2–8 Installation and Wiring
Assembling the Components Assembling the I/O Modules and Bases 1
Insert Module into Base 1. Pull base arm back to allow space for module to enter base. 2. Align module slides with base track.
Installation and Power Wiring
3. Press module firmly into base.
3 2
Mounting the Components on DIN Rail
Installation and Safety Guidelines
2
3
1 NOTE: Do not force the base controller on the DIN rail. Due to slight size variations in different manufacturers’ DIN rail, it may be necessary to first unlatch the locking tab, rotate the module into place, then latch the locking tab.
Install on DIN Rail 1. Make sure the locking tab is in the latched position (pushed in). 2. Hook upper tab over upper flange of DIN rail. 3. Tilt the unit toward DIN rail until it snaps securely to DIN rail.
Page 22
2–9 Installation and Wiring
Connecting the Components on the DIN Rail
Slide the module assembly on the DIN rail until the clip arm attaches securely to the adjacent module.
Installation and Power Wiring
Slide Assembly into Position on DIN Rail
NOTE: One power supply is required in the leftmost component position followed by the base controller. Additional power supplies should be added between I/O modules as necessary to meet power budget requirements (see page 3–18). Each power supply powers the modules to its right, but is interrupted by the next power supply.
Removing I/O Modules from the Base Installation and Safety Guidelines To remove the module from the base, grip the center of the base arm and rotate outward releasing the module. Lift the module from the base. To remove a module assembly from the DIN rail, lift the clip arm up and slide the module assembly away from the adjacent module. Pull the locking tab down (out) and lift the assembly off the DIN rail. Refer to the “I/O Module Hot Swap Feature” section in Chapter 3 to remove an I/O module with Terminator I/O system power ON.
Page 23
2–10 Installation and Wiring
Multiple Power Supplies / Local Expansion Configurations
Installation and Power Wiring
Multiple Power Supply Configuration
It is possible to have multiple power supplies in a single slave (node) system to meet power budget requirements. One power supply is required in the leftmost component position followed by the base controller. Additional power supplies should be added between I/O modules as necessary to meet power budget requirements. There are some restrictions on where power supplies can be placed in the system when using the T1K–05CBL–RR(–1) expansion base cable. Each power supply powers the modules to its right, but is interrupted by the next power supply. Each slave (node) system can be divided into one row of base I/O plus two rows of local expansion I/O up to a total of 16 I/O modules. Expansion cables are available in two configurations: one that passes 24VDC base power through and one that does not (both cables pass the 5VDC base power). The (–1) version of the expansion cables pass 24VDC through on an isolated wire. Any local expansion DC input modules configured for “internal power” (current sourcing) must either have a power supply preceeding it on the same base or, have a (–1) version cable pass 24VDC from a power supply on the preceeding base.
Example Using Two T1K–10CBL(–1) Expansion Cables Base Controller
Power Supply #1 (a power supply must be the leftmost component in a system followed by the base controller)
Local Base I/O I/O Addressing
Power Supply #2
Installation and Safety Guidelines
T1K–10CBL(–1)
1st Local Expansion I/O I/O Addressing T1K–10CBL
Power Supply #3
2nd Local Expansion I/O I/O Addressing
System shown above: The first power supply powers the base controller and the two I/O modules to its right. The second power supply powers the the two modules to its right and the three I/O modules on the first local expansion base. Power Supply #3 powers the three I/O modules to its right on the second local expansion base. This is only an example and the power budget requirements vary depending on the I/O modules used.
Page 24
2–11 Installation and Wiring
Example Using T1K–05CBL–RR(–1) and T1K–05CBL–LL(–1) Expansion Cables Power Supply #1
Base Controller
(a power supply must be the leftmost component in a system followed by the base controller)
Local Base I/O
I/O Addressing
Power Supply #2
T1K–05CBL–RR(–1)
Installation and Power Wiring
Do not connect a T1K–05CBL–LL(–1) to the left side of the local I/O base.
1st Local Expansion I/O I/O Addressing A power supply cannot be used on a base that is connected to a system by a T1K–05CBL–RR(–1)
T1K–05CBL–LL(–1)
2nd Local Expansion I/O Power Supply #3
System shown above: The first power supply powers the base controller and the two I/O modules to its right. The second power supply powers the the two modules to its right and the three I/O modules on the first local expansion base. When a T1K–05CBL–RR(–1) is used, the expansion I/O assignments are from right to left (reversed). A power supply cannot be used on a base that is connected to a system by a T1K–05CBL–RR(–1). Power Supply #3 powers the three I/O modules to its right on the second local expansion base.This is only an example and the power budget requirements vary depending on the I/O modules used.
Installation and Safety Guidelines
I/O Addressing
Page 25
2–12 Installation and Wiring
Example Using T1K–10CBL(–1) and T1K–05CBL–RR(–1) Expansion Cables Base Controller
Power Supply #1 (a power supply must be the leftmost component in a system followed by the base controller)
Local Base I/O Power Supply #2
Installation and Power Wiring
I/O Addressing
T1K–10CBL(–1)
1st Local Expansion I/O Power Supply #3 I/O Addressing T1K–05CBL–RR(–1)
A power supply cannot be used on a base that is connected to a system by a T1K–05CBL–RR(–1)
Installation and Safety Guidelines
2nd Local Expansion I/O I/O Addressing
System shown above: The first power supply powers the base controller and the two I/O modules to its right. The second power supply powers the the two modules to its right. Power Supply #3 powers the three I/O modules to its right on the first local expansion base and the three I/O modules on the second local expansion base. When a T1K–05CBL–RR(–1) is used, the expansion I/O assignments are from right to left (reversed). A power supply cannot be used on a base that is connected to a system by a T1K–05CBL–RR(–1). This is only an example and the power budget requirements vary depending on the I/O modules used.
