Page 31

3–4 I/O Wiring and Specifications

Powering I/O Circuits Using Separate Supplies

In most applications it will be necessary to power the input devices from one power source, and to power output loads from another source. Loads often require high-energy AC power, while input sensors use low-energy DC. If a machine operator is likely to come in close contact with input wiring, then safety reasons also require isolation from high-energy output circuits. It is most convenient if the loads can use the same power source as the Terminator I/O system, and the input sensors can use the auxiliary supply, as shown to the left in the figure below. If the loads cannot be powered from the system supply, then a separate supply must be used as shown to the right in the figure below.

AC Power Power Input

Auxiliary +24VDC Supply

Installation and Safety Guidelines

Power Input

Terminator I/O System

Terminator I/O System

Input Module

Output Module

Inputs

Outputs Com.

Com.

–

Auxiliary +24VDC Supply

+

I/O Wiring and Specifications

+

AC Power

Input Module

Output Module

Inputs

Outputs Com.

Com.

–

Loads

Loads

Load Supply

Some applications will use the external power source to also power the input circuit. This typically occurs on DC-powered systems, as shown in the drawing below to the left. The inputs share the system power source supply, while the outputs have their own separate supply. A worst-case scenario, from a cost and complexity view-point, is an application which requires separate power sources for the Terminator I/O system, input devices, and output loads. The example wiring diagram below on the right shows how this can work, but also the auxiliary supply output is an unused resource. You will want to avoid this situation if possible. +

+

–

–

DC Power AC Power Power Input

Terminator I/O System

Terminator I/O System

Power Input

Input Module

Output Module

Inputs

Outputs Com.

Com.

Auxiliary +24VDC Supply

+ Loads

Load Supply

Input Module

Output Module

Inputs

Com.

Outputs Com.

Input Supply

Loads

– Load Supply

Page 32

3–5 I/O Wiring and Specifications

Sinking / Sourcing Concepts

Before going further in the study of wiring strategies, you must have a solid understanding of “sinking” and “sourcing” concepts. Use of these terms occurs frequently in input or output circuit discussions. It is the goal of this section to make these concepts easy to understand, further ensuring your success in installation. First the following short definitions are provided, followed by practical applications.

Sinking = provides a path to supply ground (–) Sourcing = provides a path to supply source (+) First you will notice these are only associated with DC circuits and not AC, because of the reference to (+) and (–) polarities. Therefore, sinking and sourcing terminology only applies to DC input and output circuits. Input and output points that are sinking or sourcing only can conduct current in only one direction. This means it is possible to connect the external supply and field device to the I/O point with current trying to flow in the wrong direction, and the circuit will not operate. However, you can successfully connect the supply and field device every time by understanding “sourcing” and “sinking”. Terminator I/O System Input (sinking) +

Input Sensing

– Common

Sinking Input

Sinking Output Terminator I/O System Input

+ –

Input Sensing

–

Sourcing Output

Input Sensing Input

+ Common

Terminator I/O System Common +

Load

Output Switch

Common

Sourcing Input

–

Terminator I/O System Output

Terminator I/O System Common Output Switch

+ –

Output Load

Installation and Safety Guidelines

By applying the circuit principle above to the four possible combinations of input/output sinking/sourcing types as shown below. The I/O module specifications at the end of this chapter list the input or output type.

I/O Wiring and Specifications

For example, the figure to the right depicts a “sinking” input. To properly connect the external supply, you will have to connect it so the input provides a path to ground (–). Start at the Terminator I/O system input terminal, follow through the input sensing circuit, exit at the common terminal, and connect the supply (–) to the common terminal. By adding the switch, between the supply (+) and the input, the circuit has been completed . Current flows in the direction of the arrow when the switch is closed.

Page 33

3–6 I/O Wiring and Specifications

Installation and Safety Guidelines

I/O Wiring and Specifications

I/O “Common” In order for an I/O circuit to operate, Terminal Concepts current must enter at one terminal and exit at another. Therefore, at least two terminals are associated with every I/O point. In the figure to the right, the Input or Output terminal is the main path for the current. One additional terminal must provide the return path to the power supply. If there was unlimited space and budget for I/O terminals, every I/O point could have two dedicated terminals as the figure above shows. However, providing this level of flexibility is not practical or even necessary for most applications. So, most Input or Output points are in groups which share the return path (called commons). The figure to the right shows a group (or bank) of 4 input points which share a common return path. In this way, the four inputs require only five terminals instead of eight.

