The text of a manual · part 3 of 11
SOLO Temperature Controller User Manual: Chapter 2: Installation and Wiring
Pages 13 to 27 of 87, from SOLO Temperature Controller User Manual
The original document is the PDF (5.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
Filed in the catalog under the AutomationDirect SOLO 8484 /SL8484, Konnect-It SOLO 8484 /SL8484 and Koyo SOLO 8484 /SL8484
Page 13
Installation and Wiring
Chapter
2
In this Chapter... Ambient Conditions Installation Mounting Controller and Panel Cutout Safety Terminal SL4824 Series SL4824 Series SL4848 Series SL4848 Series SL4896 Series SL4896 Series SL9696 Series SL9696 Series
Page 14
Chapter 2: Installation and Wiring
Ambient Conditions Ambient Conditions 32°F to 122°F (0°C to 50°C) Ambient Temperature Range -4°F to 149°F (-20°C to 65°C) Storage Temperature Range 35% to 80% (non-condensing) Relative Humidity 2000m or lower above sea level, Altitude keep from corrosive gas, liquid and dust Degree 2 - Normally, only non-conductive pollution occurs. Pollution Degree Temporary conductivity caused by condensation is to be expected 10 to 55 Hz, 10 m/s2 for 10 min, each in X, Y and Z directions Vibration Resistance Max. 300 m/s2, 3 times in each 3 axes, 6 directions Shock Resistance IP65: Complete protection against dust and low pressure spraying IP Rating water from all directions when mounted in a suitable enclosure.
Installation Considerations Improper installation of the controller will greatly reduce its life. Be sure to observe the following precautions when selecting a mounting location:
Warning: Failure to observe these precautions may damage the controller and void the warranty! • not mount the controller near heat-radiating elements or in direct sunlight. •D o not install the controller in a place subjected to high temperature, high humidity, excessive vibration, corrosive gases or liquids, or airborne dust or metallic particles. •D o not restrict the air flow to the vent opening on the controller housing •T his controller is an open-type unit and must be placed in an enclosure to ensure proper operation and maintain the IP65 rating.
2–2
SOLO Temperature Controller User Manual
Page 15
Chapter 2: Installation and Wiring
Mounting Instructions SL4824 Series Series SL4824 temperature controllers should be mounted through a cutout in an enclosure or panel by using the dimensions shown on page 2–4.The directions for mounting the controller through a cutout are... 1. Insert the temperature controller through the panel cutout. 2. Slide the M3X0.5 nut into the opening in the top of the mounting bracket and insert the M3X0.5 X 30mm mounting screw in the mounting bracket. 3. Slide the mounting bracket onto the controller and push the mounting bracket forward until the bracket stops. 4. Tighten the M3X0.5 X 30mm screw to secure temperature controller in place. 4
3 1
2
SL4848, SL4896, SL9696 Series Series SL4848, SL4896 and SL9696 temperature controllers should be mounted through a cutout in an enclosure or panel by using the dimensions shown on page 2–4 andpage 2–5. The directions for mounting the controller through a cutout are... 1. Insert the temperature controller through the panel cutout. 2. Slide the M3X0.5 nut into the opening in the top of the mounting bracket and insert the M3X0.5 X 30mm mounting screw in the mounting bracket. 3. Insert the mounting bracket into the mounting groove at the top and bottom of the controller, and push the mounting bracket forward until the bracket stops. 4. Tighten top and bottom screws evenly to secure temperature controller in place. 2
4 3
1
2nd Ed. Rev D 04/18
SOLO Temperature Controller User Manual
2–3
Page 16
Chapter 2: Installation and Wiring
Controller and Panel Cutout Dimensions SL4824 Series Minimum Cutout and Spacing
0.86” (21.85 mm)
0.94” (24.0 mm)
SOLO 4824
1.58” (Min.) [40.0 mm]
1.76” (44.75 mm)
2.56” (Min.) [65.0mm]
