Page 51

Dimensions Rev C

T1K–01AC

T1K–01DC

Input Voltage Range

110/220VAC (85–264VAC)

12/24VDC (10.8–26.4VDC)

Input Frequency

50/60Hz (47–63Hz)

–

Max. Power

50VA

20W

Max. Inrush Current

20A

10A

> 10M ohm @ 500VDC

Voltage Withstand (Dielectric)

1 min. @ 1500VAC between primary, secondary and field ground

Auxiliary 24VDC supply

300mA max.

–

Output 1: 5VDC Base Power Supplied

Voltage

5.25VDC (5.00 – 5.50VDC)

5.25VDC (5.00 – 5.50VDC)

Current a) 2.0A max. b) 1.5A max.

2.0A max.

Ripple

5% max.

5% max.

Voltage

24VDC (20.0 – 28.0 VDC)

–

Current a) 300mA max. b) 500mA max.

–

Ripple

10% max.

–

Output 2: 24VDC Base Power Supplied

Fuse

8.1 (0.32)

1 ( Primary), not replaceable

95-240V 50/60Hz 50VA

12-24VDC 20W

T1K–01AC

-AC(L)

____ + ____ -

Insulation Resistance

48 (1.89)

PWR

-AC(N)

+

24V

LG

-OUT

LG

LG

G

G

G

80 (3.15)

Specification

9.2 (0.36)

83.3 (3.28)

T1K–01AC, T1K–01DC Power Supply

3–24

Specifications

TERMINATOR

T1K-01AC

T1K-01DC

1 PULL TO UNLOCK

12/24 VDC Terminal Strip

10.3 (0.41)

mm (in.)

Power Supply #1

Note that 500mA @ 24VDC is achieved by lowering the 5VDC to 1500mA

R

Environmental Specifications Ambient Operating Temperature

32_F to 131_F (0_C to 55_C)

Storage Temperature

–4_F to 158_F (–20_C to 70_C)

Ambient Humidity

5% to 95% (Non–condensing)

Atmosphere

No corrosive gases. The level of environmental pollution = 2 (UL 840)

Vibration Resistance

MIL STD 810C, Method 514.2

Shock Resistance

MIL STD 810C, Method 516.2

Voltage Withstand

1500VAC, 1 minute

Insulation Resistance

500VDC, 10M ohm

Noise Immunity

NEMA ICS3–304 Impulse Noise 1us, 1000V

T1K–10CBL Base Expansion Cable

Power Supply #2

L

FCC class A RFI (144MHz, 430MHz 10W, 10cm)

Note 1: The T1K–DEVNETS consumes 45mA @ 11–25 VDC from the DeviceNet System Note 2: Use T1K–01AC 24VDC auxiliary supply or external user supply

Important Power Budget Note: For each power supply in a system, make sure the current required by the interface and I/O modules does not exceed the current supplied at both 5VDC and 24VDC.

Page 52

Dimensions

Specifications

9.2 (0.36) Rev A

Ethernet slave

Communications

10Base-T

Auto-configuring

I/O type/position automatically identified during power-up

Ethernet Protocols

TCP/IP, IPX, MODBUS TCP (future)

Ethernet Port

RJ45

Node Address

1 to 99 (decimal) set by rotary switches or software (0 used for setting address via software only)

Link Distance

100 meters (328 feet)

Data Transfer Rate

10Mbps

LED Indicators

MODULE GOOD (green): On = module passed diagnostic check during last power-up Fast blink = configured I/O module no longer reporting (see auto-configuring, above) Slow blink = unconfigured I/O module added to system (see auto-configuring, above) LINK GOOD (green): On = 10Base-T link pulses are being received ACTIVITY (red): On= Ethernet network activity detected ERROR (red): On = watchdog timer timeout represents hardware, communications, or network fault; power-on reset or reset within master device software

Note: All indicators re-initialize during power-up. For more information consult the T1H–EBC–M User Manual.

Communications Port Base Power Requirement

RJ12, RS232C K–Sequence protocol, ASCII (not functional when used with H2–ERM) 350mA@5VDC (EBC); Serial port supports up to 500mA@5VDC (add for power budget consumption).

