Page 11
1–3 Getting Started
Conventions Used
When you see the “exclamation mark” icon in the left–hand margin, the paragraph to its immediate right will be a warning. This information could prevent injury, loss of property, or even death (in extreme cases). The word WARNING: in boldface will mark the beginning of the text. Key Topics for Each Chapter
The beginning of each chapter will list the key topics that can be found in that chapter.
1
Getting Started
When you see the “notepad” icon in the left–hand margin, the paragraph to its immediate right will be a special note. The word NOTE: in boldface will mark the beginning of the text.
Page 12
1–4 Getting Started
Getting Started
Terminator I/O Base Controllers Terminator I/O offers six base controller modules. All modules include an on board RJ–12 RS–232 serial port. The six base controllers are:
Ethernet Base Controller − T1H–EBC − T1H–EBC100 Base Controller − T1K–DEVNETS DP Base Controller − T1H–PBC RTU Base Controller − T1K–MODBUS DirectLogic Remote I/O Base Controller − T1K–RSSS
T1H–EBC
T1H–EBC100
T1H–PBC
T1K–MODBUS
T1K–DEVNETS
T1K–RSSS
Page 13
1–5 Getting Started
Terminator I/O System Components
I/O Modules
Power Supply
Base Controller
I/O Module I/O Module Assembly I/O Base
I/O Modules
Getting Started
Power Supplies
Terminator I/O is a modular system which combines the functions of terminal blocks and I/O modules for distributed I/O. Each Terminator I/O system has the following components: a Power Supply, a Base Controller, and one or more I/O Module(s). Terminator I/O systems can contain up to 16 I/O modules per slave (node). Each slave (node) system can be divided into one row of base I/O plus two rows of local expansion I/O using a base expansion cable. 120/240VAC and 12/24 VDC power supplies are available. The AC version has a built–in 24VDC supply. A power supply must be the leftmost component in a slave system followed by the base controller. Additional power supplies should be added between I/O modules to meet power budget requirements. A Terminator I/O module assembly consists of an I/O module and a separate base, as shown below. A complete range of discrete modules which support 12/24 VDC, 110/220 VAC and up to 7A relay outputs is offered. The analog I/O modules provide 12 and 14 bit resolution and several selections of I/O signal ranges (including bipolar). The temperature input modules provide 16 bit resolution with several temperature input range selections. All Terminator I/O modules can be “Hot Swapped” (replaced) without removing system power (except for the base controller and power supply). Refer to the “I/O Module Hot Swap” section in Chapter 3 for details.
Page 14
Installation and Power Wiring
12
In This Chapter. . . ., Safety Guidelines, Mounting Guidelines, Assembling the Components, Multiple Power Supplies / Local Expansion, Power Supply Wiring Guidelines
Page 15
2–2 Installation and Wiring
Installation and Safety Guidelines
Installation and Power Wiring
Safety Guidelines WARNING: Providing a safe operating environment for personnel and equipment is your responsibility and should be your primary goal during system planning and installation. Automation systems can fail and may result in situations that can cause serious injury to personnel or damage to equipment. Do not rely on the automation system alone to provide a safe operating environment. You should use external electromechanical devices, such as relays or limit switches, that are independent of the application to provide protection for any part of the system that may cause personal injury or damage. Every automation application is different, so there may be special requirements for your particular application. Make sure you follow all national, state, and local government requirements for the proper installation and use of your equipment. Plan for Safety
The best way to provide a safe operating environment is to make personnel and equipment safety part of the planning process. You should examine every aspect of the system to determine which areas are critical to operator or machine safety. If you are not familiar with industrial control system installation practices, or your company does not have established installation guidelines, you should obtain additional information from the following sources. • NEMA, The National Electrical Manufacturers Association, located in Washington, D.C., publishes many different documents that discuss standards for industrial control systems. You can order these publications directly from NEMA. Some of these include: ICS 1, General Standards for Industrial Control and Systems ICS 3, Industrial Systems ICS 6, Enclosures for Industrial Control Systems • NEC, The National Electrical Code provides regulations concerning the installation and use of various types of electrical equipment. Copies of the NEC Handbook can often be obtained from your local electrical equipment distributor or your local library. S Local and State Agencies, many local governments and state governments have additional requirements above and beyond those described in the NEC Handbook. Check with your local Electrical Inspector or Fire Marshall office for information.
