Page 28
Keypad Operation and Setup Parameters
Chapter
3
In this Chapter... Display, LED and Keypad Setup Parameter Regulation Mode Operation Mode Initial Setting Reset to Factory
Page 29
Chapter 3: Keypad Operation and Setup Parameters
Display, LED and Keypad The SOLO temperature controller has a two color seven segment LED display, four types of LED status indicators and four function buttons.
PV PV Display
SV Display
SV ALM1, ALM2, ALM3, LEDs
OUT1, OUT2 LEDs
°F, °C LEDs
Auto Tuning LED
AT
OUT1 OUT2 ALM1 ALM2 ALM3
F
Down Button
Rotate Button SET Button
C
SET
Up Button
SOLO 9696 PV Display The Process Value Display. Displays the value from the input source or the parameter source.
SV Display The Set Value Display. Displays the set point of the process, the parameter operation read value, manipulated variable, or the set value of the parameter.
AT LED Indicator Auto Tuning LED flashes when the Auto Tuning operation is ON.
OUT1, OUT2 LED Indicators Output 1 and Output 2 LED indicators light when the output is ON.
°F, °C LED Indicators Temperature unit LED. °C: Celsius, °F: Fahrenheit
ALM1, ALM2, ALM3 LED Indicators Alarm output LED indicators light when appropriate alarm is activated. ALM2 and ALM3 indicators are available on series SL4896 and SL9696 only.
3–2
SOLO Temperature Controller User Manual
Page 30
Chapter 3: Keypad Operation and Setup Parameters
Keypad Operation Function Buttons SET Button Press the SET button to select the desired function mode and confirm the setting value.
Rotate Button Press the Rotate button to select parameters within the function mode.
Down Button Press the Down button to decrease values displayed on the SV display. Hold down this button to speed up the decrement.
Up Button Press the Up button to increase values displayed on the SV display. Hold down this button to speed up the increment.
Initial Power up When power is first applied to the temperature controller, the module information splash screen appears. This screen shows the firmware version on the PV display and the two output types for that particular model on the SV display. After three seconds, the controller will automatically proceed to the Operation mode main screen.
Keypad Operation The temperature controller has three function modes: Initial Setting mode, Operation mode and Regulation mode. Press and hold the SET button for three seconds to go into the Initial Setting mode. Press the SET button for less than three seconds to access the Regulation mode. Press the Rotate button while inside any of the three function modes to scroll through the individual parameters for each function mode. Use the Up and Down buttons to change the individual parameter values. Pressing the SET button saves the parameter values. Press the SET button again to return the controller to the Operation mode main screen. SET Hold for 3 sec.
SET Press for less than 3 sec.
Regulation Mode
SET
SET
2nd Ed. Rev D 04/18
Initial Setting Mode
Operation Mode
Regulation Parameters
Operation Parameters
Initial Setting Parameters
Page: 3–7
Page: 3–17
Page: 3–19
SOLO Temperature Controller User Manual
3–3
Page 31
Chapter 3: Keypad Operation and Setup Parameters
Setup Parameter Listing Regulation Mode Parameters Press the ; button to access these parameters. Regulation Mode Parameter Availablity
Cooling / Heating
Heating / Cooling
Heating