General Specifications Installation Requirements mounts to right of first power supply

Operating Temperature

32° F to 131° F (0° C to 55° C)

Storage Temperature

–4° F to 158° F (–20° C to 70° C)

Relative Humidity

5 to 95% (non-condensing)

Environmental Air

No corrosive gases, pollution level = 2 (UL 840)

Vibration

MIL STD 810C 514.2

Shock

MIL STD 810C 516.2

Noise Immunity

NEMA ICS3–304 Impulse noise 1us, 1000V FCC class A RFI (144MHz, 430MHz, 10W, 10cm)

RJ45 connector

80 (3.15)

Module Type

83.3 (3.28)

T1H–EBC Ethernet Base Controller

48 (1.89) 8.1 (0.32)

RJ–12 Serial Port 1 PULL TO UNLOCK

Rotary Address Switches mm (in.)

T1H–EBC Ethernet Port Pin–out Patch (Straight–through) Cable EBC TD+ 1 TD– 2 RD+ 3 4 5 RD– 6 7 8

Crossover Cable

HUB OR/WHT OR GRN/WHT BLU BLU/WHT GRN BRN/WHT BRN

RJ45

OR/WHT OR GRN/WHT BLU BLU/WHT GRN BRN/WHT BRN

EBC

1 RD+ 2 RD– 3 TD+ 4 5 6 TD– 7 8

OR/WHT TD+ 1 OR TD– 2 GRN/WHT RD+ 3 4 5 RD– 6 GRN 7 8

RJ45

RJ45

GRN/WHT GRN OR/WHT

OR

PC 1 2 3 4 5 6 7 8

TD+ TD– RD+ RD–

RJ45

This diagram illustrates the standard wire positions in the RJ45 connector. We strongly reccommend that you use Category 5 or better, UTP cable.

T1H–EBC Serial Port Pin–out

10BaseT RJ12

8-pin RJ45 Connector (8P8C)

12 34 56

6-pin RJ12 Connector

1 2 3 4 5 6

0V 5V RXD TXD RTS CTS

Power (–) connection (GND) Power (+) connection Receive Data (RS232C) Transmit Data (RS232C Request to Send Clear to Send

3–25

1 2 3 4 5 6 78

Serial Port Pin Descriptions

Page 53

9.2 (0.36)

T1H–EBC100 Ethernet Base Controller 10/100Base-T

Auto-configuring

I/O type/position automatically identified during power-up

IP Configuration

–Obtain an IP address from a DHCP Server automatically at power–up (Default); –Dedicated IP address using NetEdit3 or HTML configuration

Ethernet Protocols

TCP/IP, UDP/IP, IPX, MODBUS TCP

Ethernet Port

RJ45

Node Address

1 to 99 (decimal) set by rotary switches or software; 0 (default, used for setting address via software only)

Link Distance

100 meters (328 feet)

Data Transfer Rate

100Mbps or 10Mbps (auto–detect)

LED Indicators

MODULE GOOD (green): On = module passed diagnostic check during last power-up Fast blink = configured I/O module no longer reporting (see auto-configuring, above) Slow blink = unconfigured I/O module added to system (see auto-configuring, above) LINK/ACTIVITY (green): On= Ethernet network activity detected 100MBIT (green): On= Ethernet activity is auto–detected at 100Mbps Off = (with LINK/ACTIVITY On) Ethernet activity is auto–detected at 10Mbps ERROR (red): On = watchdog timer timeout represents hardware, communications, or network fault; power-on reset or reset within master device software SERIAL TX (green): On= EBC RJ12 serial port is transmitting SERIAL RX (green): On= EBC RJ12 serial port is receiving

Note: All indicators re-initialize during power-up.

Serial Communications Port

RJ12, RS232C K–Sequence protocol, ASCII, MODBUS RTU (not functional when used with HX–ERM)

Base Power Requirement

350mA@5VDC (EBC100); Serial port supports up to 500mA@5VDC (add for power budget consumption).

General Specifications

RJ45 connector

80 (3.15)

Ethernet slave

Communications

48 (1.89) 8.1 (0.32)

83.3 (3.28)

Module Type

3–26

Dimensions

Specifications

RJ–12 Serial Port 1 PULL TO UNLOCK

Rotary Address Switches mm (in.)