Safety Techniques
The publications mentioned provide many ideas and requirements for system safety. At a minimum, you should follow these regulations. Using the techniques listed below will further help reduce the risk of safety problems. • Orderly system shutdown sequence in the control program. • Emergency stop switch for disconnecting system power. Class 1, Division 2, This equipment is suitable for use in Class 1, Division 2, Zone 2 , groups A, B, C and D or non–hazardous locations only. Zone 2 Approval WARNING: Explosion Hazard: • Substitution of components may impair suitability for Class 1, Division 2, Zone 2. • Do not disconnect equipment unless power has been switched off or the area is known to be non–hazardous.
Page 16
2–3 Installation and Wiring
Orderly System Shutdown
The first level of protection can be provided with the control program by identifying machine problems. Analyze your application and identify any shutdown sequences that must be performed. Typical problems are jammed or missing parts, empty bins, etc. that do not pose a risk of personal injury or equipment damage.
System Power Disconnect
By using electromechanical devices, such as master control relays and/or limit switches, you can prevent accidental equipment startup. When installed properly, these devices will prevent any machine operations from occurring. For example, if the machine has a jammed part, the control program can turn off the saw blade and retract the arbor. However, since the operator must open the guard to remove the part, you must include a bypass switch to disconnect all system power any time the guard is opened. The operator must also have a quick method of manually disconnecting all system power. This is accomplished with a mechanical device clearly labeled as an Emergency Stop switch.
Guard Limit Switch
Installation and Power Wiring
WARNING: The control program must not be the only form of protection for any problems that may result in a risk of personal injury or equipment damage.
Emergency Stop
Installation and Safety Guidelines After an Emergency shutdown or any other type of power interruption, there may be requirements that must be met before the control program can be restarted. For example, there may be specific register values that must be established (or maintained from the state prior to the shutdown) before operations can resume. In this case, you may want to use retentive memory locations, or include constants in the control program to ensure a known starting point.
Page 17
2–4 Installation and Wiring
Mounting Guidelines Before installing the Terminator I/O system you will need to know the dimensions of the components. The diagrams on the following pages provide the component dimensions to use in defining your enclosure specifications. Remember to leave room for potential expansion.
Installation and Power Wiring
NOTE: If you are using other components in your system, refer to the appropriate manual to determine how those units can affect mounting dimensions. Dimensions
The following diagrams show the base controller, power supply and I/O module dimensions. Terminator I/O components mount on 35mm wide Din rail.
Base Controller / Power Supply 48 (1.89)
83.3 (3.28)
9.2 (0.36)
Installation and Safety Guidelines
Terminator I/O components 80 (3.15) mount on 35mm wide Din rail.
10.3 (0.41)
mm (in.)
80 (3.15)
10.3 (0.41)
mm (in.)
I/O Modules (8 pt.)
(16 pt.)
48 (1.89)
89 (3.5)
80 (3.15)
mm (in.)
80 (3.15)
mm (in.)
Page 18
Installation and Wiring Panel Mounting and Layout
2--5
It is important to design your panel properly to help ensure that the Terminator I/O products operate within their environmental and electrical limits. The system installation should comply with all appropriate electrical codes and standards. It is important that the system also conforms to the operating standards for the application to insure proper performance.
OK OK
Installation and Power Wiring
Airflow
Airflow
1. Mount the unit horizontally or vertically as shown to provide proper ventilation. 2. If you place more than one unit in a cabinet, there should be a minimum of 7.2” (183mm) between them. 3. Provide a minimum clearance of 2” (50mm) between the units and all sides of the cabinet. There should also be at least 1.2” (30mm) of clearance between the base and any wiring ducts.
Temperature Probe
Note: provide a minimum of 2” (50mm) clearance between the panel door or any devices mounted in the panel door and the nearest Terminator Component.
