Page 71

89 (3.5)

9.2 (0.36)

Rev C

Relay Form A (SPST) normally open

Commons Per Module

4 , 4 pts. / common (isolated)

Operating Voltage Range

6–240 VAC, 6–27 VDC

Output Voltage Range

5–264 VAC (47–63Hz) min. / max. 5–30 VDC min. / max.

Max. Load Current

2A / pt., 6A /common(subject to derating)

Max. Leakage Current

0.1mA @ 264 VAC

Max. Inrush Current

6A for 10ms / pt.; 20A for 10ms / com

Min. Load

5mA @ 5VDC

OFF to ON Response

< 15ms

ON to OFF Response

< 10ms

Base Power Required

700mA @ 5VDC

Status Indicators

Logic Side

Error Status Indications (LEDS)

FU1/ FU2 ON = fuse 1 or 2 blown FU3/ FU4 ON = fuse 3 or 4 blown

Fuses (User Replaceable) T1K–FUSE–2

4, (10A, 250V / common), (4 pts. / fuse) 5 x 20 mm type

Weight

200g

Output Points TR Fuses located under top cover

0 1 2 3 4 5 6 7 8 9 1011 12 13 1415 L

L L L L L L L

COM 0

COM 1

V0

V1

FU3

FU2

FU4

L L L L L L L L

COM 2

COM 3

Commons

6-27VDC 6-240VAC

FU1

54.3(2.14)

16

Output Type

6-27VDC 6-240VAC

V2

V3

8.1 (0.32)

V0 – V3 not used with Relay Output Modules mm (in.) 83.3 (3.28)

Equivalent Output Circuit Environmental Specifications Ambient Operating Temperature

32_F to 131_F (0_C to 55_C)

Storage Temperature

–4_F to 158_F (–20_C to 70_C)

Ambient Humidity

5% to 95% (Non–condensing)

Atmosphere

No corrosive gases. The level of environmental pollution = 2 (UL 840)

Vibration Resistance

MIL STD 810C, Method 514.2

Shock Resistance

MIL STD 810C, Method 516.2

Voltage Withstand

1500VAC, 1 minute

Insulation Resistance

500VDC, 10M ohm

Noise Immunity

NEMA ICS3–304

Internal Module Circuitry +V

Output

L To LED 10A

AC or DC Supply

Side View

COM 6-27VDC 6-240VAC

Impulse Noise 1us, 1000V

Date Code: 012* and later

FCC class A RFI (144MHz, 430MHz 10W, 10cm) Agency Approvals

UL, CE, FCC class A

80 (3.15)

Outputs Per Module

8.1 (0.32)

25.7(1.01)

T1K–16TR Relay Output

3–44

Wiring & Dimensions

Specifications

Derating Chart

Typical Relay Life (Operations) at Room Temperature Voltage & Type of Load

Load Current

Points 16

1A

2A

24 VDC Resistive

500K

250K

24 VDC Solenoid

100K

50K

110 VAC Resistive

500K

250K

110 VAC Solenoid

200K

100K

4

220 VAC Resistive

350K

200K

0

220 VAC Solenoid

100K

50K

1.0A 1.5A

12 2.0A

8

0 32

10 20 30 40 50 55 °C 50 68 86 104 122 131 ° F Ambient Temperature (°C/°F)

Page 72

Specifications

Wiring & Dimensions

T1K–08TRS Relay Output

Note: Apply the labels that come with the I/O module to the I/O base to properly identify the terminal points.

Outputs Per Module

8

Output Type

Relay Form A (SPST) normally open

Commons Per Module

8, 1 pt. / common (isolated)

Operating Voltage Range

6–240 VAC (47–63Hz), 6–27 VDC

89 (3.5)

9.2 (0.36) 8.1 (0.32)

Output Points

5–264 VAC (47–63Hz) min. / max. 5–30 VDC min. / max.