Ramp / Soak
Manual
ON /OFF
PID
Cooling
Heating / Cooling
Control Mode
LV(E)
LR(E)
CV(E)
CR(E)
At Auto Tuning
VV(E)
Display Parameter Name
P1-1
VR(E)
ID #
RR(E)
Controller Type
- - - 4 4 4 4 P1-2 pidn PID Parameter Group 4 4 4 4 4 4 4 4 - - 4 4 4 4 4 P1-3 4 4 4 4 4 4 4 4 - - 4 4 4 4 4 svn Target SV P1-4 4 4 4 4 4 4 4 4 - - 4 4 4 4 4 pn Proportion Band P1-5 4 4 4 4 4 4 4 4 - - 4 4 4 4 4 in Integral Time P1-6 Derivative Time 4 4 4 4 4 4 4 4 - - 4 4 4 4 4 dn P1-7 PDof PD Control Offset 4 4 4 4 4 4 4 4 - - 4 4 4 4 4 P1-8 iofn Integral Offset 4 4 4 4 4 4 4 4 - - 4 4 4 4 4 P1-9 4 4 4 4 4 4 4 - 4 - - 4 - 4 4 hts Heating Hysteresis P1-10 4 4 4 4 4 4 4 - 4 - - - 4 4 4 Cts Cooling Hysteresis P1-11 htpd Output 1 Heating Period 4 4 4 4 4 4 4 4 - 4 4 4 - 4 P1-12 Clpd Output 1 Cooling Period 4 4 4 4 4 4 4 4 - 4 4 - 4 - 4 P1-13 hCpd Output 2 Period 4 4 4 4 4 4 4 4 - 4 4 - - 4 4 P1-14 Coef Proportion Band Coefficient 4 4 4 4 4 4 4 4 - - 4 - - 4 4 P1-15 dead Dead Band 4 4 4 4 4 4 4 4 4 - 4 - - 4 4 P1-16 tpof PV Offset P1-17 Crhi Analog High Adjustment P1-18 Crlo Analog Low Adjustment
3–4
4 4 4 4 4 4 4 4
4 4 4 4 4 4 4 4 4 4 4 4 4 4 4
- - - 4 4 4 4 4 4 4 4 4 4 4 4 - - - 4 4 4 4 4 4 4 4 4 4 4 4
SOLO Temperature Controller User Manual
Page 32
Chapter 3: Keypad Operation and Setup Parameters
Operation Mode Parameters Press the • button to access these parameters. Operation Mode Parameter Availablity
P2-1 P2-2 P2-3 r-s Run / Stop
Cooling / Heating
Heating / Cooling
Heating
Ramp / Soak
Manual
ON /OFF
PID
Cooling
Heating / Cooling
Control Mode
LV(E)
LR(E)
CV(E)
CR(E)
VV(E)
Display Parameter Name
VR(E)
ID #
RR(E)
Controller Type
4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 ptrn Starting Ramp / Soak Pattern 4 4 4 4 4 4 4 - - - 4 4 4 4 4 sp Decimal Point Position
4 4 4 4 4 4 4 4 4 4 4 4 4 4 4
P2-4 al1h Alarm 1 High Limit
4 4 4 4 4 4 4 4 4 4 4 4 4 4 4
P2-5 al1l Alarm 1 Low Limit
4 4 4 4 4 4 4 4 4 4 4 4 4 4 4
P2-6 al2h Alarm 2 High Limit
4 4 4 4 4 4 4 4 4 4 4 4 4 4 4
P2-7 al2l Alarm 2 Low Limit
4 4 4 4 4 4 4 4 4 4 4 4 4 4 4
P2-8 al3h Alarm 3 High Limit
4 4 4 4 4 4 4 4 4 4 4 4 4
P2-9 al3l Alarm 3 Low Limit
- 4 4 4 4 4 4 4 4 4 4 4 4 4 - -
P2-10 loC Lock Mode
4 4 4 4 4 4 4 4 4 4 4 4 4 4 4
P2-11 out1 Output 1 Level
4 4 4 4 4 4 4 4 4 4 4 4 4 4 4
P2-12 out2 Output 2 Level
4 4 4 4 4 4 4 4 4 4 4
2nd Ed. Rev D 04/18
- - 4 4
SOLO Temperature Controller User Manual
3–5
Page 33
Chapter 3: Keypad Operation and Setup Parameters
Initial Setting Parameters Press the ; button for more than three seconds to access these parameters.
Initial Setting Mode Parameter Availablity
P3-1 tpun Temperature Unit P3-3 tp-h Input Range High P3-4 tp-l Input Range Low P3-5 Ctrl Control Mode P3-6 Patn Ramp / Soak Pattern* P3-7 s-hC Heating / Cooling P3-8 ala1 Alarm 1 P3-9 ala2 Alarm 2 P3-10 ala3 Alarm 3 P3-11 sala System Alarm P3-12 Cosh On-Line Configuration P3-13 C-SL Modbus Protocol P3-14 C-no Network Address P3-15 bps Baud Rate P3-16 LEn Bit Length P3-17 Prty Parity P3-18 Stop Stop Bit P3-2
Cooling / Heating
Heating / Cooling
Heating
Ramp / Soak
Manual
ON /OFF
PID
Cooling
Heating / Cooling
Control Mode
LV(E)
LR(E)
CV(E)
CR(E)
VV(E)
Display Parameter Name inpt Input Type
VR(E)
ID #
RR(E)
Controller Type
4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4
*Once a Ramp / Soak pattern (P3-6) is selected, the following parameters are available.
