Page 61
3–34
Wiring & Dimensions
T1K–16NA–1 AC Input 4 , 4 pts. / common (isolated)
OperatingVoltage Range
90–120VAC, 47–63Hz
Input Voltage Range
80–132VAC, 47–63Hz min. / max.
Input Current
8mA @ 100VAC (50Hz) 10mA @ 100VAC (60Hz) 12mA @ 132VAC (50Hz) 15mA @ 132VAC (60Hz)
Input Impedance
14K ohm @ 50Hz, 12K ohm @ 60Hz
ON Current/Voltage
> 6mA @ 75VAC
OFF Current/Voltage
< 2mA @ 20VAC
OFF to ON Response
< 40ms
ON to OFF Response
< 40ms
Base Power Required
70mA @ 5 VDC
Status Indicators
Logic Side
Weight
120g
Environmental Specifications
8.1 (0.32)
Input points NA–1
0 1 2 3 4 5 6 7 8 9 10 11 1213 1415
COM 0
V0
V1
V2
V3
8.1 (0.32)
V0–V3 not used with AC Input Modules
–4_F to 158_F (–20_C to 70_C)
Ambient Humidity
5% to 95% (Non–condensing)
Atmosphere
No corrosive gases. The level of environmental pollution = 2 (UL 840)
Vibration Resistance
MIL STD 810C, Method 514.2
Shock Resistance
MIL STD 810C, Method 516.2
Voltage Withstand
1500VAC, 1 minute
8
Insulation Resistance
500VDC, 10M ohm
4
Noise Immunity
NEMA ICS3–304
Agency Approvals
COM 3
90-120VAC
Storage Temperature
RFI (144MHz, 430MHz 10W, 10cm)
COM 2
Commons
32_F to 131_F (0_C to 55_C)
FCC class A
COM 1
90-120VAC
Ambient Operating Temperature
Impulse Noise 1us, 1000V
89 (3.5)
9.2 (0.36)
54.3(2.14)
16
Commons Per Module
25.7(1.01)
Inputs Per Module
80 (3.15)
Specifications mm (in.) 83.3 (3.28) Points 16
Derating Chart
12
0 0 32
10 20 30 40 50 55 °C 50 68 86 104 122 131 °F Ambient Temperature (°C/°F)
Side View
UL, CE, FCC class A
Equivalent Input Circuit Internal Module Circuitry
+V
+V
Input
To LED
90-120VAC
COM
Optical Isolator
Page 62
Wiring & Dimensions 48 (1.89)
9.2 (0.36)
8 (sink)
Commons Per Module
2 internally connected
Operating Voltage Range
6–27 VDC
Output Voltage Range
5 –30 VDC min. / max.
Peak Voltage
T1K–08TD1
L
50 VDC
Max. Load Current
1A / pt., 4A / common
Max. Leakage Current
15uA @ 30VDC
ON Voltage Drop
0.3VDC @ 1.0A
Max. Inrush Current
2A for 100ms
OFF to ON Response
< 10us
ON to OFF Response
< 60us
Base Power Required
100mA @ 5VDC
External Power Required
200mA max. @ 20–28VDC
Status Indicators
Logic Side
Error Status Indications (LEDS)
24V ON = low external power FU1/FU2 ON = fuse 1 or fuse 2 blown
Fuses (User Replaceable) T1K–FUSE–1
2, (6.3A, 250V / common), (4pts. / fuse) NQ3–6.3 SOC corp.