Max. Load Current

7A / pt. (subject to derating)

Max. Leakage Current

0.1mA @ 264 VAC

Max. Inrush Current

8A for 10ms

Min. Load

5mA @ 5VDC

OFF to ON Response

< 15ms

ON to OFF Response

< 10ms

Base Power Required

400mA @ 5VDC

Status Indicators

Logic Side

Error Status Indications (LEDS)

FU1/ FU2 ON = fuse 1 or 2 blown FU3/ FU4 ON = fuse 3 or 4 blown FU5/ FU6 ON = fuse 5 or 6 blown FU7/ FU8 ON = fuse 7 or 8 blown

Fuses (User Replaceable) T1K–FUSE–3

8, (10A, 250V / common), (1 pt. / fuse) NQ3–10 SOC Corp.

Weight

185g

C0

2

C1

Note: See other side for wiring example.

3

C2

4

C3

5

6

Fuses located under top cover

7

L

L

L

L

C4

C5

C6

C7

Commons

V0

V1

FU1

FU3

FU5

FU7

FU2

FU4

FU6

FU8

25.7(1.01)

Output Voltage Range

1

54.3(2.14) 80 (3.15)

08TRS

0

6-240VAC 6-27VDC V2

V3

8.1 (0.32)

Note: V0 – V3 not used on Relay Output Modules mm (in.) 83.3 (3.28)

Equivalent Output Circuit Internal Module Circuitry

Environmental Specifications Ambient Operating Temperature

32_F to 131_F (0_C to 55_C)

Storage Temperature

–4_F to 158_F (–20_C to 70_C)

Ambient Humidity

5% to 95% (Non–condensing)

Atmosphere

No corrosive gases. The level of environmental pollution = 2 (UL 840)

Vibration Resistance

MIL STD 810C, Method 514.2

Shock Resistance

MIL STD 810C, Method 516.2

Voltage Withstand

1500VAC, 1 minute

Insulation Resistance

500VDC, 10M ohm

Noise Immunity

NEMA ICS3–304 Impulse Noise 1us, 1000V FCC class A RFI (144MHz, 430MHz 10W, 10cm)

Agency Approvals

UL, CE, FCC class A

+V

Output

L To LED AC or DC Supply

10A

Side View

COM 6-27VDC 6-240VAC

Derating Chart Typical Relay Life (Operations) at Room Temperature Voltage & Type of Load

Points 8

Load Current 5A 2A

24 VDC Resistive

1000K

500K

200K

100K

24 VDC Solenoid

300K

100K

**

**

110 VAC Resistive

1000K

500K

200K

100K

110 VAC Solenoid

300K

100K

**

**

220 VAC Resistive

500K

250K

125K

60K

220 VAC Solenoid

300K

100K

**

**

** Solenoid (inductive) loads > 2A cannot be used.

7A

4A 5A

6

6A

4

7A

2 0 0 32

10 20 30 40 50 55 °C 50 68 86 104 122 131 ° F Ambient Temperature (°C/°F)

3–45

1A

Page 73

Wiring & Dimensions

0–20mA, 4–20mA, –20 to 20mA

Resolution

14 bit (13 bit plus sign bit)

Frequency Response

T1F–08AD–1 Fuse

–3db @ 500Hz, –20db/decade 250 ohm

Absolute Max. Ratings

8V max. input Normal Mode: 5ms per channel *Fast Mode: 0.5ms per channel

Linearity Error

+ / – 2 count max.

Input Stability

+ / – 1 count

Full Scale Error (Offset Error not included)

16 counts max.

Offset Error

2 counts max.

Max. Full Scale Inaccuracy (% of full scale) all errors included

0.18% @ 25_C 0.36% @ 60_C

Master Update Rate

8 channels per scan max.

Input Points Required

256 discrete pts. or 8 dwords (d (double) word = 32 bit word) Network Interface dependent

Base Power Required

75mA @ 5VDC

External Power Supply

18–30 VDC, 50mA, class 2

Recommended Fuse

0.032A, Series 217 Fast Acting

Operating Temperature

0 to 60_C (32 to 140_F)

Storage Temperature

–20 to 70_C (–4 to 158_F)

Accuracy vs. Temperature

+ / – 50 ppm / _C max. full scale

Relative Humidity

5 to 95% (non–condensing) No corrosive gases permitted

Vibration

MIL STD 810C 514.2

Shock

MIL STD 810C 516.2

Noise Immunity

NEMA ICS3–304

Weight

136g

Input Range Resolution: –20 to 20mA

–8192 to 8191 counts

0 – 20mA

0 – 8191 counts

4 – 20mA

1638 – 8191 counts

0

2–Wire Current Transmitter

Transmitter Supply 18-30VDC

E

D

1

2

B 6 1 C 5 3

2

4 4

3 5

6

7

0 1 2 3 4 5 6 7

-

+ Module Supply 24VDC

Note: V1 internally connected to Commons

8.1 (0.32) mm (in.)

