Page 61

3–34

Wiring & Dimensions

T1K–16NA–1 AC Input 4 , 4 pts. / common (isolated)

OperatingVoltage Range

90–120VAC, 47–63Hz

Input Voltage Range

80–132VAC, 47–63Hz min. / max.

Input Current

8mA @ 100VAC (50Hz) 10mA @ 100VAC (60Hz) 12mA @ 132VAC (50Hz) 15mA @ 132VAC (60Hz)

Input Impedance

14K ohm @ 50Hz, 12K ohm @ 60Hz

ON Current/Voltage

> 6mA @ 75VAC

OFF Current/Voltage

< 2mA @ 20VAC

OFF to ON Response

< 40ms

ON to OFF Response

< 40ms

Base Power Required

70mA @ 5 VDC

Status Indicators

Logic Side

Weight

120g

Environmental Specifications

8.1 (0.32)

Input points NA–1

0 1 2 3 4 5 6 7 8 9 10 11 1213 1415

COM 0

V0

V1

V2

V3

8.1 (0.32)

V0–V3 not used with AC Input Modules

–4_F to 158_F (–20_C to 70_C)

Ambient Humidity

5% to 95% (Non–condensing)

Atmosphere

No corrosive gases. The level of environmental pollution = 2 (UL 840)

Vibration Resistance

MIL STD 810C, Method 514.2

Shock Resistance

MIL STD 810C, Method 516.2

Voltage Withstand

1500VAC, 1 minute

8

Insulation Resistance

500VDC, 10M ohm

4

Noise Immunity

NEMA ICS3–304

Agency Approvals

COM 3

90-120VAC

Storage Temperature

RFI (144MHz, 430MHz 10W, 10cm)

COM 2

Commons

32_F to 131_F (0_C to 55_C)

FCC class A

COM 1

90-120VAC

Ambient Operating Temperature

Impulse Noise 1us, 1000V

89 (3.5)

9.2 (0.36)

54.3(2.14)

16

Commons Per Module

25.7(1.01)

Inputs Per Module

80 (3.15)

Specifications mm (in.) 83.3 (3.28) Points 16

Derating Chart

12

0 0 32

10 20 30 40 50 55 °C 50 68 86 104 122 131 °F Ambient Temperature (°C/°F)

Side View

UL, CE, FCC class A

Equivalent Input Circuit Internal Module Circuitry

+V

+V

Input

To LED

90-120VAC

COM

Optical Isolator

Page 62

Wiring & Dimensions 48 (1.89)

9.2 (0.36)

8 (sink)

Commons Per Module

2 internally connected

Operating Voltage Range

6–27 VDC

Output Voltage Range

5 –30 VDC min. / max.

Peak Voltage

T1K–08TD1

L

50 VDC

Max. Load Current

1A / pt., 4A / common

Max. Leakage Current

15uA @ 30VDC

ON Voltage Drop

0.3VDC @ 1.0A

Max. Inrush Current

2A for 100ms

OFF to ON Response

< 10us

ON to OFF Response

< 60us

Base Power Required

100mA @ 5VDC

External Power Required

200mA max. @ 20–28VDC

Status Indicators

Logic Side

Error Status Indications (LEDS)

24V ON = low external power FU1/FU2 ON = fuse 1 or fuse 2 blown

Fuses (User Replaceable) T1K–FUSE–1

2, (6.3A, 250V / common), (4pts. / fuse) NQ3–6.3 SOC corp.

Weight

85g

8.1 (0.32)

Output Points

L

L

L

L

L

L

L

24V FU1

Fuses located under top cover

+ 12-24 VDC -

F

A

FU2

0

E

D

1

2

B 6 1 C 5 3

4 4

2 3 5

6

7

80 (3.15)

Outputs Per Module

0 1 2 3 4 5 6 7 25.7(1.01)

T1K–08TD1 DC Output

Rev A

54.3(2.14)

Specifications

Commons 24VDC + 8.1 (0.32)

V0–V1 internally connected mm (in.) 83.3 (3.28)

T1K–08TD1 Derating Chart

Points

Environmental Specifications

8

0.5A

Ambient Operating Temperature

32_F to 131_F (0_C to 55_C)