Weight
85g
8.1 (0.32)
Output Points
L
L
L
L
L
L
L
24V FU1
Fuses located under top cover
+ 12-24 VDC -
F
A
FU2
0
E
D
1
2
B 6 1 C 5 3
4 4
2 3 5
6
7
80 (3.15)
Outputs Per Module
0 1 2 3 4 5 6 7 25.7(1.01)
T1K–08TD1 DC Output
Rev A
54.3(2.14)
Specifications
Commons 24VDC + 8.1 (0.32)
V0–V1 internally connected mm (in.) 83.3 (3.28)
T1K–08TD1 Derating Chart
Points
Environmental Specifications
8
0.5A
Ambient Operating Temperature
32_F to 131_F (0_C to 55_C)
6
0.75A
Storage Temperature
–4_F to 158_F (–20_C to 70_C)
4
1.0A
Ambient Humidity
5% to 95% (Non–condensing)
2
Atmosphere
No corrosive gases. The level of environmental pollution = 2 (UL 840)
0
Vibration Resistance
MIL STD 810C, Method 514.2
Shock Resistance
MIL STD 810C, Method 516.2
Voltage Withstand
1500VAC, 1 minute
Insulation Resistance
500VDC, 10M ohm
Noise Immunity
NEMA ICS3–304
0 32
10 20 30 40 50 55 °C 50 68 86 104 122 131 ° F Ambient Temperature (°C/°F)
Equivalent Output Circuit 24VDC
Impulse Noise 1us, 1000V FCC class A
-
RFI (144MHz, 430MHz 10W, 10cm) Agency Approvals
Side View
UL, CE, FCC class A
Sink Module External Power
-
+
+
Internal Module Circuitry
V0 V1
Output
Optical Isolator
L
To LED
12-24VDC 6.3A Other Circuits
3–35
COM
Page 63
Wiring & Dimensions 48 (1.89)
9.2 (0.36)
Commons Per Module
2 internally connected
Operating Voltage Range
12–24 VDC
Output Voltage Range
10.8–26.4 VDC min. / max.
Peak Voltage
T1K–08TD2–1
L
50 VDC
Max. Load Current
1A / pt., 4A / common
Max. Leakage Current
15uA @ 26.4VDC
ON Voltage Drop
1.2VDC @ 1.0A
Max. Inrush Current
2A for 100ms
OFF to ON Response
< 10us
ON to OFF Response
< 0.5ms
Base Power Required
100mA @ 5VDC
Status Indicators
Logic Side
Error Status Indications (LEDS)
FU1/FU2 ON = fuse 1 or fuse 2 blown
Fuses (User Replaceable) T1K–FUSE–1
2, (6.3A, 250V / common), (4pts. / fuse) NQ3–6.3 SOC corp.
Weight
100g
8.1 (0.32)
Output Points
L
L
L
L
L
L
L
FU1
Fuses located under top cover
12-24 VDC +
+
F
0
12-24 VDC
E
D
1
2
Storage Temperature
–4_F to 158_F (–20_C to 70_C)
Ambient Humidity
5% to 95% (Non–condensing)
0V
No corrosive gases. The level of environmental pollution = 2 (UL 840)
Vibration Resistance
MIL STD 810C, Method 514.2
Shock Resistance
MIL STD 810C, Method 516.2
Voltage Withstand
1500VAC, 1 minute
Insulation Resistance
500VDC, 10M ohm
Noise Immunity
NEMA ICS3–304
3
4 4
2 3 5
6
7
0V 8.1 (0.32) mm (in.)
Note: Apply the 0V label that comes with the I/O module to I/O base terminal points V0–V1 to properly identify the 0VDC terminal points. 83.3 (3.28) Derating Chart
Points
Atmosphere
C 5
0 1 2 3 4 5 6 7
Environmental Specifications 32_F to 131_F (0_C to 55_C)
B 6 1
Commons
V0–V1 internally connected
Ambient Operating Temperature
A
FU2
8
0.75A
6
1.0A
4 2 0 0 32
10 20 30 40 50 55 °C 50 68 86 104 122 131 ° F Ambient Temperature (°C/°F)
Impulse Noise 1us, 1000V
Equivalent Output Circuit
FCC class A
Internal Module Circuitry
RFI (144MHz, 430MHz 10W, 10cm) Agency Approvals
Side View
UL, CE, FCC class A
Output
Source Module External Power
0V (V0-V1)
Optical Isolator
L To LED -
+
COM 12-24VDC
6.3A Other Circuits
80 (3.15)
8 (sourcing)
54.3(2.14)
Outputs Per Module
25.7(1.01)
T1K–08TD2–1 DC Output
Rev A
3–36
Specifications
Page 64
Specifications
Wiring & Dimensions
T1H–08TDS Isolated DC Output
Note: Apply the labels that come with the I/O module to the I/O base to properly identify the terminal points.