83.3 (3.28) NOTES: 1: Shields should be grounded at the signal source. 2: More than one external power supply can be used, provided all the power supply commons are connected. 3: A Series 217, 0.032A fast-acting fuse is recommended for 4–20 mA current loops. 4: If the power supply common of an external power supply is not connected to the 0V terminal on the module, then the output of the external transmitter must be isolated. To avoid “ground loop” errors, recommended 4–20 mA transmitter types are: –For 2 or 3 wire connections: Isolation between the input supply signal and the power supply. –For 4 wire connections: Isolation between the input supply signal, the power supply and the 4–20mA output.

Side View

Equivalent Input Circuit Transmitter Supply 18-30VDC

+

+

-

-

See NOTE 1 +

+

4 – 20mA 20mA

20mA

4mA

Internal Module Circuitry

Input

– 3–Wire Current Transmitter

Input Signal Ranges

Module Supply 24VDC V0 V1 mm (in.)

0 – 20mA

Fuse 250 ohms

0mA Analog Switch

Environmental Air

4–Wire Current Transmitter

A

+

Conversion Time (Default: Normal Mode)

F

Commons (not isolated)

-

+

Input Resistance

Fuse

80 (3.15)

Input Ranges

Input points

25.7(1.01)

8, single ended (1 common)

8.1 (0.32)

54.3(2.14)

T1F–08AD–1 8 Channel Current Analog Input Number of Channels

48 (1.89)

9.2 (0.36)

Rev B

3–46

Specifications

0

1638

8191 –20 to 20mA

A to D Converter

20mA 0mA

*Fast mode supported in module hardware version B or later.

COM

–20mA –8191

8191

8191

Page 74

Wiring & Dimensions

0–5V, 0–10V, +/– 5V, +/– 10V

Resolution

14 bit (13 bit plus sign bit)

Frequency Response

–3db @ 500Hz, –20db/decade

Input Resistance

200K ohm min.

Absolute Max. Ratings

Fault Protected Input 130V(rms) or 100VDC

T1F–08AD–2 F

-

Normal Mode: 5ms per channel *Fast Mode: 0.5ms per channel

Linearity Error

+ / – 2 count max.

Input Stability

+ / – 1 count

Calibration Full Scale Error

8 counts max.

Calibration Offset Error

2 counts max.

Max. Full Scale Inaccuracy (% of full scale); all errors included

0.08% @ 25_C 0.26% @ 60_C

Master Update Rate

8 channels per scan max.

Input Points Required

256 discrete pts. or 8 dwords (d (double) word = 32 bit word) Network Interface dependent

Base Power Required

75mA @ 5VDC

External Power Supply

18–30 VDC, 50mA, class 2

Operating Temperature

0 to 60_C (32 to 140_F)

Storage Temperature

–20 to 70_C (–4 to 158_F)

Accuracy vs. Temperature

+ / – 50 ppm / _C max. full scale

0

4–Wire Voltage Transmitter

5 to 95% (non–condensing)

Environmental Air

No corrosive gases permitted

Vibration

MIL STD 810C 514.2

Shock

MIL STD 810C 516.2

Noise Immunity

NEMA ICS3–304 weight

136g

Transmitter Supply 18-30VDC + Module Supply 24VDC

Note: V1 internally connected to Commons

0 – 8191 counts

+ / – 5V

–4095 to 4095 counts

+ / – 10V

–8192 to 8191 counts

5

6

7 mm (in.)