T1H–EBC100 Ethernet Port Pin–out Patch (Straight–through) Cable EBC TD+ 1 TD– 2 RD+ 3 4 5 RD– 6 7 8

Crossover Cable

HUB OR/WHT OR GRN/WHT BLU BLU/WHT GRN BRN/WHT BRN

RJ45

OR/WHT OR GRN/WHT BLU BLU/WHT GRN BRN/WHT BRN

EBC

1 RD+ 2 RD– 3 TD+ 4 5 6 TD– 7 8

OR/WHT TD+ 1 OR TD– 2 GRN/WHT RD+ 3 4 5 RD– 6 GRN 7 8

RJ45

RJ45

GRN/WHT GRN OR/WHT

OR

PC 1 2 3 4 5 6 7 8

TD+ TD– RD+ RD–

RJ45

This diagram illustrates the standard wire positions in the RJ45 connector. We strongly reccommend that you use Category 5 or better, UTP cable.

T1H–EBC100 Serial Port Pin–out

10/100Base–T RJ12

Installation Requirements mounts to right of first power supply

Operating Temperature

32° F to 131° F (0° C to 55° C)

Storage Temperature

–4° F to 158° F (–20° C to 70° C)

Relative Humidity

5 to 95% (non-condensing)

Environmental Air

No corrosive gases, pollution level = 2 / (UL 840)

Vibration

MIL STD 810C 514.2

1 2 3 4 5 6 78

Shock

MIL STD 810C 516.2

Noise Immunity

NEMA ICS3–304 Impulse noise 1us, 1000V FCC class A RFI (144MHz, 430MHz, 10W, 10cm)

8-pin RJ45 Connector (8P8C)

12 34 56

6-pin RJ12 Connector

Serial Port Pin Descriptions 1 2 3 4 5 6

0V 5V RXD TXD RTS CTS

Power (–) connection (GND) Power (+) connection Receive Data (RS232C) Transmit Data (RS232C Request to Send Clear to Send

Page 54

Specifications

T1K–DEVNETS

Dimensions 48 (1.89) 8.1 (0.32)

9.2 (0.36)

Rev B

DeviceNet Communication Protocol (Slave) Predefined Master/Slave Group 2 Server only

Network Node Address

0 to 63 (Rotary switch setting)

Data Packet

0 to 8 Bytes (Data beyond eight bytes are divided.)

Communication Rate (Max. cable length)

125KB 250KB 500KB

Communication Status Indicators

MS: Module Status LED Green: normal device operation Red: unrecoverable controller fault

(1640 ft./ 500m) (820 ft./ 250m) (328 ft./ 100m)

DeviceNet Connector

NS: Network Status LED Green: communication link online and connected Green flashing: on–line, but not connected Red: critical link or controller failure Red flashing: connection time–out DeviceNet Power Consumption

45mA @11 to 25 VDC

Base Power Consumption

190mA @ 5VDC

T1K-DEVNETS

DIP Switch located under hinged cover on side of unit

RJ–12 Serial Port

1 PULL TO UNLOCK

Rotary Node 10.3 (0.41) Switches

DeviceNet Specification Device Type

Generic

Explicit Peer to Peer Message

No

I/O Peer to Peer Message

No

Configuration Consistency

No

Fault Node Recovery

No

Communication Baud Rate 125K, 250K, 500K

Yes

Master/Scanner

No

I/O Slave Message Bit Strobe Polling Cyclic Change of State

No Yes No No

80 (3.15)

Communication Form

83.3 (3.28)

Communications Specification mm (in.)

T1K–DEVNETS port pin–out

T1K–DEVNETS DIP Switch Settings *Note: Default setting assigns the node’s first Input and Output word to I/O Diagnostics.

V– (black) CAN Low (blue) Shield (bare) CAN High (white) V+ (red) Use Belden Cable 3084A, or equivalent.

General Specifications must mount to right of first power supply in a slave system

Operating Temperature

32° F to 131° F (0° C to 55° C)

Storage Temperature

–4° F to 158° F (–20° C to 70° C)

Ambient Humidity

5% – 95% relative humidity (non–condensing) 1500VAC, 1 minute (DeviceNet connector internal)

Insulation Resistance

500VDC, 10MΩ (DeviceNet connector internal)

Vibration Resistance

MIL STD 810C, Method 514.2

Shock Resistance

MIL STD 810C, Method 516.2

Noise Immunity

NEMA (ICS3–304) Impulse noise 1µs, 1000V FCC class A RFI (145MHz, 435MHz 10W, 10cm)

Atmosphere Weight

No corrosive gases Environmental Pollution Level 2 6.0 oz (170 g)

