Page 41
3–14 I/O Wiring and Specifications
Selecting Internal 24VDC Power Supply
The DC input field devices can be powered from the integrated 24 VDC power supply from the power supply bus. The T1K–08ND3 and T1K–16ND3 DC input modules have jumpers for selecting internal 24VDC power supply available for 2 and 3–wire field devices. The analog I/O and DC output modules do not have direct access to the internal bussed 24 VDC. Jumpers located under top cover of T1K–08ND3 and T1K–16ND3
Position jumper to set the module to sink or source current
Installation and Safety Guidelines
I/O Wiring and Specifications
Position jumper to set the module to provide internally bussed 24VDC or if external power is to be supplied
The diagram below shows DC input devices using internally bussed 24VDC for Using Internal 24VDC Base Power power. If the module is set to “sink” current , +24VDC power is supplied to the input module base “COM” terminals and 0VDC is supplied to the module base “V” terminals. If the module is set to “source” current, +24VDC is supplied to the input module base “V” terminals and 0VDC is supplied to the module base “COM” terminals.
Using Internally Bussed 24VDC (T1K–08ND3, T1K–16ND3 only)
2 and 3–wire input field devices
Page 42
3–15 I/O Wiring and Specifications
External 24VDC Wiring Options
DC output and analog I/O modules do not have direct access to the internally bussed 24VDC. External user supplied 24 VDC power, or auxiliary 24 VDC from the T1K–01AC, can be applied directly to one end of the DC I/O module base terminal (V and COM) rows and jumpered across each base as needed in a system. This creates a “bus” (row) of 24VDC and a bus of 0VDC power. Be sure not to exceed the supply’s power budget. NOTE: If you intend to use the I/O module Hot Swap feature, refer to the “Check External 24VDC Wiring Before Hot Swapping” section on page 3–17. The external 24VDC wiring options below are not recommended when intending to Hot Swap DC output or analog I/O modules.
Using T1K–01AC for External 24VDC Power
I/O Wiring and Specifications
Use T1K–01AC external 24VDC create a power bus for the DC modules
Place wire jumpers from one DC I/O module base to another as necessary to continue the external 24VDC power bus
Use an external 24VDC power supply to create a power bus for the DC modules
Place wire jumpers from one DC I/O module base to another as necessary to continue the external 24VDC power bus
Installation and Safety Guidelines
Using an External 24VDC Power Supply
Page 43
3–16 I/O Wiring and Specifications
I/O Wiring Checklist
Terminal Type
Screw Type
Spring Type
Wire Guage
Solid: 24 – 12 AWG Stranded: 24 – 12 AWG*
Solid: 24 – 14 AWG Stranded: 24 – 14 AWG*
Recommended Torque
1.77 – 3.54 lb–in (0.2 – 0.4 Nm)
–
I/O Wiring and Specifications
*Twist conductors before inserting into gate 2. Always use a continuous length of wire, do not combine wires to attain a needed length. 3. Use the shortest possible wire length. 4. Use wire trays for routing where possible. 5. Avoid running wires near high–energy wiring. 6. Avoid running input wiring close to output wiring where possible. 7. To minimize voltage drops when wires must run a long distance, consider using multiple wires for the return line. 8. Avoid running DC wiring in close proximity to AC wiring where possible. 9. Avoid creating sharp bends in the wires. 10. To reduce the risk of having a module with a blown fuse, we suggest you add external fuses to your I/O wiring. A fast blow fuse, with a lower current rating than the I/O module fuse can be added to each common, or a fuse with a rating of slightly less than the maximum current per output point can be added to each output. Output Module Fusing
Installation and Safety Guidelines
Use the following guidelines when wiring the base terminals in your system. 1. There is a limit to the size of wire the terminals can accept. The table below lists the suggested AWG for each module type.
All Terminator I/O discrete output modules have internal user–replaceable fuses. For fuse specifications and part numbers for a specific output module, refer to the output module specifications later in this chapter. Be sure to remove system power or disable outputs via the Base Contoller switch before attempting to remove the I/O module from its base. Refer to the next section “I/O Module Hot Swap Feature” if attempting to remove an I/O module with the system power ON. Fuses located under top cover of output modules Note: A fuse blown indicator illuminates only when a fuse is blown and an associated output point is turned ON by the program.