83.3 (3.28)

–5 to 5V

0 – 10V 5V

10V

5V

0V

0

4095

0V

–5V

0V

0V

0

8191

–10 to 10V 10V

Side View mm (in.)

–10V –4095

4095

–8192

8191

Equivalent Input Circuit Transmitter Supply 18-30VDC

– 3–Wire Voltage Transmitter

*Fast mode supported in module hardware version B or later.

+

+

-

-

Module Supply 24VDC V0 V1 Input

+

COM

Internal Module Circuitry

A to D Converter

3–47

0 – 10V

4 4

Analog Switch

0 – 4095 counts

3

Input Signal Ranges

+

0 – 5V

2

2 3

8.1 (0.32)

NOTES: 1: Shields should be grounded at the signal source. 2: Unused inputs should be connected to Common (0VDC). 3: More than one external power supply can be used, provided all the power supply commons are connected.

See NOTE 1

Input Range Resolution:

D

1

C 5

0 1 2 3 4 5 6 7

0 – 5V

Relative Humidity

E

B 6 1

+

Conversion Time (Default: Normal Mode)

Commons (not isolated)

A

25.7(1.01)

Input Ranges

Input points

+

8, single ended (1 common)

8.1 (0.32)

80 (3.15)

T1F–08AD–2 8 Channel Voltage Analog Input Number of Channels

48 (1.89)

9.2 (0.36)

Rev B

54.3(2.14)

Specifications

Page 75

89 (3.5)

9.2 (0.36) 8.1 (0.32)

T1F–16AD–1 16 Channel Current Analog Input Number of Channels

16, single ended (1 common)

Input Ranges

0–20mA, 4–20mA, –20 to 20mA

Resolution

14 bit (13 bit plus sign bit)

Frequency Response

–3db @ 500Hz, –20db/decade

Input Resistance

250 ohm

Absolute Max. Ratings

8V max. input

+

Conversion Time

5ms per channel

Linearity Error

+ / – 2 count max.

4–Wire Current Transmitter

Input Stability

+ / – 1 count

Full Scale Error (Offset Error not included)

16 counts max.

Offset Error

2 counts max.

Max. Full Scale Inaccuracy (% of full scale) all errors included

0.18% @ 25_C , 0.36% @ 60_C

Master Update Rate

16 channels per scan max.

Input Points Required

512 discrete pts. or 16 dwords (d (double) word = 32 bit word) Network Interface dependent

Base Power Required

75mA @ 5VDC

External Power Supply

18–30 VDC, 50mA, class 2

Recommended Fuse

0.032A, Series 217 Fast Acting

Operating Temperature

0 to 60_C (32 to 140_F)

Storage Temperature

–20 to 70_C (–4 to 158_F)

Accuracy vs. Temperature

+ / – 50 ppm / _C max. full scale

Relative Humidity

5 to 95% (non–condensing)

Environmental Air

No corrosive gases permitted

3–48

Wiring & Dimensions

54.3(2.14)

Input points 0 1 2 3 4 5 6 7 8 9 10 11 12 13 1415

Fuse

Fuse

Commons (not isolated) COM 0

COM 1

COM 2

COM 3

V2

V3

2–Wire Current Transmitter

25.7(1.01)

-

+ Transmitter Supply 18-30VDC V0

V1

8.1 (0.32)

-

Note: V0 and V1 internally Module Supply connected 24VDC

Note: V2 and V3 internally connected to Commons

+ mm (in.)

83.3 (3.28) NOTES: 1: Shields should be grounded at the signal source. 2: More than one external power supply can be used, provided all the power supply commons are connected. 3: A Series 217, 0.032A fast-acting fuse is recommended for 4–20 mA current loops. 4: If the power supply common of an external power supply is not connected to the 0V terminal on the module, then the output of the external transmitter must be isolated. To avoid “ground loop” errors, recommended 4–20 mA transmitter types are: –For 2 or 3 wire connections: Isolation between the input supply signal and the power supply. –For 4 wire connections: Isolation between the input supply signal, the power supply and the 4–20mA output.

side View

Shock

MIL STD 810C 516.2

Noise Immunity

NEMA ICS3–304

Weight

168g

Transmitter Supply 18-30VDC +

+

-

-

See NOTE 1 +

Input

–

Input Range Resolution: –20 to 20mA

–8192 to 8191 counts

0 – 20mA

0 – 8191 counts

4 – 20mA

1638 – 8191 counts

3–Wire Current Transmitter

+

Module Supply 24VDC

4 – 20mA 20mA

20mA

V0-V1 V2-v3 Internal Module Circuitry

Fuse 250 ohms

4mA 0mA Analog Switch

MIL STD 810C 514.2 mm (in.)