8 (isolated)
Operating Voltage Range
5 to 36VDC
Max. Voltage
36VDC
Output Clamp Voltage
40VDC
Max. Load Current
2A per point, 16A per module, 32 to140_F (0 to 60_C)
Electronic Over Current Protection
Output trips at 6A min., 12A max.
Max.Load Voltage
36VDC
Max. Leakage Current
75µA
Max. ON State Voltage Drop
0.3V at 2A, 0.15V at 1A
Inrush Current
5A for 20ms
OFF to ON Response
< 3µs
ON to OFF Response
<100µs
Base Power Required
200mA max.
Thermal Shutdown
Between Tjunction = 302_F to 374_F (150_C to 190_C)
Overtemperature Reset
Thermal shutdown temp.minus 5_F (15_C)
Status Indications
Logic Side
Weight
93.6g
Output Points 0 0
1
1
2
L
L -
-
+
+
2 3
3
4
Sourcing Examples
4
5
5
6 6
5–36VDC - + + L
T1H–08TDS
7 7
L
54.3(2.14) 80 (3.15)
8 (isolated, sink/source)
Commons
8.1 (0.32)
Sinking Examples
5–36VDC 25.7(1.01)
Outputs Per Module
89 (3.5)
9.2 (0.36)
Commons C0 C0 C1 C1 C2 C2 C3 C3 C4 C4 C5 C5 C6 C6 C7 C7
8.1 (0.32) –––– USER BUS 1 ––––
83.3 (3.28)
–––– USER BUS 2 –––– mm (in.)
No connection: Eight User Bus 1 terminals bussed together for distribution; same for eight User Bus 2 terminals.
Environmental Specifications Ambient Operating Temperature
32_F to 140_F (0_C to 60_C)
Storage Temperature
–4_F to 158_F (–20_C to 70_C)
Ambient Humidity
5% to 95% (Non–condensing)
Atmosphere
No corrosive gases. The level of environmental pollution = 2 (UL 840)
Vibration Resistance
MIL STD 810C, Method 514.2
Shock Resistance
MIL STD 810C, Method 516.2
Voltage Withstand
1500VAC, 1 minute
Insulation Resistance
500VDC, 10M ohm
Noise Immunity
NEMA ICS3–304 Impulse Noise 1us, 1000V FCC class A RFI (144MHz, 430MHz 10W, 10cm)
Agency Approvals
Equivalent Output Circuit Side View
Sourcing (High Side Switching)
Sinking (Low Side Switching)
Internal Module Circuitry COM +
-
5-36VDC
L
Out
Internal Module Circuitry
Isolated DC P/S
L +
-
Opto Isolator
To LED
COM
5-36VDC
Out
Isolated DC P/S
Opto Isolator
To LED
UL, CE, FCC class A
3–37
Page 65
3–38
Wiring & Dimensions 89 (3.5)
9.2 (0.36)
16 (sink)
Commons Per Module
4 internally connected
Operating Voltage Range
6–27 VDC
Output Voltage Range
5–30 VDC min. /max.
Peak Voltage
50 VDC
Max. Load Current
1A / pt., 4A / common
Max. Leakage Current
15uA @ 30VDC
ON Voltage Drop
0.3VDC @ 1.0A
Max. Inrush Current
2A for 100ms
OFF to ON Response
< 10us
ON to OFF Response
< 60us
Base Power Required
200mA @ 5VDC
External Power Required
400mA max. @ 20–28VDC
Status Indicators
Logic Side
Error Status Indications (LEDS)
24V ON = low external power FU1/FU2 ON = fuse 1 or 2 blown FU3/FU4 ON = fuse 3 or 4 blown
Fuses (User Replaceable) T1K–FUSE–1
4, (6.3A, 250V / common), (4 pts. / fuse) NQ3–6.3 SOC corp.