Pin 1 2 3 4 5 6

SW1

SW2

Port Baud Rate

125kbps

OFF

OFF

Baud Rate

SW6

OFF

9600 bps

OFF

19200 bps

ON

250kbps

Serial Port Pinout Signal 0V + 5V RXD TXD RTS CTS

RJ12 plug on cable

SW 6 Maintenance

Baud Rate

ON

500kbps

OFF

ON

Reserved

ON

ON

SW 8 RTS / CTS SW 4 Disable I/O Polling Diagnostics I/O Diagnostics

SW4

Enable

OFF

Disable

12 34 56

ON

*See Dip Switch 4 Note above.

SW 5 Hold Outputs

Enable / Disable

Outputs

SW5

RTS/CTS

SW8

Turn Off

OFF

Disable

OFF

Hold

ON

Enable

ON

3–27

Voltage Withstand

SW 1–2 DeviceNet Baud Rate

Serial Port 12 34 56

Installation Requirement

Page 55

Dimensions 48 (1.89) 8.1 (0.32)

9.2 (0.36)

Rev A

MODBUS RTU (Slave)

MODBUS Connector

15–pin female D–shell

MODBUS Port Type

RS–232C, RS422/485

Station Address

1 to F7h (247), Rotary switch setting

Number of I/O Points

Discrete: Inputs: 1024, Outputs: 1024; Analog: Inputs: 64 Channels, Outputs: 64 Channels

Communication Baud Rate

(300, 600, 1200, 2400, 4800, 9600, 19.2k, 38.4k) bps Dip Switch 1–3 Set

Communication Data

8–bit (fixed), 1 Start bit, 1 or 2 Stop bit Parity: None/Odd/Even; configure using Setup Tool Defaults: 8 (fixed), 1, 1, Odd

Communication Time out

500ms, 1s, 2.5s, 5s, 10s, 25s, 60s Default: 1s; configure using Setup Tool

RTS On / Off Delay Time

(0, 2, 5, 10, 50, 100, 500) ms Default: 0ms; configure using Setup Tool

Status Indicators

RWR (Green): ON when power good RX (Green): ON when data is being received TX (Green): ON when data is being transmitted RUN (Green): ON when communicating with Master ERR (Red): Communication error DIAG (Red): I/O system error

Output Enable Switch

Enable: outputs are enabled Disable: outputs are disabled

Installation Requirement must mount to right of first power supply in a slave system

Base Power Requirement

250mA @ 5VDC

Communications Port (RJ 12 Serial Port)

RJ12, RS232C Use to configure MODBUS port using MODBUS Setup Tool Utility or use to upgrade firmware Baud rate: 9600, 19.2k bps (set with Dip Switch 6) Fixed settings: 8 data bits, 1 start bit, 1 stop bit, parity Odd

General Specifications Installation Requirement must mount to right of first power supply in a slave system

Operating Temperature

32° F to 131° F (0° C to 55° C)

Storage Temperature

–4° F to 158° F (–20° C to 70° C)

Ambient Humidity

30% – 95% relative humidity (non–condensing)

MODBUS port

DIP Switch located under hinged cover on side of unit

T1K-MODBUS

Rotary Address Switches mm (in.)

MODBUS Port Pin–Out Pin 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

T1K–MODBUS DIP Switch Settings SW 1–3 MODBUS Port Baud Rate

Signal Definition 5V TXD RXD RTS CTS RXD– 0V 0V TXD+ TXD – RTS+ RTS – RXD + CTS + CTS –

5 VDC Transmit Data (RS–232C) Receive Data (RS–232C) Request to Send (RS–232C) Clear to Send (RS–232C) Receive Data – (RS–422) Logic Ground Logic Ground Transmit Data + (RS–422) Transmit Data – (RS–422) Request to Send + (RS–422) Request to Send – (RS–422) Receive Data + (RS–422) Clear to Send + (RS–422) Clear to Send – (RS–422)

SW2

SW3

Baud Rate

SW6

300 bps

OFF

OFF

OFF

9600 bps

OFF

600 bps

ON

OFF

OFF

19200 bps

ON

1200 bps

OFF

ON

OFF

SW 7 MODBUS RTU

2400 bps

ON

ON

OFF

Addressing Mode

4800 bps

OFF

OFF

ON

Mode

SW7

9600 bps

ON

OFF

ON

584/984

OFF

19200 bps

OFF

ON

ON

DirectLogic

ON

38400 bps

ON

ON

ON

SW 4 Communication Setting Mode

RTS/CTS

SW8

Option Mode (see T1K–MODBUS Manual)