Input Signal Ranges

Equivalent Input Circuit

0 – 20mA

Vibration

80 (3.15)

Specifications

0

1638

8191

–20 to 20mA A to D Converter

20mA 0mA

COM

–20mA –8191

8191

8191

Page 76

Wiring & Dimensions 89 (3.5)

9.2 (0.36) 8.1 (0.32)

T1F–16AD–2 16 Channel Voltage Analog Input Input Ranges

0–5V, 0–10V, +/– 5V, +/– 10V

Resolution

14 bit (13 bit plus sign bit)

Frequency Response

–3db @ 500Hz, –20db/decade

Input Resistance

200K ohm min.

Absolute Max. Ratings

Fault Protected Input 130V(rms) or 100VDC

Conversion Time

5ms per channel

Linearity Error

+ / – 2 count max.

Input Stability

+ / – 1 count

Calibration Full Scale Error

8 counts max.

Calibration Offset Error

2 counts max.

Max. Full Scale Inaccuracy (% of full scale); all errors included

0.08% @ 25_C 0.26% @ 60_C

Master Update Rate

16 channels per scan max.

Input Points Required

512 discrete pts. or 16 dwords (d (double) word = 32 bit word) Network Interface dependent

Base Power Required

75mA @ 5VDC

External Power Supply

18–30VDC, 50mA, class 2

Operating Temperature

0 to 60_C (32 to 140_F)

Storage Temperature

–20 to 70_C (–4 to 158_F)

Accuracy vs. Temperature

+ / – 50 ppm / _C max. full scale

Relative Humidity

Input points 54.3(2.14)

16, single ended (1 common)

0 1 2 3 4 5 6 7 8 9 10 11 12 13 1415

+

Commons (not isolated)

-

4–Wire Voltage Transmitter

COM 0

COM 1

COM 2

COM 3 2

+ Transmitter Supply 18-30VDC V0

V2

V1

V3

8.1 (0.32)

-

Note: V0 and V1 Internally Module Supply connected 24VDC

Note: V2 and V3 internally connected to Commons

+ mm (in.)

83.3 (3.28) NOTES: 1: Shields should be grounded at the signal source. 2: Unused inputs should be connected to Common (0VDC). 3: More than one external power supply can be used, provided all the power supply commons are connected.

Input Signal Ranges –5 to 5V

0 – 10V

0 – 5V

–10 to 10V

5V

10V

5V

10V side View

5 to 95% (non–condensing)

Environmental Air

No corrosive gases permitted

Vibration

MIL STD 810C 514.2

Shock

MIL STD 810C 516.2

Noise Immunity

NEMA ICS3–304

Weight

168g

Input Range Resolution:

0V

0

4095

0

8191

0 – 8191 counts

+ / – 5V

–4095 to 4095 counts

+ / – 10V

–8192 to 8191 counts

4095

–8192

8191

Equivalent Input Circuit Transmitter Supply 18-30VDC

+ – 3–Wire Voltage Transmitter

+

+

-

-

Module Supply 24VDC V0-V1 V2-V3 Input

+

COM

Internal Module Circuitry

A to D Converter

3–49

0 – 10V

–10V –4095

Analog Switch

0 – 4095 counts mm (in.)

