place the SOLO controller in the Manual control mode and set the Output 1 Level (out1, P2-11) to 0% then increase / decrease the parameter value to get the desired analog output value. The tables below show the approximate Analog Low Adjustment values needed to obtain the desired output value. The actual controller output will vary. Check and adjust the values until the desired output level is achieved.
Current Output 0mA 1mA 2mA 3mA 4mA 5mA 6mA 7mA Crlo -1440 -1080 -720 -360 0 360 720 1080 8mA 9mA 10mA 11mA 12mA 13mA 14mA 15mA Crlo 1440 1799 2159 2519 2879 3239 3599 3959 16mA 17mA 18mA 19mA 20mA Crlo 4319 4678 5038 5398 5758
2nd Ed. Rev D 04/18
SOLO Temperature Controller User Manual
3–15
Page 43
Chapter 3: Keypad Operation and Setup Parameters Voltage Output
Crlo Crlo
0V 1V 2V 3V 4V 5V 6V 7V 0 759 1518 2277 3036 3795 4553 5312 8V 9V 10V 6071 6830 7589
Note: When increasing the parameter value of Analog Low Adjustment above 9999, the SOLO display will “roll up” to 0000, indicating a value of 10000. For example, to enter a value of 10625 for Analog Low Adjustment, hold the ’. button until the SOLO display reads 0625. Note: The output may be saturated before it reaches the minimum or maximum value.
This parameter is available when Output 1 is Current or Linear Voltage.
3–16
SOLO Temperature Controller User Manual