Replaceable Fuses
Page 44
3–17 I/O Wiring and Specifications
I/O Module Hot Swap Feature The “Hot Swap” feature allows Terminator I/O modules to be replaced with Terminator I/O system power ON. Be careful not to touch the terminals with your hands or any conductive material to avoid the risk of personal injury or equipment damaged. Always remove power if it is equally convenient to do so. WARNING: Only authorized personnel fully familiar with all aspects of the application should replace an I/O module with system power ON. The following Base Controllers support the “Hot Swap” feature. Base Controller
Supports “Hot Swap”
T1K–DEVNETS
Yes
T1K–MODBUS
Yes
T1K–RSSS
Yes
T1H–EBC(100)
Yes (refer to T1H–EBC–M or T1H–PBC–M User Manual for “Hot Swap” information)
T1H–PBC
The following module types can be “Hot Swapped”.
Check External 24VDC Wiring Before Hot Swapping
No
Base Controller
No
I/O Modules (discrete / analog)
Yes
The following steps explain how to “Hot Swap” an I/O module. 1. Remove I/O module from base. 2. Install new I/O module of the same part number. 3. Verify that the Base Controller LEDs have returned to normal. A feature that may be used in a non–continuous process application is the Outputs Enable/Disble switch. The switch is located on the front of the T1K–(DEVNETS, MODBUS, RSSS) base controllers. When the switch is in the Disable position all outputs are disabled (OFF), although discrete and analog input data continues to be read. This option may be used at a convenient time during the process application to replace an I/O module. Before “Hot Swapping” an analog I/O module or a DC output module in a Terminator I/O system, make sure that each of the analog I/O and DC output module’s 24VDC and 0VDC base terminals are wired directly to the external power supply individually (see diagram below). If the external 24VDC / 0VDC is jumpered from base to base in a daisy chain fashion, and an analog I/O or DC output module is removed from its base, the risk of disconnecting the external 24VDC to the subsequent I/O modules exists.
Wire each analog I/O and DC output module independently to the external power supply. Do not jumper modules together creating 24VDC bus for Hot Swap.
Installation and Safety Guidelines
Outputs Enable/Disable Switch
Can be “Hot Swapped”
Power Supply
I/O Wiring and Specifications
Hot Swap: I/O Module Replacement
Module
Page 45
3–18 I/O Wiring and Specifications
Calculating the Power Budget Managing your Power Resource
When determining the types and quantity of I/O modules you will be using in the Terminator I/O system, it is important to remember there is a limited amount of power available from the power supply to the system. We have provided a chart to help you easily see the amount of power available with AC and DC power supplies. At the end of this section you will also find an example of power budgeting and a worksheet showing sample calculations. If the I/O you chose exceeds the maximum power available from the power supply you can resolve the problem by simply adding another power supply . WARNING: It is extremely important to calculate the power budget correctly. If you exceed the power budget, the system may operate in an unpredictable manner which may result in a risk of personal injury or equipment damage.
Installation and Safety Guidelines
I/O Wiring and Specifications
Power Supply Specifications
The following chart shows the amount of current supplied by the Terminator I/O power supply. Use this to calculate the power budget for your system. The Auxiliary 24V Power Source mentioned in the table can be used to power field devices or modules that require an external 24VDC.
AC Power Supply
5VDC Current Auxiliary 24VDC Supplied in mA Power Source (internal) Current Supplied in mA.
DC Power Supply
5VDC Current Auxiliary 24VDC Supplied in mA. Power Source (internal) Current Supplied in mA.