Weight
140g
Output Points TD1
0 1 2 3 4 5 6 7 8 9 1011 1213 14 15
12-24 VDC + -
L
L L L L L L L
COM 0
24V FU1
FU3
FU2
FU4
L L L L L L L L
COM 2
COM 3
Commons
+ 24VDC
COM 1
Fuses located under top cover
54.3(2.14)
Outputs Per Module
8.1 (0.32)
25.7(1.01)
T1K–16TD1 DC Output
Rev A
V0
V1
V2
V3
8.1 (0.32)
V0 – V3 internally connected mm (in.) 83.3 (3.28) T1K–16TD1
Environmental Specifications
Points
Derating Chart 0.4A 0.5A
16 Ambient Operating Temperature
32_F to 131_F (0_C to 55_C)
Storage Temperature
–4_F to 158_F (–20_C to 70_C)
Ambient Humidity
5% to 95% (Non–condensing)
Atmosphere
No corrosive gases. The level of environmental pollution = 2 (UL 840)
Vibration Resistance
MIL STD 810C, Method 514.2
Shock Resistance
MIL STD 810C, Method 516.2
Voltage Withstand
1500VAC, 1 minute
Insulation Resistance
500VDC, 10M ohm
Noise Immunity
NEMA ICS3–304
12 8
0.75A
4
1.0A
0 0 32
10 20 30 40 50 55 °C 50 68 86 104 122 131 ° F Ambient Temperature (°C/°F)
Side View
Equivalent Output Circuit
Impulse Noise 1us, 1000V
24VDC
FCC class A RFI (144MHz, 430MHz 10W, 10cm) Agency Approvals
80 (3.15)
Specifications
-
UL, CE, FCC class A
Sink Module External Power
-
+
+
Internal Module Circuitry V0-V3
Output
Optical Isolator
L To LED
12-24VDC 6.3A COM
Other Circuits
Page 66
Wiring & Dimensions 89 (3.5)
9.2 (0.36)
16 (source)
Commons Per Module
4 internally connected
Operating Voltage Range
12–24 VDC
Output Voltage Range
10.8–26.4 VDC
Rev A
Output Points TD2–1 Fuses located under top cover
0 1 2 3 4 5 6 7 8 9 1011 1213 1415
Peak Voltage
50 VDC
Max. Load Current
1A / pt., 4A/common (subject to derating)
Max. Leakage Current
15uA @ 26.4 VDC
ON Voltage Drop
1.2 VDC @ 1.0A
Max. Inrush Current
2A for 100ms
-
-
OFF to ON Response
< 10us
+
+
ON to OFF Response
< 0.5ms
Base Power Required
200mA @ 5VDC
Status Indicators
Logic Side
Error Status Indications (LEDS)
FU1/FU2 ON = fuse 1 or 2 blown FU3/FU4 ON = fuse 3 or 4 blown
Fuses (User Replaceable) T1K–FUSE–1
4, (6.3A, 250V / common), (4 pts. / fuse) NQ3–6.3 SOC corp.
Weight
140g
FU1
FU3
FU2
FU4
54.3(2.14)
Outputs Per Module
12-24 VDC L L L L L L L L L L L L L L L L 12-24 VDC
COM 0
COM 1
COM 2
COM 3
-
-
+
+
25.7(1.01)
T1K–16TD2–1 DC Output
8.1 (0.32)
Commons
0V
0V
0V
0V
80 (3.15)
Specifications
8.1 (0.32)
V0 – V3 internally connected mm (in.)
Note: Apply the 0V label that comes with the I/O module to I/O base terminal points V0–V3 to properly identify the 0VDC terminal points.
83.3 (3.28)
Environmental Specifications Ambient Operating Temperature
32_F to 131_F (0_C to 55_C)
Storage Temperature
–4_F to 158_F (–20_C to 70_C)
Ambient Humidity
5% to 95% (Non–condensing)
Atmosphere
No corrosive gases. The level of environmental pollution = 2 (UL 840)
12
Vibration Resistance
MIL STD 810C, Method 514.2
8
Shock Resistance
MIL STD 810C, Method 516.2
4
Voltage Withstand
1500VAC, 1 minute
Insulation Resistance
500VDC, 10M ohm
Noise Immunity
NEMA ICS3–304
Derating Chart Points 16
0.5A 0.75A 1.0A
0 0 32
10 20 30 40 50 55 °C 50 68 86 104 122 131 °F Ambient Temperature (°C/°F)
Side View
Impulse Noise 1us, 1000V FCC class A
Equivalent Output Circuit
RFI (144MHz, 430MHz 10W, 10cm) Agency Approvals
UL, CE, FCC class A
Internal Module Circuitry Output
Source Module External Power
0V (V0-V3)
Optical Isolator
L To LED +
COM 12-24VDC
6.3A Other Circuits
3–39
-
Page 67
Wiring & Dimensions 48 (1.89)
9.2 (0.36)
Commons Per Module
2, 4 pts. / common (isolated)
Operating Voltage Range
17–240 VAC (47–63Hz)
Output Voltage Range
15–264 VAC (47–63Hz) min. /max.