6

0.75A

Storage Temperature

–4_F to 158_F (–20_C to 70_C)

4

1.0A

Ambient Humidity

5% to 95% (Non–condensing)

2

Atmosphere

No corrosive gases. The level of environmental pollution = 2 (UL 840)

0

Vibration Resistance

MIL STD 810C, Method 514.2

Shock Resistance

MIL STD 810C, Method 516.2

Voltage Withstand

1500VAC, 1 minute

Insulation Resistance

500VDC, 10M ohm

Noise Immunity

NEMA ICS3–304

0 32

10 20 30 40 50 55 °C 50 68 86 104 122 131 ° F Ambient Temperature (°C/°F)

Equivalent Output Circuit 24VDC

Impulse Noise 1us, 1000V FCC class A

-

RFI (144MHz, 430MHz 10W, 10cm) Agency Approvals

Side View

UL, CE, FCC class A

Sink Module External Power

-

+

+

Internal Module Circuitry

V0 V1

Output

Optical Isolator

L

To LED

12-24VDC 6.3A Other Circuits

3–35

COM

Page 63

Wiring & Dimensions 48 (1.89)

9.2 (0.36)

Commons Per Module

2 internally connected

Operating Voltage Range

12–24 VDC

Output Voltage Range

10.8–26.4 VDC min. / max.

Peak Voltage

T1K–08TD2–1

L

50 VDC

Max. Load Current

1A / pt., 4A / common

Max. Leakage Current

15uA @ 26.4VDC

ON Voltage Drop

1.2VDC @ 1.0A

Max. Inrush Current

2A for 100ms

OFF to ON Response

< 10us

ON to OFF Response

< 0.5ms

Base Power Required

100mA @ 5VDC

Status Indicators

Logic Side

Error Status Indications (LEDS)

FU1/FU2 ON = fuse 1 or fuse 2 blown

Fuses (User Replaceable) T1K–FUSE–1

2, (6.3A, 250V / common), (4pts. / fuse) NQ3–6.3 SOC corp.

Weight

100g

8.1 (0.32)

Output Points

L

L

L

L

L

L

L

FU1

Fuses located under top cover

12-24 VDC +

+

F

0

12-24 VDC

E

D

1

2

Storage Temperature

–4_F to 158_F (–20_C to 70_C)

Ambient Humidity

5% to 95% (Non–condensing)

0V

No corrosive gases. The level of environmental pollution = 2 (UL 840)

Vibration Resistance

MIL STD 810C, Method 514.2

Shock Resistance

MIL STD 810C, Method 516.2

Voltage Withstand

1500VAC, 1 minute

Insulation Resistance

500VDC, 10M ohm

Noise Immunity

NEMA ICS3–304

3

4 4

2 3 5

6

7

0V 8.1 (0.32) mm (in.)

Note: Apply the 0V label that comes with the I/O module to I/O base terminal points V0–V1 to properly identify the 0VDC terminal points. 83.3 (3.28) Derating Chart

Points

Atmosphere

C 5

0 1 2 3 4 5 6 7

Environmental Specifications 32_F to 131_F (0_C to 55_C)

B 6 1

Commons

V0–V1 internally connected

Ambient Operating Temperature

A

FU2

8

0.75A

6

1.0A

4 2 0 0 32

10 20 30 40 50 55 °C 50 68 86 104 122 131 ° F Ambient Temperature (°C/°F)

Impulse Noise 1us, 1000V

Equivalent Output Circuit

FCC class A

Internal Module Circuitry

RFI (144MHz, 430MHz 10W, 10cm) Agency Approvals

Side View

UL, CE, FCC class A

Output

Source Module External Power

0V (V0-V1)

Optical Isolator

L To LED -

+

COM 12-24VDC

6.3A Other Circuits

80 (3.15)

8 (sourcing)

54.3(2.14)

Outputs Per Module

25.7(1.01)

T1K–08TD2–1 DC Output

Rev A

3–36

Specifications

Page 64

Specifications

Wiring & Dimensions

T1H–08TDS Isolated DC Output

Note: Apply the labels that come with the I/O module to the I/O base to properly identify the terminal points.