0V

–5V

0V

0V

See NOTE 1

0 – 5V

80 (3.15)

Number of Channels

25.7(1.01)

Specifications

Page 77

Wiring & Dimensions 48 (1.89)

9.2 (0.36)

T1F–08DA–1 8 Channel Current Analog Output

3–50

Specifications

8.1 (0.32)

Output Points

8

Output Ranges

0–20mA, 4–20mA

Output Type single ended, 1 common

Resolution

12 bit (1 in 4096)

Commons (not isolated)

30 VDC 30 VDC

Max. Load (Ohm) / Power Supply

620/18V, 910/24V, 1200/30V

Min. Load (ohm) / Power Supply**

0/24V, 350/30V @ 40_C 250/24V, 600/30V @ 60_C

Linearity Error (end to end)

+ / – 2 count max. + / – 0.050% of full scale max

Conversion Settling Time

400us max. full scale change

Full Scale Calibration Error

+ / – 12 counts max.

Offset Calibration Error

0 – 20mA: + / – 5 counts max. 4 – 20mA: + / – 6 counts max.

Accuracy vs. Temperature

+ / – 50 ppm/_C full scale calibration change

Max. Full Scale Inaccuracy (% of full scale) all errors included

0.2% @ 25_C , 0.4% @ 60_C

Master Update Rate

8 channels per scan max.

Output Points Required

256 disctete pts. or 8 dwords (d (double) word = 32 bit word) Network Interface dependent

Base Power Required

75mA @ 5VDC

External Power Supply

21.6–26.4VDC, 150mA class 2

0

0 to 60_C (32 to 140_F)

Storage Temperature

–20 to 70_C (–4 to 158_F)

Relative Humidity

5 to 95% (non–condensing)

Environmental Air

No corrosive gases permitted

Vibration

MIL STD 810C 514.2

Shock

MIL STD 810C 516.2

Noise Immunity

NEMA ICS3–304

Weight

145g

**max. allowable output power dissipation. For example, at 60_C and 24VDC, there must be a load of at least 250 ohms on the output circuit. Smaller loads will damage the analog output circuit.

D

1

2

C 5 3

4 4

2 3 5

6

7

0 1 2 3 4 5 6 7

Loop Supply 18-30VDC

+ Module Supply 24VDC

8.1 (0.32)

Note: V1 internally connected to Commons mm (in.)

NOTES: 1: Shields should be connected to the 0V terminal of the module or the 0V of the power supply. 2. Unused current outputs should remain open (no connections) for minimum power consumption.

83.3 (3.28)

Output Signal Ranges 4 – 20mA

0 – 20mA 20mA

20mA

Side View

4mA 0mA

Operating Temperature

E

B 6 1

+

Peak Output Voltage

Load 250 ohms typical

A

25.7(1.01)

Max. Loop Supply

F

80 (3.15)

Number of Channels

54.3(2.14)

Rev B

0

0

4095 mm (in.)

4095

Equivalent Output Circuit Loop Supply 18-30VDC See Note 1

+

+

-

-

Load 250 ohms typical

Module Supply 24VDC V0 V1 Output

Internal Module Circuitry Current sinking

D to A Converter

Note: This module requires software setup via the Module Control Byte. Refer to the Memory Map Chapter in the T1K–INST–M Installation and I/O Manual.

COM

Page 78

Specifications

Wiring & Dimensions 48 (1.89)

9.2 (0.36)

T1F–08DA–2 8 Channel Voltage Analog Output

8.1 (0.32)

Output Points

0–5V, 0–10V, +/– 5V, +/– 10V

Output Type single ended, 1 common

Resolution

12 bit (1 in 4096)

Peak Output Voltage

15 VDC

Load Impedance

4K ohm min.

Load Capacitance

0.01uF max.

Linearity Error (end to end)

+ / – 2 count max. + / – 0.050% of full scale max

Conversion Settling Time

100us max. full scale change

Full Scale Calibration Error

+ / – 12 counts max.

Offset Calibration Error

10V ranges:+ / – 6 counts max 5V ranges: + / – 11 counts max

Accuracy vs. Temperature

+ / – 50 ppm/_C full scale calibration change

Max. Full Scale Inaccuracy (% of full scale); all errors and temp drift included

10V ranges:+ / –0.2% @ 25_C + / –0.4% @ 60_C 5V ranges: + / –0.3% @ 25_C + / –0.5% @ 60_C

Master Update Rate

8 channels per scan max.