ON

Disable

OFF

Enable

ON

SW 5 Hold Outputs Outputs

SW5

Turn Off

OFF

Insulation Resistance

500VDC, 10MΩ

Hold

ON

Vibration Resistance

MIL STD 810C, Method 514.2

Shock Resistance

MIL STD 810C, Method 516.2

Noise Immunity

NEMA (ICS3–304) Impulse noise 1µs, 1000V FCC class A RFI (145MHz, 435MHz)

Weight

6.0 oz (170 g)

MODBUS port

Default Mode

12 34 56

No corrosive gases Environmental Pollution Level 2

1234 5 6

Enable / Disable

OFF

1500VAC, 1 minute (15–pin connector internal)

RJ12 plug on cable

SW 8 RTS / CTS

Default Mode

Voltage Withstand

RJ12 port

Port Baud Rate

SW1

No corrosive gasses. The level for the environmental pollution = 2.

Serial Port Pin–out

SW 6 Maintenance

Baud Rate

Atmoshere (UL 840)

Atmosphere

. .

RJ 12 serial port

1 PULL TO UNLOCK

80 (3.15)

Communication Protocol

83.3 (3.28)

T1K– MODBUS Base Controller

3–28

Specifications

Baud Rate

Pin

Signal Definition

Communication Data

8 Bit

1 2

0V 5V

Start Bit

1 bit

Stop Bit

1 bit

3

RXD

Parity Bit

Odd

Address Mode

4

TXD

Communication Time Out

1s

5 6

RTS CTS

RTS/CTS

RTS ON Delay Time

0 ms

RTS OFF Delay Time

0 ms

Comm Setting Hold Outputs

Enable /Disable Maintenance Port Baud Rate

Page 56

Specifications

Dimensions 48 (1.89) 8.1 (0.32)

9.2 (0.36)

T1K–RSSS Remote I/O Base Controller SM–NET

RM–NET

Station Address

1 to 31 set by rotary switches

1 to 7 set by rotary switches

Number of Masters per PLC CPU

Check PLC CPU / remote Master module remote I/O specifications

Max. Slave I/O Points per PLC CPU Baud Rate / Communication Distance (set by DIP switches)

Baud rate 19.2kbps 38.4kbps 153.6kbps 307.2kbps 614.4kbps

Distance 1.2Km 1.2Km 600m 300m 100m

Baud rate 19.2kbps 38.4kbps

Distance 1.2Km 1.2Km

LED Indicators

RUN: On when communication is active. DIAG: On when a slave hardware failure error occurs. I/O: Fast Blink: I/O error (250ms on/off time) Slow Blink: I/O configuration error while outputs are enabled (500ms on/off time) Continuous ON: I/O and configuration error LINK: On when a communication error occurs.

Output Enable Switch

Enable: outputs are enabled Disable: outputs are disabled

Communications Port (active in SM–NET only)

RJ12, RS232C (K–Sequence) Dip switch selectable: Baud rate: 4800–38400bps *select 9600 baud for operator interface (default) (other baud rates are for updating T1K–RSSS) Parity: odd (default), even Fixed settings: 8 data bits, 1 start bit, 1 stop bit

Base Power Requirement

250mA @ 5VDC

Communication Cabling for remote I/O, RS–485 twisted pair Belden 9841 or equivalent

General Specifications Installation Requirements must mount to right of first power supply in a slave system

Operating Temperature

32° F to 131° F (0° C to 55° C)

Storage Temperature

–4° F to 158° F (–20° C to 70° C)

Relative Humidity

5 to 95% (non-condensing)

Environmental Air

No corrosive gases, pollution level = 2 (UL 840)

Vibration

MIL STD 810C 514.2

Shock

MIL STD 810C 516.2

Noise Immunity

NEMA ICS3–304 Impulse noise 1us, 1000V FCC class A RFI (144MHz, 430MHz, 10W, 10cm)

Remote I/O connector

-T -1 -2 -3

DIP Switch located under hinged cover on side of unit

T1K-RSSS

RJ–12 Serial Port

1 PULL TO UNLOCK

Rotary Address Switches

10.3 (0.41) mm (in.)