8 (isolated)

Operating Voltage Range

5 to 36VDC

Max. Voltage

36VDC

Output Clamp Voltage

40VDC

Max. Load Current

2A per point, 16A per module, 32 to140_F (0 to 60_C)

Electronic Over Current Protection

Output trips at 6A min., 12A max.

Max.Load Voltage

36VDC

Max. Leakage Current

75µA

Max. ON State Voltage Drop

0.3V at 2A, 0.15V at 1A

Inrush Current

5A for 20ms

OFF to ON Response

< 3µs

ON to OFF Response

<100µs

Base Power Required

200mA max.

Thermal Shutdown

Between Tjunction = 302_F to 374_F (150_C to 190_C)

Overtemperature Reset

Thermal shutdown temp.minus 5_F (15_C)

Status Indications

Logic Side

Weight

93.6g

Output Points 0 0

1

1

2

L

L -

-

+

+

2 3

3

4

Sourcing Examples

4

5

5

6 6

5–36VDC - + + L

T1H–08TDS

7 7

L

54.3(2.14) 80 (3.15)

8 (isolated, sink/source)

Commons

8.1 (0.32)

Sinking Examples

5–36VDC 25.7(1.01)

Outputs Per Module

89 (3.5)

9.2 (0.36)

Commons C0 C0 C1 C1 C2 C2 C3 C3 C4 C4 C5 C5 C6 C6 C7 C7

8.1 (0.32) –––– USER BUS 1 ––––

83.3 (3.28)

–––– USER BUS 2 –––– mm (in.)

No connection: Eight User Bus 1 terminals bussed together for distribution; same for eight User Bus 2 terminals.

Environmental Specifications Ambient Operating Temperature

32_F to 140_F (0_C to 60_C)

Storage Temperature

–4_F to 158_F (–20_C to 70_C)

Ambient Humidity

5% to 95% (Non–condensing)

Atmosphere

No corrosive gases. The level of environmental pollution = 2 (UL 840)

Vibration Resistance

MIL STD 810C, Method 514.2

Shock Resistance

MIL STD 810C, Method 516.2

Voltage Withstand

1500VAC, 1 minute

Insulation Resistance

500VDC, 10M ohm

Noise Immunity

NEMA ICS3–304 Impulse Noise 1us, 1000V FCC class A RFI (144MHz, 430MHz 10W, 10cm)

Agency Approvals

Equivalent Output Circuit Side View

Sourcing (High Side Switching)

Sinking (Low Side Switching)

Internal Module Circuitry COM +

-

5-36VDC

L

Out

Internal Module Circuitry

Isolated DC P/S

L +

-

Opto Isolator

To LED

COM

5-36VDC

Out

Isolated DC P/S

Opto Isolator

To LED

UL, CE, FCC class A

3–37

Page 65

3–38

Wiring & Dimensions 89 (3.5)

9.2 (0.36)

16 (sink)

Commons Per Module

4 internally connected

Operating Voltage Range

6–27 VDC

Output Voltage Range

5–30 VDC min. /max.

Peak Voltage

50 VDC

Max. Load Current

1A / pt., 4A / common

Max. Leakage Current

15uA @ 30VDC

ON Voltage Drop

0.3VDC @ 1.0A

Max. Inrush Current

2A for 100ms

OFF to ON Response

< 10us

ON to OFF Response

< 60us

Base Power Required

200mA @ 5VDC

External Power Required

400mA max. @ 20–28VDC

Status Indicators

Logic Side

Error Status Indications (LEDS)

24V ON = low external power FU1/FU2 ON = fuse 1 or 2 blown FU3/FU4 ON = fuse 3 or 4 blown

Fuses (User Replaceable) T1K–FUSE–1

4, (6.3A, 250V / common), (4 pts. / fuse) NQ3–6.3 SOC corp.