Output Points Required

256 discrete pts. or 8 dwords (d (double) word = 32 bit word) Network Interface dependent

Base Power Required

F

Commons (not isolated) Load 4K ohm minimum

21.6–26.4VDC, 150mA class 2

Operating Temperature

0 to 60_C (32 to 140_F)

Storage Temperature

–20 to 70_C (–4 to 158_F)

Relative Humidity

5 to 95% (non–condensing)

Environmental Air

No corrosive gases permitted

Vibration

MIL STD 810C 514.2

Shock

MIL STD 810C 516.2

Noise Immunity

NEMA ICS3–304

Weight

145g

D

1

2

C 5 3

4 4

2 3 5

6

7

8.1 (0.32)

Note: V1 internally connected to Commons mm (in.)

NOTES: 1: Shields should be connected to the 0V terminal of the module ot the 0V terminal of the power supply. 2. Unused voltage outputs should remain open (no connections) for minimum power consumption.

0V – 10V

5V

–5V to +5V

10V

0V

–10V to +10V

+5V

+10V

0V

0V

–5V

–10V

Side View

0V 4095

83.3 (3.28)

Bipolar Ranges

Unipolar Ranges 0V – 5V

0

0

4095

0 (+2047) +4095 mm (in.)

0 (+2047)+4095

Equivalent Output Circuit Module Supply 24VDC + V0 V1

See Note 1

Output

Load 4K ohm minimum

COM

Internal Module Circuitry Voltage Sink/Source

D to A Converter

3–51

Note: This module requires software setup via the Module Control Byte. Refer to the Memory Map Chapter in the T1K–INST–M Installation and I/O Manual.

E

B 6 1

0 1 2 3 4 5 6 7

+ Module Supply 24VDC

75mA @ 5VDC

External Power Supply

0

A

80 (3.15)

8

Output Ranges

25.7(1.01)

Number of Channels

54.3(2.14)

Rev B

Page 79

0–20mA, 4–20mA

Output Type single ended, 1 common

Resolution

12 bit (1 in 4096)

Max. Loop Supply

30 VDC

Peak Output Voltage

30 VDC

Max. Load (ohm) / Power Supply

620/18V, 910/24V, 1200/30V

Min. Load (ohm) / Power Supply**

0/24V, 350/30V @ 40_C 250/24V, 600/30V @ 60_C

Linearity Error (end to end)

+ / – 2 count max. + / – 0.050% of full scale max

Conversion Settling Time

400us max. full scale change

Full Scale Calibration Error

+ / – 12 counts max.

Offset Calibration Error

0 – 20mA: + / – 5 counts max. 4 – 20mA: + / – 6 counts max.

Accuracy vs. Temperature

+ / – 50 ppm/_C full scale calibration change

Max. Full Scale Inaccuracy (% of full scale) all errors included

0.2% @ 25_C, 0.4% @ 60_C

Master Update Rate

16 channels per scan max.

Output Points Required

512 discrete pts. or 16 dwords (d (double) word = 32 bit word) Network Interface dependent

Base Power Required

75mA @ 5VDC

External Power Supply

21.6–26.4VDC, 150mA class 2

Operating Temperature

0 to 60_C (32 to 140_F)

Storage Temperature

–20 to 70_C (–4 to 158_F)

Relative Humidity

5 to 95% (non–condensing)

Environmental Air

No corrosive gases permitted

Vibration

MIL STD 810C 514.2

Shock

MIL STD 810C 516.2

Noise Immunity

NEMA ICS3–304

Weight

172g

**max. allowable output power dissipation. For example, at 60_C and 24VDC, there must be a load of at least 250 ohms on the output circuit. Smaller loads will damage the analog output circuit.

Output Points 54.3(2.14)

Output Ranges

0 1 2 3 4 5 6 7 8 9 10 11 12 13 1415

Commons (not isolated)

Load 250 ohms typical

Loop Supply 18-30VDC +

COM 0

COM 1

COM 2

COM 3

V0

V1

V2

V3

+

16

8.1 (0.32)

Note: V0 and Module Supply V1 Internally 24VDC connected

8.1 (0.32)

Note: V2 and V3 internally connected to Commons mm (in.)