Page 26
2–13 Installation and Wiring
Example Using T1K–05CBL–RR(–1) Expansion Cable Base Controller
Power Supply #1 (a power supply must be the leftmost component in a system followed by the base controller)
Local Base I/O
T1K–05CBL–RR(–1)
Installation and Power Wiring
Power Supply #2 I/O Addressing
1st Local Expansion I/O I/O Addressing A power supply cannot be used on a base that is connected to a system by a T1K–05CBL–RR(–1)
Installation and Safety Guidelines
System shown above: The first power supply powers the base controller and the two I/O modules to its right. The second power supply powers the the two modules to its right and the five I/O modules on the first local expansion base. When a T1K–05CBL–RR(–1) is used, the expansion I/O assignments are from right to left (reversed). A power supply cannot be used on a base that is connected to a system by a T1K–05CBL–RR(–1). This is only an example and the power budget requirements vary depending on the I/O modules used.
Page 27
2–14 Installation and Wiring
Power Supply Wiring Guidelines Power Wiring
The diagram below shows the terminal connections located on the Terminator I/O AC and DC power supplies. The table below shows the wire guage size and recommended torque for the power supply screw terminals.
Installation and Power Wiring
NOTE: You can connect either a 110 VAC or 220 VAC supply to the AC terminals. Special wiring or jumpers are not required as with some of the other DirectLOGIC products.
110/220 VAC Terminal Strip
12/24 VDC Terminal Strip
95-240V 50/60Hz 50VA
12-24 20W
AC (L)
+ ____ - ____
Installation and Safety Guidelines
AC (N)
+ 24V -
LG
OUT
G
LG G
T1K-01DC T1K-01AC Power Supply
T1K–01AC
T1K–01DC
Wire Guage
Solid: 24 – 12 AWG Stranded: 24 – 12 AWG
Solid: 24 – 12 AWG Stranded: 24 – 12 AWG
Recommended Torque
4.43 – 5.31 lb–in (0.5 – 0.6 Nm)
4.43 – 5.31 lb–in (0.5 – 0.6 Nm)
Page 28
I/O Wiring and Specifications
13
In This Chapter. . . ., I/O Wiring Strategies, I/O Modules Position, Wiring, and Specifications, I/O Module Hot Swap Feature, Calculating the Power Budget, I/O Specification Terms
Page 29
3–2 I/O Wiring and Specifications
I/O Wiring Strategies
Terminator I/O System Isolation Boundaries
The Terminator I/O system is very flexible and will work in many different wiring configurations. By studying this section before actual installation, you can probably find the best wiring strategy for your application. This will help to lower system cost, wiring errors, and avoid safety problems. Terminator I/O system circuitry is divided into three main regions separated by isolation boundaries, shown in the drawing below. Electrical isolation provides safety, so that a fault in one area does not damage another. A transformer in the power supply provides magnetic isolation between the primary and secondary sides. Opto-couplers provide optical isolation in Input and Output circuits. This isolates logic circuitry from the field side, where factory machinery connects. Note the discrete inputs are isolated from the discrete outputs, because each is isolated from the logic side. Isolation boundaries protect the operator interface (and the operator) from power input faults or field wiring faults. When wiring a Terminator I/O system, it is extremely important to avoid making external connections that connect logic side circuits to any other. Primary Side
Terminator I/O System
I/O Wiring and Specifications Installation and Safety Guidelines
Secondary, or Logic side
Power Input
Main Power Supply
Isolation Boundary
Slave CPU
Field Side
(backplane)
Input Module
Inputs
(backplane)
Output Module
Outputs
Programming Device, Operator Interface, or Network
Isolation Boundary
The next figure shows the physical layout of a Terminator I/O system, as viewed from the front. In addition to the basic circuits covered above, AC-powered bases include an auxiliary +24VDC power supply with its own isolation boundary. Since the supply output is isolated from the other three circuits, it can power input and/or output circuits! Terminator I/O System
Primary Side Power Input
Main Power Supply
Slave Internal
CPU
+24VDC Out
Auxiliary +24VDC Supply
Secondary, or Logic side Backplane
Comm.
Input Module
Output Module
Operator Interface
Inputs Commons
Outputs Commons
Field Side
Supply for Output Circuit
Page 30
3–3 I/O Wiring and Specifications
Powering I/O Circuits with the Auxiliary Supply
In some cases, using the built-in auxiliary +24VDC supply can result in a cost savings for your control system. It can power combined loads up to 500mA if power budget allows. Be careful not to exceed the current rating of the supply. If you are the system designer for your application, you may be able to select and design in field devices which can use the +24VDC auxiliary supply. All AC power supplies feature an internal auxiliary supply. If input devices AND output loads need +24VDC power, the auxiliary supply may be able to power both circuits as shown in the following diagram.
AC Power Power Input
Auxiliary +24VDC Supply
+
Terminator I/O System Input Module
Output Module
Inputs
Outputs Com.
Com.
– Loads
+
–
–
DC Power
Terminator I/O System Power Input
Input Module
Output Module
Inputs
Outputs Com.
Com.
Loads
Installation and Safety Guidelines
+
I/O Wiring and Specifications
DC-powered units are designed for application environments in which low-voltage DC power is more readily available than AC. These include a wide range of battery–powered applications, such as remotely-located control, in vehicles, portable machines, etc. For this type of application, all input devices and output loads typically use the same DC power source. Typical wiring for DC-powered applications is shown in the following diagram.