T1K–01AC
2000
300
T1K–01DC
2000
– a max. of 500mA @ 24VDC can be achieved by lowering the 5VDC to 1500mA
1500
500
–
–
–
Power Supply #1 Power Supply #2 pwrbud1 Note on Power Supplies: One power supply is required in the leftmost component position (power supply #1), as shown above. Additional power supplies should be added between I/O modules as necessary to meet power budget requirements. Each power supply powers the modules to its right, but is interrupted by the next power supply. It is not mandatory to have a power supply in the leftmost position on an expansion rack. System shown above: The first power supply (ps#1) powers the network interface module and the two I/O modules to its right. The second power supply (ps#2) powers the remaining five I/O modules. This is only an example and the power budget requirements vary depending on the I/O modules used.
Page 46
3–19 I/O Wiring and Specifications
Module Power Requirements
This chart shows the amount of maximum current required for each of the Terminator I/O modules. Use this information to calculate the power budget for your system. If an external 24VDC power source is required, you can use the built-in 24VDC auxiliary supply as long as you do not exceed the power budget. If any device is connected to the Controller’s serial port that uses the 5VDC supply pin, be sure to include the device’s power consumption in your 5VDC power budget calculation. Base Controller and I/O Module Power Consumption Module
5VDC (mA)
24VDC (mA)
Base Controllers
Module
5VDC (mA)
24VDC (mA)
AC Output Modules
T1K–RSSS
250
0
T1K–08TA
250
0
T1K–DEVNETS
190
(see note 1)
T1K–16TA
450
0
T1H–EBC(100)
350
0
T1K–08TAS
300
0
T1K–MODBUS
250
0
Relay Output Modules
T1H–PBC
530
0
T1K–08TR
350
0
DC Input Modules
T1K–16TR
700
0
T1K–08ND3
35
0
T1K–08TRS
400
0
T1K–16ND3
70
0
Analog Input Modules 75
50 (see note 2)
35
0
T1F–16AD–1
75
50 (see note 2)
T1K–16NA–1
70
0
T1F–08AD–2
75
50 (see note 2)
T1F–16AD–2
75
50 (see note 2)
DC Output Modules T1K–08TD1
100
200 (see note 2)
T1F–16RTD
150
0
T1K–08TD2–1
100
0
T1F–14THM
60
70 (see note 2)
T1H–08TDS
200
0
Analog Ouput Modules
T1K–16TD1
200
400 (see note 2)
T1F–08DA–1
75
150 (see note 2)
T1K–16TD2–1
200
0
T1F–16DA–1
75
150 (see note 2)
Combination Analog Modules
T1F–08DA–2
75
150 (see note 2)
75
150 (see note 2)
T1F–8AD4DA–1
60 (see note 2
T1F–16DA–2
75 and 3) 70 (see note 2)
Specialty Modules and other devices (see note 4) T1H–CTRIO
400
0
Note 1: The T1K–DEVNETS consumes 45mA @ 11–25 VDC from the DeviceNet System. Note 2: Use T1K–01AC 24VDC auxiliary supply or external user supply. Note 3: 60mA plus 20mA per output loop Note 4: If any device is connected to the Controller’s serial port that uses the 5VDC supply pin, be sure to include the device’s power consumption in your 5VDC power budget calculation.
Important Power Budget Note: For each power supply in a system, make sure the current required by the interface and I/O modules does not exceed the current supplied at both 5VDC and 24VDC.
Installation and Safety Guidelines
T1F–8AD4DA–2
75
I/O Wiring and Specifications
T1F–08AD–1
T1K–08NA–1
AC Input Modules
Page 47
3–20 I/O Wiring and Specifications
Power Budget Calculation Example
The following example shows how to calculate the power budget for the first slave unit of an I/O system.
SLAVE (Node) # 1 Power Supply # 1 Module Part Number
5 VDC (mA) Required
Power Supplied T1K–01AC see p. 3–18
2000
300
Slave
T1H–EBC
350
0
Module
T1K–16NA–1
70
0
Module
T1K–16TA
450
0
Other (OI, etc.)