Max. Load Current
1A / pt., 4A /common(subject to derating)
ON Voltage Drop
1.5VAC @ > 50mA, 4.0VAC @ < 50mA
Max. Leakage Current
4mA @ 264 VAC
Max. Inrush Current
10A for 10ms
Min. Load
10mA
OFF to ON Response
< 1ms
ON to OFF Response
< 1ms + 1/2 cycle
Base Power Required
250mA @ 5VDC
Status Indicators
Logic Side
Error Status Indications (LEDS)
FU1 ON = fuse 1 blown FU2 ON = fuse 2 blown
Fuses (User Replaceable) T1K–FUSE–2
2, (10A, 250V / common), (4 pts. / fuse) 5 x 20 mm type
Weight
140g
Output Points
T1K–08TA L
L
L
L
L
L
L
L
FU1 FU2
Fuses located under top cover
F
0
17-240VAC
17-240VAC
V0–V1 not used with AC Output Modules
Date Code: 008* Derating Chart
Date Code: 00Z* and later Derating Chart
Points
0.5A
Ambient Operating Temperature
32_F to 131_F (0_C to 55_C)
6
0.75A
6
0.75A
Storage Temperature
–4_F to 158_F (–20_C to 70_C)
4
1.0A
4
1.0A
Ambient Humidity
5% to 95% (Non–condensing)
2
Atmosphere
No corrosive gases. The level of environmental pollution = 2 (UL 840)
0
1500VAC, 1 minute
Insulation Resistance
500VDC, 10M ohm
Noise Immunity
NEMA ICS3–304
4 4
5
6
7
83.3 (3.28)
8
MIL STD 810C, Method 516.2
3 mm (in.)
0.5A
Voltage Withstand
2
2 3
8.1 (0.32)
8
Shock Resistance
D
1
C 5
0 1 2 3 4 5 6 7
Environmental Specifications
MIL STD 810C, Method 514.2
E
B 6 1
Commons
Points
Vibration Resistance
A
2 0 0 32
10 20 30 40 50 55 °C 50 68 86 104 122 131 ° F Ambient Temperature (°C/°F)
0 32
10 20 30 40 50 55 °C 50 68 86 104 122 131 ° F Ambient Temperature (°C/°F)
Side View
Equivalent Output Circuit
Impulse Noise 1us, 1000V
Internal Module Circuitry
FCC class A RFI (144MHz, 430MHz 10W, 10cm) Agency Approvals
80 (3.15)
8
54.3(2.14)
Rev B
Outputs Per Module
8.1 (0.32)
25.7(1.01)
T1K–08TA AC Output
3–40
Specifications
UL, CE, FCC class A
+V
Output
L
To LED 10A
17-240VAC
COM
Optical Isolator
Page 68
Wiring & Dimensions
Specifications
89 (3.5)
9.2 (0.36)
16
Commons Per Module
4, 4 pts. / common (isolated)
Operating Voltage Range
17–240 VAC (47–63Hz)
Output Voltage Range
15–264 VAC (47–63Hz) min. /max.