T1K–RSSS DIP Switch Settings 1

2, 3, 4

Mode

Baud Rate

OFF = SM–NET ON = RM–NET

Baud Rate 19.2k 38.4k 153.6k 307.2k 614.4k

5 switch position 2 3 4 0 0 0 X 0 0 0 X 0 X X 0 0 0 X

Output Default OFF = Clear ON = Hold

6

7, 8

Serial Port Parity

Serial Port Baud Rate

OFF = Odd ON = None

Baud Rate 4.8k 9.6k 19.2k 38.4k

SM–NET only switch position 7 8 X 0 0 0 0 X X X

X = ON, 0 = OFF Port Active in SM–NET only Use 9.6k, odd parity for Operator Interface

X = ON, 0 = OFF Baud rates above 38.4k for SM–NET only

T1K–RSSS Serial Port Pin–out RJ12 plug on cable

RJ12 socket on T1K–RSSS

12 34 56

Protocol

83.3 (3.28)

non–intelligent slave

80 (3.15)

Rev A

Module Type

Pin

Signal Definition

1 2

0V 5V

3

RS232C Data In

4

RS232C Data Out

5

5V

6

0V

3–29

12 3 4 56

Port Pinout

Page 57

Dimensions 48 (1.89) 8.1 (0.32)

9.2 (0.36)

T1H–PBC Profibus Base Controller 32 stations per segment, repeaters max./segment, 126 stations maximum

Communications

RS–485

Auto–configuring

GSD file in Master

Profibus Profile

DP (Decentralized Periphery)

Profibus Port

9–pin D–shell

Node Address

1 to 126 (decimal) set by rotary switches (0 used by Master)

Segment Distance

100 meters (327 feet) to 1200 meters (3270feet)

Baud Rate

Slectable from 9.6 kbps to 12 Mbps

LED Indicators

STATUS (Module): ON = module power–up check passed OFF = module power–up check failed ACTIVE (Link): ON = Network is active OFF = Network is not active TOKEN (Holding): ON = PBC is configured correctly and running OFF = Incorrect I/O configuration ERROR: ON = watchfog timer timeout represents hardware, communications, or network fault; power–on reset or reset within master device software

Communications Port

RJ12, RS232C (used for firmware upgrade only)

Base Power Requirement

530mA @ 5VDC (supplied by base power supply)

P R O F I B U S P O R T

Profibus Connector

MODULE STATUS LINK ACTIVE HOLDING TOKEN ERROR

Profibus Base Controller

80 (3.15)

Profibus Network Interface Module

Maximum Expansion

83.3 (3.28)

Module Type

3–30

Specifications x16 NODE ADDR x1

RJ–12 Serial Port

1 PULL TO UNLOCK

CONFIG. PORT

Rotary Node 10.3 (0.41) Switches mm (in.)

T1H–PBC port pin–out RxD/TxD–P

3

3

RxD/TxD–P

DGND

5

5

DGND

VP

6

6

VP

RxD/TxD–N

8

8

RxD/TxD–N

General Specifications must mount to right of first power supply

Operating Temperature

32° F to 131° F (0° C to 55° C)

Storage Temperature

–4° F to 158° F (–20° C to 70° C)

Relative Humidity

5% – 95% (non–condensing)

Environmental Air

No corrosive gases, pollution level = 2 (UL840)

Vibration

MIL STD 810C, Method 514.2

Shock

MIL STD 810C, Method 516.2

Noise Immunity

NEMA (ICS3–304) Impulse noise 1µs, 1000V FCC class A RFI (145MHz, 435MHz 10W, 10cm)

Manufacturer

Host Automation Products

Shield

Use Belden Profibus 3079A Cable or Siemens 6XV1 830 0AH10

Serial (Config) Port

RJ12 plug on cable

(Use for firmware upgrades only)

12 34 56

Installation Requirement

12 34 56

Serial Port Pin Descriptions 1 2 3 4 5 6

0V 5V RXD TXD RTS CTS

Power (–) connection (GND) Power (+) connection Receive Data (RS232C) Transmit Data (RS232C Request to Send Clear to Send

Page 58

Wiring & Dimensions 48 (1.89)

9.2 (0.36)

8 (sink/source)

Commons Per Module ext. power: 2, isolated (4 pts. / com) int. power: 2, all 8 pts. internally connected

Operating Voltage Range

12–24 VDC

Input Voltage Range

10.8 – 26.4 VDC min. / max.