–
0
0
870
0
Maximum power required Remaining Power Available
Power Supply # 2 Part Number Power Supplied T1K–01AC see p. 3–18
I/O Wiring and Specifications
24 VDC (mA) Required
2000–870 = 1130 5 VDC (mA) Required
300 – 0
= 300
24 VDC (mA) Required 1500
500
Module
T1K–08AD–2
75
50
Module
T1K–08AD–2
75
50
Module
T1K–16TD1
200
400
Module
T1K–08TR
350
0
Module
T1K–08ND3
35
0
Other
–
0
0
735
500
1500–735 = 765
500 – 500 = 0 (see note 1)
Maximum power required Remaining Power Available
Installation and Safety Guidelines
Note 1: An external user power supply must be used in if the 24VDC current requirement exceeds the T1K–01AC 24VDC auxiliary supply.
1. Using the tables at the beginning of the Power Budgeting section of this chapter, fill in the information for the base controller, I/O modules, and any other devices that will use system power, including devices that use the 24 VDC output. Devices which fall into the “Other” category are devices such as an operator interface which also has power requirements but do attach as a module to the system. 2. Add the current columns starting with the slave and put the total in the row labeled “Maximum power required”. 3. Subtract the row labeled “Maximum power required” from the “Power Supplied”. Place the difference in the row labeled “Remaining Power Available”. 4. If “Maximum Power Required” is greater than “Power Supplied” in either of the two columns, the power budget will be exceeded. It will be unsafe to use this configuration and you will need to restructure your I/O configuration.
Page 48
3–21 I/O Wiring and Specifications
Power Budget Worksheet SLAVE # _________ Power Supply #
Module Part Number
5 VDC (mA) (required)
Auxiliary Power Source 24 VDC Output (mA) (required)
Power Supplied
I/O Wiring and Specifications
Maximum power required Remaining Power Available
Installation and Safety Guidelines
Other
Page 49
3–22 I/O Wiring and Specifications
Installation and Safety Guidelines
I/O Wiring and Specifications
I/O Specification Terms Inputs or Outputs Per Module
Indicates number of input or output points per module and designates current sinking, current sourcing, or either.
Commons Per Module
Number of commons per module and their electrical characteristics.
Input Voltage Range
The operating voltage range of the input circuit.
Output Voltage Range
The operating voltage range of the output circuit.
Peak Voltage
Maximum voltage allowed for the input circuit.
AC Frequency
AC modules are designed to operate within a specific frequency range.
ON Voltage Level
The voltage level at which the input point will turn ON.
OFF Voltage Level
The voltage level at which the input point will turn OFF.
Input Impedance
Input impedance can be used to calculate input current for a particular operating voltage.
Input Current
Typical operating current for an active (ON) input.
Minimum ON Current
The minimum current for the input circuit to operate reliably in the ON state.
Maximum OFF Current
The maximum current for the input circuit to operate reliably in the OFF state.
Minimum Load
The minimum load current for the output circuit to operate properly.
External DC Required
Some output modules require external power for the output circuitry.
ON Voltage Drop
Sometimes called “saturation voltage”, it is the voltage measured from an output point to its common terminal when the output is ON at max. load.
Maximum Leakage The maximum current a connected maximum load will receive when the output point is OFF. Current Maximum Inrush Current
The maximum current used by a load for a short duration upon an OFF to ON transition of a output point. It is greater than the normal ON state current and is characteristic of inductive loads in AC circuits.
Base Power Required
Power from the base power supply is used by the Terminator I/O modules and varies between different modules. The guidelines for using module power are explained in the power budget section of this manual.
Page 50
3–23 I/O Wiring and Specifications
OFF to ON Response
The time the module requires to process an OFF to ON state transition.
ON to OFF Response
The time the module requires to process an ON to OFF state transition.
Terminal Type
Indicates whether the terminal type is a removable or non-removable connector or a terminal.
Status Indicators
The LEDs that indicate the ON/OFF status of an input point. These LEDs are electrically located on either the logic side or the field device side of the input circuit.
Weight
Indicates the weight of the module.
Fuses
Protective device for an output circuit, which stops current flow when current exceeds the fuse rating. They may be replaceable or non–replaceable, or located externally or internally.
I/O Wiring and Specifications Installation and Safety Guidelines