SOLO Temperature Controller User Manual: Chapter 5: Control Modes
Pages 62 to 66 of 87, from SOLO Temperature Controller User Manual
The original document is the PDF (5.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
Filed in the catalog under the AutomationDirect SOLO 8484 /SL8484, Konnect-It SOLO 8484 /SL8484 and Koyo SOLO 8484 /SL8484
Page 62
Control Modes
Chapter
5
In this Chapter... PID On / Off Ramp / Soak Manual Error Display
Page 63
Chapter 5: Control Modes The SOLO controller can be configured for any of the following control modes. • PID control • On / Off control • Ramp / Soak control • Manual control
PID Control All of the SOLO controllers can store up to four PID parameter groups (PID parameter groups 0 - 3) Group 0
Group 1
Group 2
Group 3 sv0 p0 i0 d0 iof0 sv1 p1 i1 d1 iof1 sv2 p2 i2 d2 iof2 sv3 p3 i3 d3 iof3
Set Value Proportion Band Integral Time Derivative Time Integral Offset
Note: Other parameters are shared among all PID parameter groups.
The operator can select any of the parameter groups for PID control. The SOLO controller also supports the PID parameter group 4. However, this is not an actual parameter group. When the PID parameter group 4 is selected, the controller checks the SV of each parameter group and uses the parameter group which has a SV that is the closest to the SV set by the operator. If there are two or more PID parameter groups that have SV values equally close to the SV, the controller uses the lowest number parameter group (eg. If parameter groups 0 3 have the same SV, the controller uses the parameter group 0). Group 0
Group 1
Group 2
Group 3 sv0 p0 i0 d0 iof0 sv1 p1 i1 d1 iof1 sv2 p2 i2 d2 iof2 sv3 p3 i3 d3 iof3
Group 4 SV When the PID parameter group 4 is selected, the controller compares SV0 - SV3 with the PV. Then it uses the parameter group which has a SV that is the closest to the SV set by the operator..
Once the controller selects one of the PID parameter groups (group 0 - 3), the setup parameters of the selected parameter group are displayed on th controller. The SL4896 and SL9696 series controller also support an additional PID parameter group. The parameter group is used with the Event2 input. When Event2 input is on, the SOLO controller uses the additional PID group for the PID control.
5–2
SOLO Temperature Controller User Manual
Page 64
Chapter 5: Control Modes Event 2 = Off Group 0
Group 1
Group 2
Group 3
Event 2 = On
Group for Event 2
Group 4
Auto Tuning All SOLO controllers support the Auto Tuning feature to set up the following PID parameters automatically. Proportional Band (Pn, P1-4) p Integral Time (In, P1-5) i Derivative Time (dn, P1-6) d iof Integral Offset (iofn, P1-8) Coef Proportional Band Coefficient (Coef, P1-14)
Temperature
To start the Auto Tuning, set the parameter Auto Tuning (AT, P1-1) to on. the controller automatically controls the output to change the PV as shown below. Control output turns off Cycle
SV Amplitude SV- 2
Control output turns on
The Auto Tuning ends and the PID control starts Time
Once the Auto Tuning process is completed, the SOLO controller calculates the above PID parameters and starts the PID control with the new parameter values immediately.
On / Off Control In the On / Off control mode the output is controlled according to the difference between the SV and the PV. If the PV is lower than the SV, the heating output is turned on. If the PV is higher than the SV, the cooling output is turned on. The Heating / Cooling Hysteresis and the Dead Band setups can be used to avoid output chatter.
2nd Ed. Rev D 04/18
SOLO Temperature Controller User Manual
5–3
Page 65
Chapter 5: Control Modes dead (P1-15) Cts (P1-10)
Dead band hts (P1-9)
Heating hysteresis
Cooling hysteresis
ON Heating
Cooling
OFF
PV Set point
Hysteresis There are two types of hysteresis, heating and cooling. If the heating hysteresis is set, the heating output turns on using the following formula. PV < SV - (dead / 2) - hts
If the cooling hysteresis is set, the cooling output turns on using the following formula. PV > SV + (dead / 2) + Cts
Dead Band The Dead Band is the range around the PV in which the heating / cooling outputs remain off. The Dead Band is defined by the formula. SV ± (dead / 2)
Ramp / Soak Control
Temperature
The Ramp / Soak control mode is used to control the outputs according to the preprogrammed SV patterns with the PID control method. The SOLO controllers support up to eight Ramp / Soak patterns. Each Ramp / Soak pattern can store up to eight steps. Each step has its target SV and the time duration setups. You can set up each Ramp / Soak step. Step4 Step2 Step0
Step3
Step1
Step5 Step6
Time You can select which Ramp / Soak pattern the SOLO controller will execute first. The Ramp / Soak patterns can be executed in series, so the Ramp / Soak control can execute up to 64 steps (8 steps x 8 patterns). You can select which Ramp / Soak pattern will execute next or the controller stops after executing the current pattern.
5–4
SOLO Temperature Controller User Manual
Page 66
Chapter 5: Control Modes The SOLO controller can execute the same Ramp / Soak pattern up to 200 times before it stops or moves to the next Ramp / Soak pattern.
Ramp / Soak Display There are three Ramp / Soak display modes possible with the SOLO controller. From the controller main screen press the . and , buttons to choose from these three optional display modes.
p-st - Pattern Number - Step Number sp - Set Point r-ti - Remaining time in current step Press the ; button to save the selection.
Manual Control In the Manual control mode, the outputs of the controller are manipulated manually by the operator. Adjust the values of the parameters Output 1 Level (out1, P2-11) and / or Output 2 Level (out2, P2-12) to control the output levels. Output 2 Level is only available when you select a dual output mode.
Error Display Information The chart below illustrates the possible error displays shown on the SOLO Temperature controller.
Controller Error Display
Display Display Position PV SV PV SV PV SV PV SV b160 Cr
Meaning
Cause
Corrective Action
The SOLO controller displays this information The controller Initialization for a few seconds after power up. If the is in the PV = Firmware controller continues displaying this information, initialization version check the input wiring. If the problem still process. SV = Module type exists, replace the sensor or the controller. No sensor input
The input terminals are open.
Input error
The controller Check the sensor and the input wiring. If the cannot read the problem still exists, replace the sensor or the input value controller.
EEPROM error
There is an Cycle the power to the SOLO controller. If the error with the problem still exists, replace the controller. EEPROM
Flashing PV PV out of range
Check the PV range. The Input Range High ( , P3-3) and the Input Range Low The PV is out of TP-H (TP-l, P3-4) parameters define the range. range Refer to section 12-1, 12-2 or 12-3 for directions on how to access these parameters.
no Cont Err Inpt Err Prom
PV SV
2nd Ed. Rev D 04/18
Check the input wiring. If the problem still exists, replace the sensor or the controller.