4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 -
P3-19 spmn Ramp / Soak SV
4 4 4 4 4 4 4
P3-20 timn Ramp / Soak Time
4 4 4 4 4 4 4 psxn Last Step Number CYCn Additional Cycles P3-23 linn Next Pattern Number P3-21 P3-22
3–6
SOLO Temperature Controller User Manual
- - 4 4 4 4 4 - - 4 4 4 4 4 - - 4 4 4 4 4 - - 4 4 4 4 4 - - 4 4 4 4 4
Page 34
Chapter 3: Keypad Operation and Setup Parameters
Regulation Mode Parameters Press the ; button to access these parameters.
At
Auto Tuning
ID Number P1-1
Range: - Auto Tuning activated Off - Auto Tuning deactivated When this parameter is set to On, the controller begins auto tuning. After auto tuning is complete, the parameter is set to Off automatically. If this parameter is set to Off during the auto tuning process, the controller stops the auto tuning process immediately and does not change any PID parameter.
PIDn
PID Parameter Group
ID Number P1-2
This parameter name will be displayed as one of the following.
PID0 PID Parameter Group 0 PID1 PID Parameter Group 1 PID2 PID Parameter Group 2 PID3 PID Parameter Group 3 PID4 PID Parameter Group Auto Select PID PID Parameter Group for Event 2 Input Range: PID0 to PID4 The SOLO controller can store up to 4 PID parameter groups (PID0 PID3) for regular operation. The PID Parameter Group parameter sets which PID group (PID0 - PID3) to use for control. The SV display shows the Target SV assigned to the PID group. (For more information about the Target SV, refer to P1-3 Target SV) When PID4 is selected as the PID parameter group, the controller automatically chooses the one PID parameter group (PID0 - PID3) that has a Target SV that is the nearest to the SV set by the operator and uses that group for control.
PID is a special PID parameter group for the SL4896 and SL9696 series controllers Event inputs. This is the PID group that the controller uses when the Event 2 input is on. To configure the PID parameter for this parameter group, the Event 2 input must be active.
SVn
Target SV
ID Number P1-3
This parameter name will be displayed as one of the following. Only the Target SV for the selected PID Parameter Group (PID0, P1-2) will be displayed when accessing this parameter.
2nd Ed. Rev D 04/18
SOLO Temperature Controller User Manual
3–7
Page 35
Chapter 3: Keypad Operation and Setup Parameters
SV0 SV1 SV2 Sv3 sv
Target SV of PID Parameter Group 0 Target SV of PID Parameter Group 1 Target SV of PID Parameter Group 2 Target SV of PID Parameter Group 3 Target SV of PID Parameter Group for Event 2 Input
Range: -99.9 to 999.9 (For more information about the parameter groups, refer to P1-2 PID Parameter Group.) The Target SV is the setting value that each parameter group works toward. When the Target SV is the closest to the SV of the PID groups, this value is used to select which tuning parameters are used by the controller. The controller can store up to four PID parameter groups (PID0, - PID3) for regular operation. One of the PID parameter groups can be selected manually, or the controller selects the PID parameter group that has a Target SV that is the nearest to the SV set by the operator. If there are two or more PID parameter groups that have SV values equally close to the current PV, the controller uses the lowest number parameter group (eg. If parameter groups 0 - 3 have the same Target SV, the controller uses the parameter group 0). The parameter SV is the Target SV of the PID parameter group for Event 2 input. This parameter is only displayed when the Event 2 input is on. The Event 2 input is only available on the SL4896 and SL9696 series controllers.
Pn
Proportion Band
ID Number P1-4
This parameter name will be displayed as one of the following. Only the Proportion Band for the selected PID Parameter Group (PID0, P1-2) will be displayed when accessing this parameter.
p0 p1 p2 p3 p
Proportion Band of PID Parameter Group 0 Proportion Band of PID Parameter Group 1 Proportion Band of PID Parameter Group 2 Proportion Band of PID Parameter Group 3 Proportion Band of PID Parameter Group for Event 2 Input
Range: 0.1 to 999.9 (For more information about the parameter groups, refer to P1-2 PID Parameter Group.) The Proportion Band is a parameter group used for PID control. The controller can store up to four PID parameter groups (PID0, - PID3) for regular operation. One of the PID parameter groups can be selected manually, or the controller selects the PID parameter group that has a Target SV that is the nearest to the SV set by the operator. The parameter P is the Proportion Band of the PID parameter group for
3–8
SOLO Temperature Controller User Manual