Max. Load Current
1A / pt., 4A/common (subject to derating)
ON Voltage Drop
1.5VAC @ > 50mA, 4.0VAC @ < 50mA
Max. Leakage Current
4mA @ 264 VAC
Max. Inrush Current
10A for 10ms
Min. Load
10mA
OFF to ON Response
< 1ms
ON to OFF Response
< 1ms + 1/2 cycle
Base Power Required
450mA @ 5VDC
Status Indicators
Logic Side
Error Status Indications (LEDS)
FU1/FU2 ON = fuse 1 or 2 blown FU3/FU4 ON = fuse 3 or 4 blown
Fuses (User Replaceable) T1K–FUSE–2
4, (10A, 250V / common), (4 pts. / fuse) 5 x 20 mm type
Weight
190g
Output Points TA
0 1 2 3 4 5 6 7 8 9 1011 1213 1415 L
L L L L L L L
COM 0
Fuses located under top cover
FU1
FU3
FU2
FU4
54.3(2.14) 80 (3.15)
Outputs Per Module
8.1 (0.32)
L L L L L L L L
COM 1
COM 2
COM 3
17-240VAC
25.7(1.01)
T1K–16TA AC Output
Rev B
Commons
17-240VAC V0
V2
V1
V3
8.1 (0.32)
V0 – V3 not used with AC Output Modules mm (in.) 83.3 (3.28)
Date Code: 012* and Later Derating Chart
Environmental Specifications Points 16
Ambient Operating Temperature
32_F to 131_F (0_C to 55_C)
Storage Temperature
–4_F to 158_F (–20_C to 70_C)
Ambient Humidity
5% to 95% (Non–condensing)
8
Atmosphere
No corrosive gases. The level of environmental pollution = 2 (UL 840)
4
Vibration Resistance
MIL STD 810C, Method 514.2
0
Shock Resistance
MIL STD 810C, Method 516.2
Voltage Withstand
1500VAC, 1 minute
Insulation Resistance
500VDC, 10M ohm
Noise Immunity
NEMA ICS3–304
0.5A 0.75A
12
1.0A
0 32
10 20 30 40 50 55 °C 50 68 86 104 122 131 ° F Ambient Temperature (°C/°F)
Side View
Equivalent Output Circuit
Impulse Noise 1us, 1000V FCC class A
Internal Module Circuitry
RFI (144MHz, 430MHz 10W, 10cm) Agency Approvals
UL, CE, FCC class A
+V
Output
L
To LED 10A
Optical Isolator
3–41
17-240VAC
COM
Page 69
Wiring & Dimensions
T1K–08TAS AC Output
Note: Apply the labels that come with the I/O module to the I/O base to properly identify the terminal points.
8 , 1 pt. / common (isolated)
Operating Voltage Range
17–240 VAC (47–63Hz)
Output Voltage Range
15–264 VAC (47–63Hz) min. /max.
Max. Load Current
2A / pt. (subject to derating)
ON Voltage Drop
1.5VAC @ > 50mA, 4.0VAC @ < 50mA
Max. Leakage Current
4mA @ 264 VAC
Max. Inrush Current
10A for 10ms
Min. Load
10mA
OFF to ON Response
< 1ms
ON to OFF Response
< 1ms + 1/2 cycle
Base Power Required
300mA @ 5VDC
Status Indicators
Logic Side
Error Status Indications (LEDS)
FU1/FU2 ON = fuse 1 or 2 blown FU3/FU4 ON = fuse 3 or 4 blown FU5/FU6 ON = fuse 5 or 6 blown FU7/FU8 ON = fuse 7 or 8 blown
Fuses (User Replaceable) T1K–FUSE–3
8, (10A, 250V / common), (1 pt. / fuse) NQ3–10 SOC Corp.
Weight
190g
Environmental Specifications
Output Points 0
C0
1
C1
32_F to 131_F (0_C to 55_C)
Storage Temperature
–4_F to 158_F (–20_C to 70_C)
Ambient Humidity
5% to 95% (Non–condensing)
Atmosphere
No corrosive gases. The level of environmental pollution = 2 (UL 840)
Vibration Resistance
MIL STD 810C, Method 514.2
Shock Resistance
MIL STD 810C, Method 516.2
Voltage Withstand
1500VAC, 1 minute
Insulation Resistance
500VDC, 10M ohm
Noise Immunity
NEMA ICS3–304
3
C2
C3
4
5
6
7
L
L
L
L
C4
C5
C6
C7
Fuses located under top cover
FU1
FU3
FU5
FU7
FU2
FU4
FU6
FU8
Commons
Note: See other side for wiring example.