Installation and Safety Guidelines
Panel Power Source
Star Washers
Ground Braid Copper Lugs
Star Washers
Panel or Single Point Ground
Panel Ground Terminal
Earth Ground
Page 19
2–6 Installation and Wiring
Installation and Safety Guidelines
Installation and Power Wiring
4. There must be a minimum of 2” (50mm) clearance between the panel door and the nearest Terminator I/O component. 5. The ground terminal on the Terminator I/O power supply must be connected to a single point ground. Use copper stranded wire to achieve a low impedance. Copper eye lugs should be crimped and soldered to the ends of the stranded wire to ensure good surface contact. Remove anodized finishes and use copper lugs and star washers at termination points. A general rule is to achieve a 0.1 ohm of DC resistance between the Terminator I/O slave and the single point ground. 6. There must be a single point ground (i.e. copper bus bar) for all devices in the panel requiring an earth ground return. The single point of ground must be connected to the panel ground termination. The panel ground termination must be connected to earth ground. For this connection you should use #12 AWG stranded copper wire as a minimum. Minimum wire sizes, color coding, and general safety practices should comply with appropriate electrical codes and standards for your region. A good common ground reference (Earth ground) is essential for proper operation of the Terminator I/O. There are several methods of providing an adequate common ground reference, including: a) Installing a ground rod as close to the panel as possible. b) Connection to incoming power system ground.
Enclosures
7. Properly evaluate any installations where the ambient temperature may approach the lower or upper limits of the specifications. Place a temperature probe in the panel, close the door and operate the system until the ambient temperature has stabilized. If the ambient temperature is not within the operating specification for the Terminator I/O system, measures such as installing a cooling/heating source must be taken to get the ambient temperature within the Terminator I/O operating specifications. 8. Device mounting bolts and ground braid termination bolts should be #10 copper bolts or equivalent. Tapped holes instead of nut–bolt arrangements should be used whenever possible. To assure good contact on termination areas impediments such as paint, coating or corrosion should be removed in the area of contact. 9. The system is designed to be powered by 110/220 VAC or 24 VDC normally available throughout an industrial environment. Isolation transformers and noise suppression devices are not normally necessary, but may be helpful in eliminating/reducing suspect power problems. Your selection of a proper enclosure is important to ensure safe and proper operation of your Terminator I/O system. Applications of Terminator I/O systems vary and may require additional features. The minimum considerations for enclosures include: • Conformance to electrical standards • Protection from the elements in an industrial environment • Common ground reference • Maintenance of specified ambient temperature • Access to equipment • Security or restricted access S Sufficient space for proper installation and maintenance of equipment
Page 20
2–7 Installation and Wiring
Environmental Specifications
The following table lists the environmental specifications that apply to the Terminator I/O modules. Be sure to check the specifications of the controller you are using. Also refer to the appropriate I/O module specifications in Chapter 3 for the temperature derating curves for the specific module. Rating
Storage temperature
–4° F to 158° F (–20° C to 70° C)
Ambient operating temperature
32° F to 131° F (0° C to 55° C)
Ambient humidity*
5% – 95% relative humidity (non–condensing)
Vibration resistance
MIL STD 810C, Method 514.2
Shock resistance
MIL STD 810C, Method 516.2
Noise immunity
NEMA (ICS3–304) Impulse noise 1us, 1000V FCC class A RFI (144MHz, 430MHz 10W, 10cm)
Atmosphere
No corrosive gases. The level for the environmental pollution = 2. (UL840)
Installation and Power Wiring
Specification
*Equipment will operate at low humidity. However, static electricity problems occur much more frequently at lower humidity levels. Make sure you take adequate precautions when you touch the equipment. Consider using ground straps, anti-static floor coverings, etc. if you use the equipment in low humidity environments.
Power
The power source must be capable of supplying voltage and current complying with the base power supply specifications. Specification
DC Power Supply
Part Numbers
T1K–01AC
T1K–01DC
Input Voltage Range
110/220VAC (85–264VAC) 50/60Hz (47–63Hz)
12/24VDC (10.8–26.4VDC)) with less than 10% ripple
Maximum Inrush Current
20A
10A
Maximum Power
50 VA
20W
Voltage Withstand (dielectric)
1 minute @ 1500 VAC between primary, secondary, field ground
Insulation Resistance
> 10 M ohm at 500 VDC
Auxiliary 24 VDC Output
20–28 VDC, l0% ripple max. 300 mA. A max. of 500 mA @24VDC can be achieved if the 5VDC power budget rating of 2000mA is reduced to 1500mA. See power budget section.
None
Some applications require agency approvals. Typical agency approvals which your application may require are: • UL (Underwriters’ Laboratories, Inc.) • CSA (Canadian Standards Association) • FM (Factory Mutual Research Corporation) S CUL (Canadian Underwriters’ Laboratories, Inc.)
Installation and Safety Guidelines
Agency Approvals
AC Power Supply