Peak Voltage

30 VDC

Input Current (Typical)

4mA @ 12 VDC, 8.5mA @ 24 VDC

Input Impedance

2.8 K ohm

ON Voltage Level

> 10.0 VDC

OFF Voltage Level

< 2.0 VDC

Min. ON Current

4mA

Max. OFF Current

0.5mA

OFF to ON Response

2–8ms, Typ: 4ms

ON to OFF Response

2–8ms, Typ: 4ms

Base Power Required

35mA @ 5VDC

Status Indicators

Logic Side

Weight

70g

Environmental Specifications Ambient Operating Temperature

32_F to 131_F (0_C to 55_C)

Storage Temperature

–4_F to 158_F (–20_C to 70_C)

Ambient Humidity

5% to 95% (Non–condensing)

Atmosphere

No corrosive gases. The level of environmental pollution = 2 (UL 840)

Input points

Note: External Power, Sink Module Configuration Shown

T1K–08ND3 F

+

+ 12-24 VDC -

0

12-24 - VDC

MIL STD 810C, Method 516.2

Voltage Withstand

1500VAC, 1 minute

Insulation Resistance

500VDC, 10M ohm

Noise Immunity

NEMA ICS3–304 Impulse Noise 1us, 1000V FCC class A RFI (144MHz, 430MHz 10W, 10cm)

Agency Approvals

UL, CE, FCC class A

D

1

2

3

6

7

Side View

8.1 (0.32) mm (in.)

Jumper Selection

External Power

Equivalent Input Circuit Sink Module External Power

SOURCE

INT

V0 V1 Input

SINK

EXT

Internal Module Circuitry

+V

+V

To LED Sink + -

MODULE

Source Module External Power

SOURCE

INT

SINK

EXT

Optical Isolator

- + 12-24 VDC

Internal Power

MODULE

COM

Source

MODULE

SOURCE

INT

SOURCE

INT

SINK

EXT

SINK

EXT

V0

V0 8

Source Module Internal Power

6

5

V0 and V1 supply 24VDC or 0VDC if Internal Power Jumper is selected

Derating Chart

Points

4 4

2

83.3 (3.28)

3

Commons

MIL STD 810C, Method 514.2

Shock Resistance

E

B 6 C 5

1

0 1 2 3 4 5 6 7

MODULE

Vibration Resistance

A

25.7(1.01)

Inputs Per Module

80 (3.15)

T1K–08ND3 DC Input

8.1 (0.32)

54.3(2.14)

Specifications

V1 Input

Internal Module Circuitry

Sink Module Internal Power

V1 Input

Internal Module Circuitry

4

0 0 32

10 20 30 40 50 55 °C 50 68 86 104 122 131 ° F Ambient Temperature (°C/°F)

NPN Field COM Device

-

+ 24 VDC Internal

PNP COM Field Device

+

24 VDC Internal

3–31

2

Page 59

83.3 (3.28) 89 (3.5)

9.2 (0.36)

Commons Per Module ext. power : 4, isolated (4 pts. / com) int. power :4, all 16 pts. internally connected

Operating Voltage Range

12–24 VDC

Input Voltage Range

10.8 – 26.4 VDC min. / max.

Peak Voltage

30 VDC

Input Current (Typical)

4mA @ 12 VDC, 8.5mA @ 24 VDC

Input Impedance

2.8 K ohm

ON Voltage Level

> 10.0 VDC

OFF Voltage Level

< 2.0 VDC

Min. ON Current

4mA

Max. OFF Current

0.5mA

OFF to ON Response

2–8ms, Typ: 4ms

ON to OFF Response

2–8ms, Typ: 4ms

Base Power Required

70mA @ 5VDC

Status Indicators

Logic Side

Weight

120g

Environmental Specifications Ambient Operating Temperature

32_F to 131_F (0_C to 55_C)

Storage Temperature

–4_F to 158_F (–20_C to 70_C)

Ambient Humidity

5% to 95% (Non–condensing)

Atmosphere

No corrosive gases. The level of environmental pollution = 2 (UL 840)

Vibration Resistance

Note: External Power, Sink Module Configuration Shown

0 1 2 3 4 5 6 7 8 9 10 11 12 13 1415

+ -

+ -

COM 0

MIL STD 810C, Method 516.2

Voltage Withstand

1500VAC, 1 minute

Insulation Resistance

500VDC, 10M ohm

Noise Immunity

NEMA ICS3–304 Impulse Noise 1us, 1000V

COM 1

COM 2

V0

V2

V1

Agency Approvals

UL, CE, FCC class A

Points

+ -

V3

8.1 (0.32)

V0 – V3 supply 24VDC or 0VDC if Internal Power Jumper is selected mm (in.)