0.87" [22.0 mm]
SV
PV
AT
OUT1
OUT2
ALM
F
1.76” +0.02 -0 [44.8 mm] +0.6 -0
C
+0.02 -0 +0.6 -0
SET
0.13” (3.40 mm)
1.89” (48.0 mm)
3.93” (99.8 mm)
SL4848 Series
Minimum Cutout and Spacing 2.56" (Min.) [65.0 mm]
SOLO 4848
OUT1
OUT2
ALM
SET
1.89” (48.0 mm)
2–4
1.89” (48.0 mm)
F
AT
1.76” (44.75 mm)
C
0.37” (9.5 mm)
2.36” (Min.) [60.0 mm]
1.76” (44.75 mm)
PV SV
3.15” (80.0 mm)
SOLO Temperature Controller User Manual
+0.02
1.77" -0 [45.0 mm] +0.6 -0
+0.02
1.77" -0 [45.0 mm] +0.6 -0
Page 17
Chapter 2: Installation and Wiring
Controller and Panel Cutout Dimensions, cont’d SL4896 Series
Minimum Cutout and Spacing 2.36" (Min.) [60.0 mm]
1.73” (44.0 mm)
OUT2
F
C
AT
ALM1
ALM2
ALM3
3.58” (91.0 mm)
OUT1
3.87” (98.2 mm) 3.77” (95.7 mm)
SV
4.72" (Min.) [120.0 mm]
SOLO 4896
PV
+0.02
1.75" -0 [44.5 mm] +0.6 -0
SET +0.02
3.60" -0 [91.4 mm] +0.6
1.89” (48.0 mm)
0.50” (12.8 mm)
-0
3.12” (79.2 mm)
SL9696 Series Minimum Cutout and Spacing 4.33" (Min) [110.0 mm]
C
3.57” (90.8 mm)
F
3.78” (96.0 mm)
OUT1 OUT2 ALM1 ALM2 ALM3
3.86” (98.0 mm)
AT
SET
2nd Ed. Rev D 04/18
3.58" +0.02 -0 [90.9 mm] +0.6 -0
3.58" +0.02 -0 [90.9 mm] +0.6 -0
SOLO 9696 3.78” (96.0 mm)
4.33" (Min) [110.0 mm]
3.57” (90.8 mm)
PV
SV
0.62” (15.88 mm)
3.12” (79.2 mm)
SOLO Temperature Controller User Manual
2–5
Page 18
Chapter 2: Installation and Wiring
Safety Information
DANGER! Warning: To minimize the risk of potential safety problems, you should follow all applicable local and national codes that regulate the installation and operation of your equipment. These codes vary from area to area and it is your responsibility to determine which codes should be followed, and to verify that the equipment, installation, and operation are in compliance with the latest revision of these codes Warning: To prevent electric shock, do not touch the AC terminals while power is supplied to the controller. Warning: This controller is an open-type temperature controller. make sure to evaluate any dangerous application in which a serious human injury or serious property damage may occur. Wiring Notes: PLEASE READ PRIOR TO INSTALLATION. Equipment damage or serious injury to personnel can result from the failure to follow all applicable codes and standards. We do not guarantee the products described in this publication are suitable for your particular application, nor do we assume any responsibility for your product design, installation, or operation. If you have any questions concerning the installation or operation of this equipment, or if you need additional information, please call us at 1-800-633-0405 or 770-844-4200. This publication is based on information that was available at the time it was printed. At Automationdirect.com® we constantly strive to improve our products and services, so we reserve the right to make changes to the products and/or publications at any time without notice and without obligation. This publication may also discuss features that may not be available in certain revisions of the product. 1. use recommended solder-less terminals: Fork terminal with isolation (M3 screw, width is 7.0mm, hole diameter 3.2mm). Screw size: M3 x 6.5 (With 6.8 x 6.8 square washer). Recommended tightening torque: 0.4 Nm (4kgfcm). Applicable wire: Solid/ twisted wire of 2 mm, 12AWG to 24AWG. Choose AutomationDirect fork terminals part numbers BM-00120, BM-00220 or BM-00320 depending on wire size. Be sure to tighten them properly. 2. the controller from dust or foreign objects as they can cause the controller to malfunction. 3. modify or disassemble the controller. 4. not connect anything to the “Not used” terminals. 5. sure all wires are connected to the correct polarity of terminals. 6. not install and/or use the controller in places subject to: (a) Dust or corrosive gases and liquid (b) High humidity (c) Vibration or shock (d) EMI / RFI (e) high temperature. 7. must be turned off when wiring or changing a sensor.
