Page 21

2–8 Installation and Wiring

Assembling the Components Assembling the I/O Modules and Bases 1

Insert Module into Base 1. Pull base arm back to allow space for module to enter base. 2. Align module slides with base track.

Installation and Power Wiring

3. Press module firmly into base.

3 2

Mounting the Components on DIN Rail

Installation and Safety Guidelines

2

3

1 NOTE: Do not force the base controller on the DIN rail. Due to slight size variations in different manufacturers’ DIN rail, it may be necessary to first unlatch the locking tab, rotate the module into place, then latch the locking tab.

Install on DIN Rail 1. Make sure the locking tab is in the latched position (pushed in). 2. Hook upper tab over upper flange of DIN rail. 3. Tilt the unit toward DIN rail until it snaps securely to DIN rail.

Page 22

2–9 Installation and Wiring

Connecting the Components on the DIN Rail

Slide the module assembly on the DIN rail until the clip arm attaches securely to the adjacent module.

Installation and Power Wiring

Slide Assembly into Position on DIN Rail

NOTE: One power supply is required in the leftmost component position followed by the base controller. Additional power supplies should be added between I/O modules as necessary to meet power budget requirements (see page 3–18). Each power supply powers the modules to its right, but is interrupted by the next power supply.

Removing I/O Modules from the Base Installation and Safety Guidelines To remove the module from the base, grip the center of the base arm and rotate outward releasing the module. Lift the module from the base. To remove a module assembly from the DIN rail, lift the clip arm up and slide the module assembly away from the adjacent module. Pull the locking tab down (out) and lift the assembly off the DIN rail. Refer to the “I/O Module Hot Swap Feature” section in Chapter 3 to remove an I/O module with Terminator I/O system power ON.

Page 23

2–10 Installation and Wiring

Multiple Power Supplies / Local Expansion Configurations

Installation and Power Wiring

Multiple Power Supply Configuration

It is possible to have multiple power supplies in a single slave (node) system to meet power budget requirements. One power supply is required in the leftmost component position followed by the base controller. Additional power supplies should be added between I/O modules as necessary to meet power budget requirements. There are some restrictions on where power supplies can be placed in the system when using the T1K–05CBL–RR(–1) expansion base cable. Each power supply powers the modules to its right, but is interrupted by the next power supply. Each slave (node) system can be divided into one row of base I/O plus two rows of local expansion I/O up to a total of 16 I/O modules. Expansion cables are available in two configurations: one that passes 24VDC base power through and one that does not (both cables pass the 5VDC base power). The (–1) version of the expansion cables pass 24VDC through on an isolated wire. Any local expansion DC input modules configured for “internal power” (current sourcing) must either have a power supply preceeding it on the same base or, have a (–1) version cable pass 24VDC from a power supply on the preceeding base.

Example Using Two T1K–10CBL(–1) Expansion Cables Base Controller

Power Supply #1 (a power supply must be the leftmost component in a system followed by the base controller)

Local Base I/O I/O Addressing

Power Supply #2

Installation and Safety Guidelines

T1K–10CBL(–1)

1st Local Expansion I/O I/O Addressing T1K–10CBL

Power Supply #3

2nd Local Expansion I/O I/O Addressing

System shown above: The first power supply powers the base controller and the two I/O modules to its right. The second power supply powers the the two modules to its right and the three I/O modules on the first local expansion base. Power Supply #3 powers the three I/O modules to its right on the second local expansion base. This is only an example and the power budget requirements vary depending on the I/O modules used.

Page 24

2–11 Installation and Wiring

Example Using T1K–05CBL–RR(–1) and T1K–05CBL–LL(–1) Expansion Cables Power Supply #1

Base Controller

(a power supply must be the leftmost component in a system followed by the base controller)

Local Base I/O

I/O Addressing

Power Supply #2

T1K–05CBL–RR(–1)

Installation and Power Wiring

Do not connect a T1K–05CBL–LL(–1) to the left side of the local I/O base.

1st Local Expansion I/O I/O Addressing A power supply cannot be used on a base that is connected to a system by a T1K–05CBL–RR(–1)

T1K–05CBL–LL(–1)

2nd Local Expansion I/O Power Supply #3

System shown above: The first power supply powers the base controller and the two I/O modules to its right. The second power supply powers the the two modules to its right and the three I/O modules on the first local expansion base. When a T1K–05CBL–RR(–1) is used, the expansion I/O assignments are from right to left (reversed). A power supply cannot be used on a base that is connected to a system by a T1K–05CBL–RR(–1). Power Supply #3 powers the three I/O modules to its right on the second local expansion base.This is only an example and the power budget requirements vary depending on the I/O modules used.

Installation and Safety Guidelines

I/O Addressing

Page 25

2–12 Installation and Wiring

Example Using T1K–10CBL(–1) and T1K–05CBL–RR(–1) Expansion Cables Base Controller

Power Supply #1 (a power supply must be the leftmost component in a system followed by the base controller)

Local Base I/O Power Supply #2

Installation and Power Wiring

I/O Addressing

T1K–10CBL(–1)

1st Local Expansion I/O Power Supply #3 I/O Addressing T1K–05CBL–RR(–1)

A power supply cannot be used on a base that is connected to a system by a T1K–05CBL–RR(–1)

Installation and Safety Guidelines

2nd Local Expansion I/O I/O Addressing

System shown above: The first power supply powers the base controller and the two I/O modules to its right. The second power supply powers the the two modules to its right. Power Supply #3 powers the three I/O modules to its right on the first local expansion base and the three I/O modules on the second local expansion base. When a T1K–05CBL–RR(–1) is used, the expansion I/O assignments are from right to left (reversed). A power supply cannot be used on a base that is connected to a system by a T1K–05CBL–RR(–1). This is only an example and the power budget requirements vary depending on the I/O modules used.