83.3 (3.28)

NOTES: 1: Shields should be connected to the 0V terminal of the module or the 0V of the power supply. 2. Unused current outputs should remain open (no connections) for minimum power consumption.

Output Signal Ranges 4 – 20mA

0 – 20mA 20mA

20mA side View 4mA 0mA 0

0

4095

See Note 1 Load 250 ohms typical

4095

Equivalent Output Circuit Loop Supply 18-30VDC

80 (3.15)

Rev B Number of Channels

89 (3.5)

9.2 (0.36)

25.7(1.01)

T1F–16DA–1 16 Channel Current Analog Output

Note: This module requires software setup via the Module Control Byte. Refer to the Memory Map Chapter in the T1K–INST–M Installation and I/O Manual.

3–52

Wiring & Dimensions

Specifications

+

+

-

-

Module Supply 24VDC V0-V1 V2-V3 Output

Internal Module Circuitry Current sinking

D to A Converter

COM mm (in.)

Page 80

Wiring & Dimensions

Specifications

89 (3.5)

9.2 (0.36) 8.1 (0.32)

T1F–16DA–2 16 Channel Voltage Analog Output Rev B

0–5V, 0–10V, +/– 5V, +/– 10V

Output Type single ended, 1 common

Resolution

12 bit (1 in 4096)

Peak Output Voltage

15 VDC

Load Impedance

4K ohm min.

Load Capacitance

0.01uF max.

Linearity Error (end to end)

+ / – 2 count max. + / – 0.050% of full scale max

Conversion Settling Time

100us max. full scale change

Full Scale Calibration Error

+ / – 12 counts max.

Offset Calibration Error

10V ranges:+ / – 6 counts max 5V ranges: + / – 11 counts max

Accuracy vs. Temperature

+ / – 50 ppm/_C full scale calibration change

Max. Full Scale Inaccuracy (% of full scale); all errors and temp drift included

10V ranges:+ / –0.2% @ 25_C + / –0.4% @ 60_C 5V ranges: + / –0.3% @ 25_C + / –0.5% @ 60_C

Master Update Rate

16 channels per scan max.

Output Points Required

512 discrete pts. or 16 dwords (d (double) word = 32 bit word) Network Interface dependent

Base Power Required

75mA @ 5VDC

External Power Supply

Output Points 0 1 2 3 4 5 6 7 8 9 10 11 12 13 1415

Commons (not isolated)

Load 4K ohm minimum

Storage Temperature

–20 to 70_C (–4 to 158_F)

Relative Humidity

5 to 95% (non–condensing)

Environmental Air

No corrosive gases permitted

Vibration

MIL STD 810C 514.2

Shock

MIL STD 810C 516.2

Noise Immunity

NEMA ICS3–304

Weight

172g

COM 1

COM 2

COM 3

V0

V1

V2

V3

-

Note: V0 and V1 Internally connected

Module Supply 24VDC

Unipolar Ranges 0V – 5V mm (in.)

83.3 (3.28)

Bipolar Ranges

10V

0V

0V 0

4095

–5V to +5V

0V – 10V

+10V

0V

0V

–5V 0

4095

–10V to +10V

+5V side View mm (in.)

–10V

0 (+2047) +4095

0 (+2047)+4095

Equivalent Output Circuit Module Supply 24VDC + V0-V1 V2-V3

See Note 1

Output

Load 4K ohm minimum

COM

Internal Module Circuitry Voltage Sink/Source

D to A Converter

3–53

Note: This module requires software setup via the Module Control Byte. Refer to the Memory Map Chapter in the T1K–INST–M Installation and I/O Manual.

8.1 (0.32)

Note: V2 and V3 internally connected to Commons

NOTES: 1: Shields should be connected to the 0V terminal of the module or the 0V of the power supply. 2. Unused voltage outputs should remain open (no connections) for minimum power consumption.

5V

0 to 60_C (32 to 140_F)

COM 0

+

21.6–26.4VDC, 150mA class 2

Operating Temperature

54.3(2.14)

Output Ranges

80 (3.15)

16

25.7(1.01)

Number of Channels