2–6
SOLO Temperature Controller User Manual
Page 19
Chapter 2: Installation and Wiring
Safety Information, cont’d 8. B e sure to use wires that match the thermocouple types when extending or connecting thermocouple wires. 9. wires with correct resistance when extending or connecting a RTD. 10. the wire as short as possible when wiring a RTD to the controller and route power wires as far as possible from sensor wires to prevent interference and induced noise. 11. controller is an open-type unit and must be placed in an enclosure to ensure proper operation and maintain the IP65 rating. 12. sure power cables and signals from instruments are all installed properly before energizing the controller, otherwise serious damage may occur. 13. prevent electric shock, do not touch the terminals on the controller or try to repair the controller when power is applied. 14. not use acid or alkaline liquids for cleaning. Use a soft, dry cloth to clean the controller. 15. instrument is not furnished with a power switch or fuse. Therefore, if a fuse or power switch is required, install the protection close to the instrument. Recommended fuse rating: Rated voltage 250 V, Rated current 1 A. Fuse type: Time-delay fuse. See the AutomationDirect catalog for the appropriate fuse for the specific application. 16. This controller does not provide overcurrent protection. Use of this product requires that suitable overcurrent protection device(s) must be added to ensure compliance with all relevant electrical standards and codes. (Rated 250 V, 15 Amps max). A suitable disconnecting device should be provided near the controller in the end-use installation.
2nd Ed. Rev D 04/18
SOLO Temperature Controller User Manual
2–7
Page 20
Chapter 2: Installation and Wiring
Terminal Identification SL4824 Series Inputs Power Input AC Models Power Input
DC Models Power Input
Sensor Input 0 – 10 VDC
4~20 mA
2-wire RTD
3-wire RTD
Thermocouple
2–8
SOLO Temperature Controller User Manual
Page 21
Chapter 2: Installation and Wiring
Terminal Identification cont’d SL4824 Series Wiring SL4824-RR
SL4824-VR
SL4824-CR
SL4824-LR
2nd Ed. Rev D 04/18
SOLO Temperature Controller User Manual
2–9
Page 22
Chapter 2: Installation and Wiring
Terminal Identification, cont’d SL4848 Series Inputs Power Input AC Models Power Input
DC Models Power Input
Sensor Input 0 – 10 VDC
4~20 mA
2-wire RTD
3-wire RTD
Thermocouple
2–10
SOLO Temperature Controller User Manual
Page 23
Chapter 2: Installation and Wiring
Terminal Identification, cont’d SL4848 Series Wiring SL4848-RR
SL4848-LV & SL4848-VV
SL4848-VR
SL4848-CR
SL4848-CV
SL4848-LR
2nd Ed. Rev D 04/18
SOLO Temperature Controller User Manual
2–11
Page 24
Chapter 2: Installation and Wiring
Terminal Identification, cont’d SL4896 Series Inputs Power Input AC Models Power Input
DC Models Power Input
Sensor Input 0 – 10 VDC
4~20 mA
2-wire RTD
3-wire RTD
Thermocouple
2–12
SOLO Temperature Controller User Manual
Page 25
Chapter 2: Installation and Wiring
Terminal Identification, cont’d SL4896 Series Wiring SL4896-RRE
SL4896-CRE
SL4896-VRE
SL4896-LRE
2nd Ed. Rev D 04/18
SOLO Temperature Controller User Manual
2–13
Page 26
Chapter 2: Installation and Wiring
Terminal Identification, cont’d SL9696 Series Inputs Power Input AC Models Power Input
DC Models Power Input
0 – 10 VDC
4~20 mA
2-wire RTD
3-wire RTD
Thermocouple
2–14
SOLO Temperature Controller User Manual
Page 27
Chapter 2: Installation and Wiring
Terminal Identification, cont’d SL9696 Series Wiring SL9696-RRE
SL9696-LRE SL9696-VRE
SL9696-CRE
SL9696-CVE
SL9696-VVE
SL9696-LVE
2nd Ed. Rev D 04/18
SOLO Temperature Controller User Manual
2–15