Terminator I/O System Main Path I/O (I/O Point) Circuit

Field Device + –

Return Path

Terminator I/O System

Input 1

Input Sensing

Input 2 Input 3 Input 4 + –

Common

NOTE: In the circuit above, the current in the common path is 4 times any channel’s input current when all inputs are energized. This is especially important in output circuits, where heavier gauge wire is sometimes necessary on commons. Most Terminator I/O input and output modules group their I/O points into banks that share a common return path. The best indication of I/O common grouping is on the wiring label, such as the one shown to the right. The miniature schematic shows two circuit banks with four output points in each. The common terminal for each is labeled “COM 0” and “COM 1”, respectively. In the wiring label example, the positive terminal of a DC supply connects to the common terminals. Some symbols you will see on the wiring labels, and their meanings are: AC supply

DC supply –

Input Switch

AC or DC supply

+

Output Load L

L L L L 0

1

2

COM 0

3

L L L L 4

5

6

COM 1

7

Page 34

3–7 I/O Wiring and Specifications

Connecting DC I/O In the previous section on Sourcing and Sinking concepts, the DC I/O circuits were explained to only allow current to flow one way. This is also true for many of the field to “Solid State” devices which have solid-state (transistor) interfaces. In other words, field devices Field Devices can also be sourcing or sinking. When connecting two devices in a series DC circuit, one must be wired as sourcing and the other as sinking. Solid State Input Sensors

Terminator I/O DC input modules are flexible because they detect current flow in either direction, so they can be wired as either sourcing or sinking. In the following circuit, a field device has an open-collector NPN transistor output. It sinks current from the input point, which sources current. The power supply can be the +24 auxiliary supply or another supply (+12 VDC or +24VDC), as long as the input specifications are met. Field Device

Terminator I/O System DC Input Input (sourcing)

Output (sinking) Supply Ground

–

+

Common

Field Device +V

Terminator I/O System DC Input Input Output (sourcing) Ground

Common

Sometimes an application requires connecting an output point to a solid state input on a device. This type of connection is usually made to carry a low-level control signal, not to send DC power to an actuator. Several of the Terminator I/O DC output modules are the sinking type. This means that each DC output provides a path to ground when it is energized. In the following circuit, the output point sinks current to the output common when energized. It is connected to a sourcing input of a field device input.

Terminator I/O System DC Sinking Output Power +DC pwr Output (sinking)

+

Common

–

Field Device +V Input (sourcing) 10–30 VDC Ground

Installation and Safety Guidelines

Solid State Output Loads

(sinking)

I/O Wiring and Specifications

In the next circuit, a field device has an open-emitter PNP transistor output. It sources current to the input point, which sinks the current back to ground. Since the field device is sourcing current, no additional power supply is required.

Page 35

3–8 I/O Wiring and Specifications

In the next example a sinking DC output point is connected to the sinking input of a field device. This is a little tricky, because both the Terminator I/O system output and field device input are sinking type. Since the circuit must have one sourcing and one sinking device, a sourcing capability needs to be added to the Terminator I/O system output by using a pull-up resistor. In the circuit below, a Rpull-up is connected from the output to the DC output circuit power input. Terminator I/O System DC Output Power +DC pwr Field Device

R pull-up (sourcing) (sinking)

Output +

Input (sinking)

–

Ground

R input

Supply

I/O Wiring and Specifications

Common

NOTE 1: DO NOT attempt to drive a heavy load (>25 mA) with this pull-up method NOTE 2: Using the pull-up resistor to implement a sourcing output has the effect of inverting the output point logic. In other words, the field device input is energized when the Terminator I/O system output is OFF, from a ladder logic point-of-view. Your ladder program must comprehend this and generate an inverted output. Or, you may choose to cancel the effect of the inversion elsewhere, such as in the field device. It is important to choose the correct value of R pull-up. In order to do so, you need to know the nominal input current to the field device (I input) when the input is energized. If this value is not known, it can be calculated as shown (a typical value is 15 mA). Then use I input and the voltage of the external supply to compute R pull-up. Then calculate the power Ppull-up (in watts), in order to size Rpull-up properly.