17-240VAC V0
V2
V1
V3
8.1 (0.32)
V0 – V3 not used with AC Output Modules mm (in.) Date Code: 008* Points 8
Derating Chart Points 8
1.0A 1.5A
2.0A
4
2
1.0A 1.5A
6
2.0A
4
83.3 (3.28)
Date Code: 012* and later
Derating Chart
6 Ambient Operating Temperature
2
54.3(2.14)
Commons Per Module
8.1 (0.32)
2
0
0 0 32
10 20 30 40 50 55 °C 50 68 86 104 122 131 °F Ambient Temperature (°C/°F)
0 32
10 20 30 40 50 55 °C 50 68 86 104 122 131 ° F Ambient Temperature (°C/°F)
Side View
Equivalent Output Circuit Internal Module Circuitry
Impulse Noise 1us, 1000V FCC class A RFI (144MHz, 430MHz 10W, 10cm) Agency Approvals
80 (3.15)
8
89 (3.5)
9.2 (0.36)
25.7(1.01)
Rev A
Outputs Per Module
3–42
Specifications
+V
Output
UL, CE, FCC class A
L
To LED 10A
17-240VAC
COM
Optical Isolator
Page 70
Wiring & Dimensions 48 (1.89)
9.2 (0.36)
Output Type
Relay Form A (SPST) normally open
Commons Per Module
2 , 4 pts. / common (isolated)
Operating Voltage Range
6–240 VAC (47–63Hz), 6–27 VDC
Output Voltage Range
T1K–08TR L
5–264 VAC (47–63Hz) min. /max. 5–30 VDC min. /max.
Max. Load Current
2A / pt., 8A / common
Max. Leakage Current
0.1mA @ 264 VAC
Max. Inrush Current
6A for 10ms / pt.; 20A for 10ms / com
Min. Load
5mA @ 5VDC
OFF to ON Response
< 15ms
ON to OFF Response
< 10ms
Base Power Required
350mA @ 5VDC
Status Indicators
Logic Side
Error Status Indications (LEDS)
FU1 ON = fuse 1 blown FU2 ON = fuse 2 blown
Fuses (User Replaceable) T1K–FUSE–2
2, (10A, 250V / common), (4 pts. / fuse) 5 x 20 mm type
Weight
110g
L
L
L
L
L
L
L
FU1 FU2
Fuses located under top cover
F
0
6-27VDC 6-240VAC
6-27VDC 6-240VAC
A
E
D
1
2
B 6 1 C 5 3
4 4
2
80 (3.15)
8
8.1 (0.32)
Output Points
Rev A
Outputs Per Module
3 5
6
7
0 1 2 3 4 5 6 7 25.7(1.01)
T1K–08TR Relay Output
54.3(2.14)
Specifications
Commons
8.1 (0.32)
V0, V1 not used with Relay Output Modules mm (in.) 83.3 (3.28)
Equivalent Output Circuit Environmental Specifications Ambient Operating Temperature
32_F to 131_F (0_C to 55_C)
Storage Temperature
–4_F to 158_F (–20_C to 70_C)
Ambient Humidity
5% to 95% (Non–condensing)
Atmosphere
No corrosive gases. The level of environmental pollution = 2 (UL 840)
Vibration Resistance
MIL STD 810C, Method 514.2
Shock Resistance
MIL STD 810C, Method 516.2
Voltage Withstand
1500VAC, 1 minute
Insulation Resistance
500VDC, 10M ohm
Noise Immunity
NEMA ICS3–304
Internal Module Circuitry +V
Output
L To LED 10A
AC or DC Supply
Side View
COM 6-27VDC 6-240VAC
Impulse Noise 1us, 1000V FCC class A
Agency Approvals
Typical Relay Life (Operations) at Room Temperature
UL, CE, FCC class A
Voltage & Type of Load
1A
2A
24 VDC Resistive
500K
250K
24 VDC Solenoid
100K
50K
110 VAC Resistive
500K
250K
110 VAC Solenoid
200K
100K
220 VAC Resistive
350K
200K
220 VAC Solenoid
100K
50K
Load Current
Derating Chart
Points 8
1.5A
6
2.0A
4 2 0 0 32
10 20 30 40 50 55 °C 50 68 86 104 122 131 °F Ambient Temperature (°C/°F)
3–43
RFI (144MHz, 430MHz 10W, 10cm)