Jumper Selection MODULE

External Power

Equivalent Input Circuit

Sink Module External Power

SOURCE

INT

SINK

EXT

V0-V3 Input

Internal Module Circuitry

+V

+V

To LED MODULE

Source Module External Power

Sink

SOURCE

INT

SINK

EXT

+ COM

Optical Isolator

Source

- + 12-24 VDC

Internal Power

MODULE

MODULE

SOURCE

INT

SOURCE

INT

SINK

EXT

SINK

EXT

Derating Chart

V0-V3

V0-V3

16

Source Module Internal Power

12

+ -

12-24 VDC

FCC class A RFI (144MHz, 430MHz 10W, 10cm)

COM 3

Commons

12-24 VDC

MIL STD 810C, Method 514.2

Shock Resistance

Side View

Input points

54.3(2.14)

16 (sink/source)

Input

Internal Module Circuitry

Sink Module Internal Power

Input

Internal Module Circuitry

8 4 0 0 32

10 20 30 40 50 55 °C 50 68 86 104 122 131 °F Ambient Temperature (°C/°F)

80 (3.15)

Inputs Per Module

8.1 (0.32)

25.7(1.01)

T1K–16ND3 DC Input

3–32

Wiring & Dimensions

Specifications

NPN Field COM Device

-

+ 24 VDC Internal

PNP COM Field Device

+

24 VDC Internal

Page 60

Wiring & Dimensions

2, 4 pts. / com (isolated)

Operating Voltage Range

90–120VAC, 47–63Hz

Input Voltage Range

80–132VAC, 47–63Hz min. / max.

Input Current

8mA @ 100VAC (50Hz) 10mA @ 100VAC (60Hz) 12mA @ 132VAC (50Hz) 15mA @ 132VAC (60Hz)

Input Impedance

14K ohm @ 50Hz, 12K ohm @ 60Hz

ON Current/Voltage

> 6mA @ 75VAC

OFF Current/Voltage

< 2mA @ 20VAC

OFF to ON Response

< 40ms

ON to OFF Response

< 40ms

Base Power Required

35mA @ 5VDC

Status Indicators

Logic Side

Weight

70g

8.1 (0.32)

Input points T1K–08NA–1 F

A

E 0

0

90-120VAC

D

1

1

B C

2

2

5 3

3

1

6

2 3

4 4

5

6

7

4

5

6

7

90-120VAC

Commons

Environmental Specifications Ambient Operating Temperature

32_F to 131_F (0_C to 55_C)

Storage Temperature

–4_F to 158_F (–20_C to 70_C)

Ambient Humidity

5% to 95% (Non–condensing)

Atmosphere

No corrosive gases. The level of environmental pollution = 2 (UL 840)

V0, V1 not used with AC Input Modules

Vibration Resistance

MIL STD 810C, Method 514.2

Shock Resistance

MIL STD 810C, Method 516.2

Voltage Withstand

1500VAC, 1 minute

Insulation Resistance

500VDC, 10M ohm

Noise Immunity

NEMA ICS3–304

Agency Approvals

83.3 (3.28)

Derating Chart

Points 8 6 4 2

FCC class A

0

UL, CE, FCC class A

8.1 (0.32) mm (in.)

Impulse Noise 1us, 1000V

RFI (144MHz, 430MHz 10W, 10cm)

80 (3.15)

8

Commons Per Module

54.3(2.14)

Inputs Per Module

48 (1.89)

9.2 (0.36)

T1K–08NA–1 AC Input

25.7(1.01)

Specifications

0 32

10 20 30 40 50 55 °C 50 68 86 104 122 131 °F Ambient Temperature (°C/°F)

Side View

Equivalent Input Circuit Internal Module Circuitry

+V

+V

Input

90-120VAC COM

Optical Isolator

3–33

To LED