Installation and Safety Guidelines

I input

=

R pull-up =

V input (turn–on) R input V supply – 0.7 I input

– R input

P pull-up =

V supply

2

R pullup

Of course, the easiest way to drive a sinking input field device as shown below is to use a DC sourcing output module. The Darlington NPN stage will have about 1.5 V ON-state saturation, but this is not a problem with low-current solid-state loads. Terminator I/O DC Sourcing Output +DC pwr

Common Field Device Output (sourcing) +

Input (sinking)

–

Ground

Supply

R input

Page 36

3–9 I/O Wiring and Specifications

Relay Output Guidelines

Several output modules in the Terminator I/O family feature relay outputs: T1K–08TR, T1K–16TR, and T1K–08TRS. Relays are best for the following applications: • Loads that require higher currents than the solid-state outputs can deliver • Cost-sensitive applications • Some output channels need isolation from other outputs (such as when some loads require different voltages than other loads) Some applications in which NOT to use relays: • Loads that require currents under 10 mA S Loads which must be switched at high speed or heavy duty cycle Relay output module contacts are availabe in Form A type, or SPST (single pole, single throw) normally open. Some relay output module’s relays share common terminals, which connect to the wiper contact in each relay of the bank. Other relay modules have relays which are completely isolated from each other. In all cases, the module drives the relay coil when the corresponding output point is on.

Terminator I/O Relay Output

Inductive Field Device Input

Output

R C Common

Supply

+

–

Common

Installation and Safety Guidelines

Relay contacts wear according to the amount of relay switching, amount of spark created at the time of open or closure, and presence of airborne contaminants. However, there are some steps you can take to help prolong the life of relay contacts: • Switch the relay on or off only when the application requires it. • If you have the option, switch the load on or off at a time when it will draw the least current. • Take measures to suppress inductive voltage spikes from inductive DC loads such as contactors and solenoids (circuit given below).

I/O Wiring and Specifications

Prolonging Relay Contact Life

Relay with Form A contacts

Page 37

3–10 I/O Wiring and Specifications

Adding external contact protection may extend relay life beyond the number of contact cycles listed in the specification tables for relay modules. High current inductive loads such as clutches, brakes, motors, direct-acting solenoid valves, and motor starters will benefit the most from external contact protection. The RC network must be located close to the relay module output connector. To find the values for the RC snubber network, first determine the voltage across the contacts when open, and the current through them when closed. If the load supply is AC, then convert the current and voltage values to peak values: Now you are ready to calculate values for R and C, according to the formulas: 2

I

C (mF) =

R (W) =

10

V 10 x I x

, where x= 1 +

50 V

C minimum = 0.001 mF, the voltage rating of C must be w V, non-polarized R minimum = 0.5 W, 1/2 W, tolerance is " 5%

I/O Wiring and Specifications

For example, suppose a relay contact drives a load at 120VAC, 1/2 A. Since this example has an AC power source, first calculate the peak values: Ipeak = Irms x 1.414, = 0.5 x 1.414 = 0.707 Amperes Vpeak = Vrms x 1.414 = 120 x 1.414 = 169.7 Volts Now, finding the values of R and C,: C (mF) =

2

=

10 R (W) =

Installation and Safety Guidelines

I x= 1 +

10

V 10 x I x 50 169.7

0.707

2

= 0.05 mF, voltage rating w 170 Volts

, where x= 1 +

= 1.29

50 V

R (W) =

169.7 10 x 0.707 1.29

= 26 W, 1/2 W, " 5%

If the contact is switching a DC inductive load, add a diode across the load as near to load coil as possible. When the load is energized the diode is reverse-biased (high impedance). When the load is turned off, energy stored in its coil is released in the form of a negative-going voltage spike. At this moment the diode is forward-biased (low impedance) and shunts the energy to ground. This protects the relay contacts from the high voltage arc that would occur as the contacts are opening. For best results, follow these guidelines in using a noise suppression diode: • DO NOT use this circuit with an AC power supply. • Place the diode as close to the inductive field device as possible. • Use a diode with a peak inverse voltage rating (PIV) at least 100 PIV, 3A forward current or larger. Use a fast-recovery type (such as Schottky type). DO NOT use a small-signal diode such as 1N914, 1N941, etc. S Be sure the diode is in the circuit correctly before operation. If installed backwards, it short-circuits the supply when the relay energizes.