Weight

140g

Output Points TD1

0 1 2 3 4 5 6 7 8 9 1011 1213 14 15

12-24 VDC + -

L

L L L L L L L

COM 0

24V FU1

FU3

FU2

FU4

L L L L L L L L

COM 2

COM 3

Commons

+ 24VDC

COM 1

Fuses located under top cover

54.3(2.14)

Outputs Per Module

8.1 (0.32)

25.7(1.01)

T1K–16TD1 DC Output

Rev A

V0

V1

V2

V3

8.1 (0.32)

V0 – V3 internally connected mm (in.) 83.3 (3.28) T1K–16TD1

Environmental Specifications

Points

Derating Chart 0.4A 0.5A

16 Ambient Operating Temperature

32_F to 131_F (0_C to 55_C)

Storage Temperature

–4_F to 158_F (–20_C to 70_C)

Ambient Humidity

5% to 95% (Non–condensing)

Atmosphere

No corrosive gases. The level of environmental pollution = 2 (UL 840)

Vibration Resistance

MIL STD 810C, Method 514.2

Shock Resistance

MIL STD 810C, Method 516.2

Voltage Withstand

1500VAC, 1 minute

Insulation Resistance

500VDC, 10M ohm

Noise Immunity

NEMA ICS3–304

12 8

0.75A

4

1.0A

0 0 32

10 20 30 40 50 55 °C 50 68 86 104 122 131 ° F Ambient Temperature (°C/°F)

Side View

Equivalent Output Circuit

Impulse Noise 1us, 1000V

24VDC

FCC class A RFI (144MHz, 430MHz 10W, 10cm) Agency Approvals

80 (3.15)

Specifications

-

UL, CE, FCC class A

Sink Module External Power

-

+

+

Internal Module Circuitry V0-V3

Output

Optical Isolator

L To LED

12-24VDC 6.3A COM

Other Circuits

Page 66

Wiring & Dimensions 89 (3.5)

9.2 (0.36)

16 (source)

Commons Per Module

4 internally connected

Operating Voltage Range

12–24 VDC

Output Voltage Range

10.8–26.4 VDC

Rev A

Output Points TD2–1 Fuses located under top cover

0 1 2 3 4 5 6 7 8 9 1011 1213 1415

Peak Voltage

50 VDC

Max. Load Current

1A / pt., 4A/common (subject to derating)

Max. Leakage Current

15uA @ 26.4 VDC

ON Voltage Drop

1.2 VDC @ 1.0A

Max. Inrush Current

2A for 100ms

-

-

OFF to ON Response

< 10us

+

+

ON to OFF Response

< 0.5ms

Base Power Required

200mA @ 5VDC

Status Indicators

Logic Side

Error Status Indications (LEDS)

FU1/FU2 ON = fuse 1 or 2 blown FU3/FU4 ON = fuse 3 or 4 blown

Fuses (User Replaceable) T1K–FUSE–1

4, (6.3A, 250V / common), (4 pts. / fuse) NQ3–6.3 SOC corp.

Weight

140g

FU1

FU3

FU2

FU4

54.3(2.14)

Outputs Per Module

12-24 VDC L L L L L L L L L L L L L L L L 12-24 VDC

COM 0

COM 1

COM 2

COM 3

-

-

+

+

25.7(1.01)

T1K–16TD2–1 DC Output

8.1 (0.32)

Commons

0V

0V

0V

0V

80 (3.15)

Specifications

8.1 (0.32)

V0 – V3 internally connected mm (in.)

Note: Apply the 0V label that comes with the I/O module to I/O base terminal points V0–V3 to properly identify the 0VDC terminal points.

83.3 (3.28)

Environmental Specifications Ambient Operating Temperature

32_F to 131_F (0_C to 55_C)

Storage Temperature

–4_F to 158_F (–20_C to 70_C)

Ambient Humidity

5% to 95% (Non–condensing)

Atmosphere

No corrosive gases. The level of environmental pollution = 2 (UL 840)

12

Vibration Resistance

MIL STD 810C, Method 514.2

8

Shock Resistance

MIL STD 810C, Method 516.2

4

Voltage Withstand

1500VAC, 1 minute

Insulation Resistance

500VDC, 10M ohm

Noise Immunity

NEMA ICS3–304

Derating Chart Points 16

0.5A 0.75A 1.0A

0 0 32

10 20 30 40 50 55 °C 50 68 86 104 122 131 °F Ambient Temperature (°C/°F)

Side View

Impulse Noise 1us, 1000V FCC class A

Equivalent Output Circuit

RFI (144MHz, 430MHz 10W, 10cm) Agency Approvals

UL, CE, FCC class A

Internal Module Circuitry Output

Source Module External Power

0V (V0-V3)

Optical Isolator

L To LED +

COM 12-24VDC

6.3A Other Circuits

3–39

-

Page 67

Wiring & Dimensions 48 (1.89)

9.2 (0.36)

Commons Per Module

2, 4 pts. / common (isolated)

Operating Voltage Range

17–240 VAC (47–63Hz)

Output Voltage Range

15–264 VAC (47–63Hz) min. /max.