Page 26

2–13 Installation and Wiring

Example Using T1K–05CBL–RR(–1) Expansion Cable Base Controller

Power Supply #1 (a power supply must be the leftmost component in a system followed by the base controller)

Local Base I/O

T1K–05CBL–RR(–1)

Installation and Power Wiring

Power Supply #2 I/O Addressing

1st Local Expansion I/O I/O Addressing A power supply cannot be used on a base that is connected to a system by a T1K–05CBL–RR(–1)

Installation and Safety Guidelines

System shown above: The first power supply powers the base controller and the two I/O modules to its right. The second power supply powers the the two modules to its right and the five I/O modules on the first local expansion base. When a T1K–05CBL–RR(–1) is used, the expansion I/O assignments are from right to left (reversed). A power supply cannot be used on a base that is connected to a system by a T1K–05CBL–RR(–1). This is only an example and the power budget requirements vary depending on the I/O modules used.

Page 27

2–14 Installation and Wiring

Power Supply Wiring Guidelines Power Wiring

The diagram below shows the terminal connections located on the Terminator I/O AC and DC power supplies. The table below shows the wire guage size and recommended torque for the power supply screw terminals.

Installation and Power Wiring

NOTE: You can connect either a 110 VAC or 220 VAC supply to the AC terminals. Special wiring or jumpers are not required as with some of the other DirectLOGIC products.

110/220 VAC Terminal Strip

12/24 VDC Terminal Strip

95-240V 50/60Hz 50VA

12-24 20W

AC (L)

+ ____ - ____

Installation and Safety Guidelines

AC (N)

+ 24V -

LG

OUT

G

LG G

T1K-01DC T1K-01AC Power Supply

T1K–01AC

T1K–01DC

Wire Guage

Solid: 24 – 12 AWG Stranded: 24 – 12 AWG

Solid: 24 – 12 AWG Stranded: 24 – 12 AWG

Recommended Torque

4.43 – 5.31 lb–in (0.5 – 0.6 Nm)

4.43 – 5.31 lb–in (0.5 – 0.6 Nm)

Page 28

I/O Wiring and Specifications

13

In This Chapter. . . ., I/O Wiring Strategies, I/O Modules Position, Wiring, and Specifications, I/O Module Hot Swap Feature, Calculating the Power Budget, I/O Specification Terms

Page 29

3–2 I/O Wiring and Specifications

I/O Wiring Strategies

Terminator I/O System Isolation Boundaries

The Terminator I/O system is very flexible and will work in many different wiring configurations. By studying this section before actual installation, you can probably find the best wiring strategy for your application. This will help to lower system cost, wiring errors, and avoid safety problems. Terminator I/O system circuitry is divided into three main regions separated by isolation boundaries, shown in the drawing below. Electrical isolation provides safety, so that a fault in one area does not damage another. A transformer in the power supply provides magnetic isolation between the primary and secondary sides. Opto-couplers provide optical isolation in Input and Output circuits. This isolates logic circuitry from the field side, where factory machinery connects. Note the discrete inputs are isolated from the discrete outputs, because each is isolated from the logic side. Isolation boundaries protect the operator interface (and the operator) from power input faults or field wiring faults. When wiring a Terminator I/O system, it is extremely important to avoid making external connections that connect logic side circuits to any other. Primary Side

Terminator I/O System

I/O Wiring and Specifications Installation and Safety Guidelines

Secondary, or Logic side

Power Input

Main Power Supply

Isolation Boundary

Slave CPU

Field Side

(backplane)

Input Module

Inputs

(backplane)

Output Module

Outputs

Programming Device, Operator Interface, or Network

Isolation Boundary

The next figure shows the physical layout of a Terminator I/O system, as viewed from the front. In addition to the basic circuits covered above, AC-powered bases include an auxiliary +24VDC power supply with its own isolation boundary. Since the supply output is isolated from the other three circuits, it can power input and/or output circuits! Terminator I/O System

Primary Side Power Input

Main Power Supply

Slave Internal

CPU

+24VDC Out

Auxiliary +24VDC Supply

Secondary, or Logic side Backplane

Comm.

Input Module

Output Module

Operator Interface

Inputs Commons

Outputs Commons

Field Side

Supply for Output Circuit

Page 30

3–3 I/O Wiring and Specifications

Powering I/O Circuits with the Auxiliary Supply

In some cases, using the built-in auxiliary +24VDC supply can result in a cost savings for your control system. It can power combined loads up to 500mA if power budget allows. Be careful not to exceed the current rating of the supply. If you are the system designer for your application, you may be able to select and design in field devices which can use the +24VDC auxiliary supply. All AC power supplies feature an internal auxiliary supply. If input devices AND output loads need +24VDC power, the auxiliary supply may be able to power both circuits as shown in the following diagram.

AC Power Power Input

Auxiliary +24VDC Supply

+

Terminator I/O System Input Module

Output Module

Inputs

Outputs Com.

Com.

– Loads

+

–

–

DC Power

Terminator I/O System Power Input

Input Module

Output Module

Inputs

Outputs Com.

Com.

Loads

Installation and Safety Guidelines

+

I/O Wiring and Specifications

DC-powered units are designed for application environments in which low-voltage DC power is more readily available than AC. These include a wide range of battery–powered applications, such as remotely-located control, in vehicles, portable machines, etc. For this type of application, all input devices and output loads typically use the same DC power source. Typical wiring for DC-powered applications is shown in the following diagram.