Page 38

3–11 I/O Wiring and Specifications

I/O Modules Position, Wiring, and Specifications Multiple Power Supply Configuration

It is possible to have multiple power supplies in a single slave (node) system to meet power budget requirements. One power supply is required in the leftmost component position followed by the base controller. Additional power supplies should be added between I/O modules as necessary to meet power budget requirements (there are some restrictions on where power supplies can be placed in the system when using the T1K–05CBL–RR(–1) expansion base cable). Each power supply powers the modules to its right, but is interrupted by the next power supply. Each slave (node) system can be divided into one row of base I/O plus two rows of local expansion I/O up to a total of 16 I/O modules. Expansion cables are available in two configurations: one that passes 24VDC base power through and one that does not (both cables pass the 5VDC base power). The (–1) version of the expansion cables pass 24VDC through on an isolated wire. Any local expansion DC input modules configured for “internal power” (current sourcing) must either have a power supply preceeding it on the same base or, have a (–1) version cable pass 24VDC from a power supply on the preceeding base.

Overview of I/O Expansion Configurations

There are several expansion I/O system configurations that can be created by using the local expansion cables. There are some restrictions on where power supplies can be placed in the system when using the T1K–05CBL–RR(–1) expansion base cable. Refer to chapter 2 for details on the example systems shown below.

Example Using T1K–10CBL(–1) and T1K–05CBL–RR(–1) Expansion Cables

Installation and Safety Guidelines

Example Using T1K–05CBL–RR(–1) Expansion Cable

Example Using T1K–05CBL–RR(–1) and T1K–05CBL–LL(–1) Expansion Cables

I/O Wiring and Specifications

Example Using Two T1K–10CBL(–1) Expansion Cables

Page 39

3–12 I/O Wiring and Specifications

Which Modules The table below lists by category those modules that you may use in a system. can go in a System Terminator I/O Module / Unit

Slave System

Base Controller

Only one per slave (node) system. Mount to the right of the first power supply.

Additional Power Supplies

Yes (see Note)

DC Input Modules

Yes

AC Input Modules

Yes

DC Output Modules

Yes

AC Output Modules

Yes

Relay Output Modules

Yes

Analog Modules (volt, current, temp)

Yes

CTRIO Counter I/O Modules

Yes

NOTE: One power supply is required in the leftmost component position followed by the

I/O Wiring and Specifications

Discrete Module Status Indicators

Installation and Safety Guidelines

Base Controller. Additional power supplies should be added between I/O modules as necessary to meet power budget requirements. Each power supply powers the modules to its right, but is interrupted by the next power supply. It is not mandatory to have a power supply in the leftmost position on an expansion rack. Expansion cables are available in two configurations: one that passes 24VDC base power through and one that does not.

Color Coding of I/O The Terminator I/O family of I/O modules have a color coding scheme to help you quickly identify the module as either a power supply, an input module or an output Modules module. This is done through a color mark indicator located on the front of each module. The color scheme is listed below:

The discrete I/O modules provide LED status indicators to show the status of the I/O points. Most of the output modules have additional LEDs to indicate a blown fuse. Status indicators

Color marks

Module Type

Color Code

Power Supply

Green

Base Controller

White

Discrete / Analog Input

Blue

Discrete / Analog Output

Red

Page 40

3–13 I/O Wiring and Specifications

Wiring the I/O Module Bases

There are two types of terminal bases for the Terminator I/O modules: screw clamp and spring clamp connectors. The recessed screw heads help minimize the risk of someone accidentally touching active wiring. WARNING: For some modules, field device power may still be present on the terminal block even though the Terminator I/O system power is turned off. To minimize the risk of electrical shock, check all field device power before you remove a wire.

Screw Clamp Terminals

Spring Clamp Terminals

I/O Wiring and Specifications spring clamp type

Recommended Torque

1.77 – 3.54 lb–inch (0.2 – 0.4 Nm)

–

Recommended Screwdriver Blade Size

0.02in.x 0.125in. (0.5mm x 3mm)

push in on clamp using screwdriver blade size: (0.016 x 0.079.to 0.032 x0.16)in. (0.4 x 2 to 0.8 x 4)mm

Wire Gauge Size solid conductor: 24–12AWG stranded conductor: 24–12AWG solid conductor: 24–14AWG stranded conductor: 24–14AWG*

*Twist conductors before inserting into gate

Installation and Safety Guidelines

Terminal Type screw type