Max. Load Current

1A / pt., 4A /common(subject to derating)

ON Voltage Drop

1.5VAC @ > 50mA, 4.0VAC @ < 50mA

Max. Leakage Current

4mA @ 264 VAC

Max. Inrush Current

10A for 10ms

Min. Load

10mA

OFF to ON Response

< 1ms

ON to OFF Response

< 1ms + 1/2 cycle

Base Power Required

250mA @ 5VDC

Status Indicators

Logic Side

Error Status Indications (LEDS)

FU1 ON = fuse 1 blown FU2 ON = fuse 2 blown

Fuses (User Replaceable) T1K–FUSE–2

2, (10A, 250V / common), (4 pts. / fuse) 5 x 20 mm type

Weight

140g

Output Points

T1K–08TA L

L

L

L

L

L

L

L

FU1 FU2

Fuses located under top cover

F

0

17-240VAC

17-240VAC

V0–V1 not used with AC Output Modules

Date Code: 008* Derating Chart

Date Code: 00Z* and later Derating Chart

Points

0.5A

Ambient Operating Temperature

32_F to 131_F (0_C to 55_C)

6

0.75A

6

0.75A

Storage Temperature

–4_F to 158_F (–20_C to 70_C)

4

1.0A

4

1.0A

Ambient Humidity

5% to 95% (Non–condensing)

2

Atmosphere

No corrosive gases. The level of environmental pollution = 2 (UL 840)

0

1500VAC, 1 minute

Insulation Resistance

500VDC, 10M ohm

Noise Immunity

NEMA ICS3–304

4 4

5

6

7

83.3 (3.28)

8

MIL STD 810C, Method 516.2

3 mm (in.)

0.5A

Voltage Withstand

2

2 3

8.1 (0.32)

8

Shock Resistance

D

1

C 5

0 1 2 3 4 5 6 7

Environmental Specifications

MIL STD 810C, Method 514.2

E

B 6 1

Commons

Points

Vibration Resistance

A

2 0 0 32

10 20 30 40 50 55 °C 50 68 86 104 122 131 ° F Ambient Temperature (°C/°F)

0 32

10 20 30 40 50 55 °C 50 68 86 104 122 131 ° F Ambient Temperature (°C/°F)

Side View

Equivalent Output Circuit

Impulse Noise 1us, 1000V

Internal Module Circuitry

FCC class A RFI (144MHz, 430MHz 10W, 10cm) Agency Approvals

80 (3.15)

8

54.3(2.14)

Rev B

Outputs Per Module

8.1 (0.32)

25.7(1.01)

T1K–08TA AC Output

3–40

Specifications

UL, CE, FCC class A

+V

Output

L

To LED 10A

17-240VAC

COM

Optical Isolator

Page 68

Wiring & Dimensions

Specifications

89 (3.5)

9.2 (0.36)

16

Commons Per Module

4, 4 pts. / common (isolated)

Operating Voltage Range

17–240 VAC (47–63Hz)

Output Voltage Range

15–264 VAC (47–63Hz) min. /max.

