Page 8

Getting Started

Chapter

1

In this Chapter... Manual Overview Overview of this Who Should Read This Technical Supplemental Special

SOLO Temperature Controller General

Serial Number Label Model Number

SOLO Temperature Controller

Page 9

Chapter 1: Getting Started

Manual Overview Overview of this Publication The SOLO Temperature Controller User Manual describes the installation, configuration, and methods of operation of the SOLO Temperature Controller.

Who Should Read This Manual This manual contains important information for those who will install, maintain, and/or operate any of the SOLO Temperature Controllers.

Technical Support

By Telephone: 7 70-844-4200

(Mon.-Fri., 9:00 a.m.-6:00 p.m. E.T.)

On the Web: support.automationdirect.com

Our technical support group is glad to work with you in answering your questions. If you cannot find the solution to your particular application, or, if for any reason you need additional technical assistance, please call technical support at 770-844-4200. We are available weekdays from 9:00 a.m. to 6:00 p.m. Eastern Time. We also encourage you to visit our web site where you can find technical and non-technical information about our products and our company. Visit us at www.automationdirect.com.

Supplemental Manuals If you are familiar with industrial control type devices, you may be able to get up and running with just the aide of the Quick Start Guide that is included with each SOLO Temperature Controller.

Special Symbols When you see the “notepad” icon in the left-hand margin, the paragraph to its immediate right will be a special note.

When you see the “exclamation mark” icon in the left-hand margin, the paragraph to its immediate right will be a warning. This information could prevent injury, loss of property, or even death (in extreme cases).

1–2

SOLO Temperature Controller User Manual

Page 10

Chapter 1: Getting Started

SOLO Temperature Controller Introduction General Description The SOLO Temperature Controller is a single loop dual output temperature controller that can control both heating and cooling simultaneously. There are four types of control modes: PID, ON / OFF, Manual, and Ramp / Soak control. Depending upon the particular model of controller, the available outputs include relay, voltage pulse, current, and linear voltage. There are up to three alarm outputs available to allow seventeen alarm types in the initial setting mode. SOLO can accept various types of thermocouple, RTD, or analog inputs, and has a built in RS-485 interface using Modbus slave (ASCII or RTU) communication protocol. Other features include: • 1/32, 1/16, 1/8 and 1/4 DIN panel sizes • line x 4 character 7-segment LED display for Process Value (PV): Red color, and Set Point (SV): Green color • Auto Tuning (AT) function with PID control • Selectable between °C and °F for thermocouple or RTD inputs • 0 to 50 °C (32 to 122 °F) operating temperature range • UL, CUL and CE agency approvals

Unpacking After receiving the SOLO Temperature Controller, please check for the following: • sure that the package includes the Controller, the mounting brackets and hardware, a 249 ohm resistor and the Quick Start Guide. • Inspect the unit to insure it was not damaged during shipment. • sure that the part number indicated on the serial number label corresponds with the part number of your order.

Mounting Brackets and Hardware

Temperature Controller (SL 9696 shown)

249 ohm resistor Quick Start Guide

2nd Ed. Rev D 04/18

SOLO Temperature Controller User Manual

1–3

Page 11

Chapter 1: Getting Started

Serial Number Label Information: SL4824 Series Serial Number Label SOLO Model Number Input Specifications Bar Code Serial Number

SL4848, SL4896, and SL9696 Series Serial Number Label SOLO Model Number Input Specifications Bar Code Serial Number

Model Number Explanation

SL 4896 - V R E - D Input Voltage None: 100 to 240 VAC D: 24 VDC

Event Input None: No Event input E: Event input is provided

2nd Output Group R: Relay output V: Voltage Pulse output

1st Output Group R: Relay output V: Voltage Pulse output C: DC Current output L: Linear Voltage output

Panel Size (W x H) 4824: 1/32 DIN W48 x H24mm 4848: 1/16 DIN W48 x H48mm 4896: 1/8 DIN W48 x H96mm 9696: 1/4 DIN W96 x H96mm

Solo Temperature Controller

1–4

SOLO Temperature Controller User Manual

Page 12

Chapter 1: Getting Started

SOLO Temperature Controller Specifications Specifications

Input Power Requirements Operation Voltage Range Power Consumption Memory Protection Control Mode

100 to 240 VAC 50 / 60 Hz or 24 VDC 85 to 264 VAC or 21.6 to 26.4 VDC 5 VA Max EEPROM 4K bit, number of writes 100,000 PID, ON/OFF, Ramp / Soak control or Manual

Input Accuracy

Less than ± 0.2% full scale (except thermocouple R, S, & B types) Max ± 3° (thermocouple R, S, & B types)

Vibration Resistance Shock Resistance Ambient Temperature Range Storage Temperature Range Altitude Relative Humidity RS-485 Communication Transmission Speed

10 to 55 Hz, 10 m/s2 for 10 min, each in X, Y and Z directions

IP Rating

IP65: Complete protection against dust and low pressure spraying water from all directions. (inside suitable enclosure)

Max. 300 m/s2, 3 times in each 3 axes, 6 directions 32°F to 122°F (0°C to 50°C) -4°F to 149°F (-20°C to 65°C) 2000m or less 35% to 80% (non-condensing) Modbus slave ASCII / RTU protocol 2400, 4800, 9600, 19.2K, 38.4K bps

Agency Approvals

UL, CUL, CE (UL file number E311366)

Pollution Degree

Degree 2 - Normally, only non-conductive pollution occurs. Temporary conductivity caused by condensation is to be expected

Input Types • Thermocouple* • Platinum RTD • Analog Input Sampling Rates • Thermocouple • Platinum RTD • Analog Control Output Options • Relay (R) • Voltage Pulse (V) • Current (C) • Linear Voltage (L)

K, J, T, E, N, R, S, B, L, U, TXK 3-wire Pt100, JPt100 0-50 mV, 0-5V, 0-10V, 0-20 mA, 4-20 mA (Current input requires the installation of the supplied 249 q resistor) 400 ms / per scan 400 ms / per scan 150 ms / per scan SL4824: SPST max. resistive load 3A @ 250 VAC SL4848: SPST max. resistive load 5A @ 250 VAC SL4896, SL9696: SPDT max. resistive load 5A @ 250 VAC SL4824: SPST max. resistive load 3A @ 30 VDC SL4848: SPST max. resistive load 5A @ 30 VDC SL4896, SL9696: SPDT max. resistive load 5A @ 30 VDC DC 14V Max, output current 40mA Max DC 4-20 mA output (Load resistance: Max 600 Ω) DC 0-10V (Load resistance Min 1KΩ)

*Note: Use only ungrounded thermocouples. 2nd Ed. Rev D 04/18

SOLO Temperature Controller User Manual