Max. Load Current

1A / pt., 4A/common (subject to derating)

ON Voltage Drop

1.5VAC @ > 50mA, 4.0VAC @ < 50mA

Max. Leakage Current

4mA @ 264 VAC

Max. Inrush Current

10A for 10ms

Min. Load

10mA

OFF to ON Response

< 1ms

ON to OFF Response

< 1ms + 1/2 cycle

Base Power Required

450mA @ 5VDC

Status Indicators

Logic Side

Error Status Indications (LEDS)

FU1/FU2 ON = fuse 1 or 2 blown FU3/FU4 ON = fuse 3 or 4 blown

Fuses (User Replaceable) T1K–FUSE–2

4, (10A, 250V / common), (4 pts. / fuse) 5 x 20 mm type

Weight

190g

Output Points TA

0 1 2 3 4 5 6 7 8 9 1011 1213 1415 L

L L L L L L L

COM 0

Fuses located under top cover

FU1

FU3

FU2

FU4

54.3(2.14) 80 (3.15)

Outputs Per Module

8.1 (0.32)

L L L L L L L L

COM 1

COM 2

COM 3

17-240VAC

25.7(1.01)

T1K–16TA AC Output

Rev B

Commons

17-240VAC V0

V2

V1

V3

8.1 (0.32)

V0 – V3 not used with AC Output Modules mm (in.) 83.3 (3.28)

Date Code: 012* and Later Derating Chart

Environmental Specifications Points 16

Ambient Operating Temperature

32_F to 131_F (0_C to 55_C)

Storage Temperature

–4_F to 158_F (–20_C to 70_C)

Ambient Humidity

5% to 95% (Non–condensing)

8

Atmosphere

No corrosive gases. The level of environmental pollution = 2 (UL 840)

4

Vibration Resistance

MIL STD 810C, Method 514.2

0

Shock Resistance

MIL STD 810C, Method 516.2

Voltage Withstand

1500VAC, 1 minute

Insulation Resistance

500VDC, 10M ohm

Noise Immunity

NEMA ICS3–304

0.5A 0.75A

12

1.0A

0 32

10 20 30 40 50 55 °C 50 68 86 104 122 131 ° F Ambient Temperature (°C/°F)

Side View

Equivalent Output Circuit

Impulse Noise 1us, 1000V FCC class A

Internal Module Circuitry

RFI (144MHz, 430MHz 10W, 10cm) Agency Approvals

UL, CE, FCC class A

+V

Output

L

To LED 10A

Optical Isolator

3–41

17-240VAC

COM

Page 69

Wiring & Dimensions

T1K–08TAS AC Output

Note: Apply the labels that come with the I/O module to the I/O base to properly identify the terminal points.

8 , 1 pt. / common (isolated)

Operating Voltage Range

17–240 VAC (47–63Hz)

Output Voltage Range

15–264 VAC (47–63Hz) min. /max.

Max. Load Current

2A / pt. (subject to derating)

ON Voltage Drop

1.5VAC @ > 50mA, 4.0VAC @ < 50mA

Max. Leakage Current

4mA @ 264 VAC

Max. Inrush Current

10A for 10ms

Min. Load

10mA

OFF to ON Response

< 1ms

ON to OFF Response

< 1ms + 1/2 cycle

Base Power Required

300mA @ 5VDC

Status Indicators

Logic Side

Error Status Indications (LEDS)

FU1/FU2 ON = fuse 1 or 2 blown FU3/FU4 ON = fuse 3 or 4 blown FU5/FU6 ON = fuse 5 or 6 blown FU7/FU8 ON = fuse 7 or 8 blown

Fuses (User Replaceable) T1K–FUSE–3

8, (10A, 250V / common), (1 pt. / fuse) NQ3–10 SOC Corp.

Weight

190g

Environmental Specifications

Output Points 0

C0

1

C1

32_F to 131_F (0_C to 55_C)

Storage Temperature

–4_F to 158_F (–20_C to 70_C)

Ambient Humidity

5% to 95% (Non–condensing)

Atmosphere

No corrosive gases. The level of environmental pollution = 2 (UL 840)

Vibration Resistance

MIL STD 810C, Method 514.2

Shock Resistance

MIL STD 810C, Method 516.2

Voltage Withstand

1500VAC, 1 minute

Insulation Resistance

500VDC, 10M ohm

Noise Immunity

NEMA ICS3–304

3

C2

C3

4

5

6

7

L

L

L

L

C4

C5

C6

C7

Fuses located under top cover

FU1

FU3

FU5

FU7

FU2

FU4

FU6

FU8

Commons

Note: See other side for wiring example.

17-240VAC V0

V2

V1

V3

8.1 (0.32)

V0 – V3 not used with AC Output Modules mm (in.) Date Code: 008* Points 8

Derating Chart Points 8

1.0A 1.5A

2.0A

4

2

1.0A 1.5A

6

2.0A

4

83.3 (3.28)

Date Code: 012* and later

Derating Chart

6 Ambient Operating Temperature

2

54.3(2.14)

Commons Per Module

8.1 (0.32)

2

0

0 0 32

10 20 30 40 50 55 °C 50 68 86 104 122 131 °F Ambient Temperature (°C/°F)

0 32

10 20 30 40 50 55 °C 50 68 86 104 122 131 ° F Ambient Temperature (°C/°F)

Side View

Equivalent Output Circuit Internal Module Circuitry

Impulse Noise 1us, 1000V FCC class A RFI (144MHz, 430MHz 10W, 10cm) Agency Approvals

80 (3.15)

8

89 (3.5)

9.2 (0.36)

25.7(1.01)

Rev A

Outputs Per Module

3–42

Specifications

+V

Output

UL, CE, FCC class A

L

To LED 10A

17-240VAC

COM

Optical Isolator

Page 70

Wiring & Dimensions 48 (1.89)

9.2 (0.36)

Output Type

Relay Form A (SPST) normally open

Commons Per Module

2 , 4 pts. / common (isolated)

Operating Voltage Range

6–240 VAC (47–63Hz), 6–27 VDC

Output Voltage Range

T1K–08TR L

5–264 VAC (47–63Hz) min. /max. 5–30 VDC min. /max.

Max. Load Current

2A / pt., 8A / common

Max. Leakage Current

0.1mA @ 264 VAC

Max. Inrush Current

6A for 10ms / pt.; 20A for 10ms / com

Min. Load

5mA @ 5VDC

OFF to ON Response

< 15ms

ON to OFF Response

< 10ms

Base Power Required

350mA @ 5VDC

Status Indicators

Logic Side

Error Status Indications (LEDS)

FU1 ON = fuse 1 blown FU2 ON = fuse 2 blown

Fuses (User Replaceable) T1K–FUSE–2

2, (10A, 250V / common), (4 pts. / fuse) 5 x 20 mm type

Weight

110g

L

L

L

L

L

L

L

FU1 FU2

Fuses located under top cover

F

0

6-27VDC 6-240VAC

6-27VDC 6-240VAC

A

E

D

1

2

B 6 1 C 5 3

4 4

2

80 (3.15)

8

8.1 (0.32)

Output Points

Rev A

Outputs Per Module

3 5

6

7

0 1 2 3 4 5 6 7 25.7(1.01)

T1K–08TR Relay Output

54.3(2.14)

Specifications

Commons

8.1 (0.32)

V0, V1 not used with Relay Output Modules mm (in.) 83.3 (3.28)

Equivalent Output Circuit Environmental Specifications Ambient Operating Temperature

32_F to 131_F (0_C to 55_C)

Storage Temperature

–4_F to 158_F (–20_C to 70_C)

Ambient Humidity

5% to 95% (Non–condensing)

Atmosphere

No corrosive gases. The level of environmental pollution = 2 (UL 840)

Vibration Resistance

MIL STD 810C, Method 514.2

Shock Resistance

MIL STD 810C, Method 516.2

Voltage Withstand

1500VAC, 1 minute

Insulation Resistance

500VDC, 10M ohm

Noise Immunity

NEMA ICS3–304

Internal Module Circuitry +V

Output

L To LED 10A

AC or DC Supply

Side View

COM 6-27VDC 6-240VAC

Impulse Noise 1us, 1000V FCC class A

Agency Approvals

Typical Relay Life (Operations) at Room Temperature

UL, CE, FCC class A

Voltage & Type of Load

1A

2A

24 VDC Resistive

500K

250K

24 VDC Solenoid

100K

50K

110 VAC Resistive

500K

250K

110 VAC Solenoid

200K

100K

220 VAC Resistive

350K

200K

220 VAC Solenoid

100K

50K

Load Current

Derating Chart

Points 8

1.5A

6

2.0A

4 2 0 0 32

10 20 30 40 50 55 °C 50 68 86 104 122 131 °F Ambient Temperature (°C/°F)

3–43

RFI (144MHz, 430MHz 10W, 10cm)