In This Chapter... Safety Guidelines........................................................................................................ 8–2 Mounting Guidelines. ................................................................................................ 8–5 Assembling the Components..................................................................................... 8–9 Multiple Power Supplies / Local Expansion Configurations................................... 8–11 Wiring Guidelines..................................................................................................... 8–19 I/O Wiring Strategies............................................................................................... 8–24
Page 124
Chapter 8: Installation and Wiring
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
Safety Guidelines
8-2
NOTE: Products with CE marks perform their required functions safely and adhere to relevant standards as specified by CE directives provided they are used according to their intended purpose and that the instructions in this manual are adhered to. The protection provided by the equipment may be impaired if this equipment is used in a manner not specified in this manual. A listing of our international affiliates is available on our Web site: http://www.automationdirect.com WARNING: Providing a safe operating environment for personnel and equipment is your responsibility and should be your primary goal during system planning and installation. Automation systems can fail and may result in situations that can cause serious injury to personnel or damage to equipment. Do not rely on the automation system alone to provide a safe operating environment. You should use external electromechanical devices, such as relays or limit switches, that are independent of the PLC application to provide protection for any part of the system that may cause personal injury or damage. Every automation application is different, so there may be special requirements for your particular application. Make sure you follow all national, state, and local government requirements for the proper installation and use of your equipment.
Plan for Safety The best way to provide a safe operating environment is to make personnel and equipment safety part of the planning process. You should examine every aspect of the system to determine which areas are critical to operator or machine safety. If you are not familiar with PLC system installation practices, or your company does not have established installation guidelines, you should obtain additional information from the following sources. •, The National Electrical Manufacturers Association, located in Washington, D.C. publishes many different documents that discuss standards for industrial control systems. These publications can be ordered directly from NEMA. Some of these include: 1, General Standards for Industrial Control and Systems
ICS 3, Industrial Systems
ICS 6, Enclosures for Industrial Control Systems
•, The National Electrical Code provides regulations concerning the installation and use of various types of electrical equipment. Copies of the NEC Handbook can often be obtained from your local electrical equipment distributor or your local library. • and State Agencies, many local governments and state governments have additional requirements above and beyond those described in the NEC Handbook. Check with your local Electrical Inspector or Fire Marshall office for information.
Do-more T1H Series PLC User Manual, 1st Edition, Rev. A - T1H-DM-M
Page 125
Chapter 8: Installation and Wiring
Three Levels of Protection The publications mentioned provide many ideas and requirements for system safety. At a minimum, you should follow these regulations. Also, you should use the following techniques, which provide three levels of system control.
1 • Emergency stop switch for disconnecting system power 2 • Mechanical disconnect for output module power • Orderly system shutdown sequence in the PLC control program 3 4 Emergency Stops It is recommended that emergency stop circuits be incorporated into the system for every 5 machine controlled by a PLC. For maximum safety in a PLC system, these circuits must not be wired into the controller, but should be hardwired external to the PLC. The emergency stop switches should be easily accessed by the operator and are generally wired into a master 6 control relay (MCR) or a safety control relay (SCR) that will remove power from the PLC I/O system in an emergency. 7 MCRs and SCRs provide a convenient means for removing power from the I/O system during an emergency situation. By de-energizing an MCR (or SCR) coil, power to the input (optional) and output devices is removed. This event occurs when any emergency stop switch 8 opens. However, the PLC continues to receive power and operate even though all its inputs and outputs are disabled. 9 The MCR circuit could be extended by placing a PLC fault relay (closed during normal PLC operation) in series with any other emergency stop conditions. This would cause 10 the MCR circuit to drop the PLC I/O power in case of a PLC failure (memory error, I/O communications error, etc.). 11 12 13 14 A B C D Guard Line Switch
Emergency Stop
Do-more T1H Series PLC User Manual, 1st Edition, Rev. A - T1H-DM-M
8-3
Page 126
Chapter 8: Installation and Wiring
Emergency Power Disconnect
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 8-4
A properly rated emergency power disconnect should be used to power the PLC controlled system as a means of removing the power from the entire control system. It may be necessary to install a capacitor across the disconnect to protect against a condition known as “outrush”. This condition occurs when the output TRIACs are turned off by powering off the disconnect, thus causing the energy stored in the inductive loads to seek the shortest distance to ground, which is often through the TRIACs. After an emergency shutdown or any other type of power interruption, there may be requirements that must be met before the PLC control program can be restarted. For example, there may be specific register values that must be established (or maintained from the state prior to the shutdown) before operations can resume. In this case, you may want to use retentive memory locations, or include constants in the control program to insure a known starting point.
Orderly System Shutdown Ideally, the first level of fault detection is the PLC control program, which can identify machine problems. Certain shutdown sequences should be performed. The types of problems usually found are things such as jammed parts, etc. that do not pose a risk of personal injury or equipment damage. WARNING: The control program must not be the only form of protection for any problems that may result in a risk of personal injury or equipment damage.
Jam Detect
Class 1, Division 2, Zone 2 Approval
Turn off Saw RST RST Retract Arm
This equipment is suitable for use in Class 1, Zone 2, Division 2, groups A, B, C and D or nonhazardous locations only. WARNING: Explosion Hazard! Substitution of components may impair suitability for Class 1, Division 2. Do not disconnect equipment unless power has been switched off or area is known to be non-hazardous. WARNING: Explosion Hazard! Do not disconnect equipment unless power has been switched off or the area is known to be non-hazardous. WARNING: All models used with connector accessories must use R/C (ECBT2) mating plug for all applicable models. All mating plugs shall have suitable ratings for device. WARNING: This equipment is designed for use in Pollution Degree 2 environments (installed within an enclosure rated at least IP54). WARNING: Transient suppression must be provided to prevent the rated voltage from being exceeded by 140%.
Do-more T1H Series PLC User Manual, 1st Edition, Rev. A - T1H-DM-M
Page 127
Chapter 8: Installation and Wiring
Mounting Guidelines Before installing the Terminator system you will need to know the dimensions of the components. The diagrams on the following pages provide the component dimensions to use in defining your enclosure specifications. Remember to leave room for potential expansion. NOTE: If you are using other components in your system, refer to the appropriate manual to determine how those units can affect mounting dimensions.
Dimensions The following diagrams show the, CPU, base controller, power supply and I/O module dimensions. Terminator components mount on 35mm wide DIN rail. CPU 48mm (1.89in)
Base Controller/Power Supply
Base Controller / Power Supply
48mm (1.89in)
48mm 48mm (1.89in)(1.89in) 48 (1.89)
89mm 48mm (3.5in) (1.89in)
83.3mm (3. 8in)
48mm (1.89in)
83.3 (3.28)
9.2 (0.36)
T1H-DM1E
T1H-DM1E
80mm (3.15in)
80mm (3.15in)
80mm 80mm 80 (3.15) (3.15in) (3.15in)
Terminator I/O components mount on 35mm wide DIN rail.
USB PGM PORT
80mm (3.15in)
80mm (3.15in)
80 (3.15)
USB PGM PORT
10.3 (0.41)
10.3 (0.41)
I/O Modules (16 pt.)
(8 pt.)
I/O Modules
89 (3.5)
48 (1.89)
48mm (1.89in)
48mm (1.89in)
89mm (3.5in)
83.3mm (3. 8in)
T1H-DM1E
80 (3.15)
80 (3.15)
80mm 3.15in)
80mm (3.15in)
80mm (3.15in)
80mm (3.15in)
USB PGM PORT
Do-more T1H Series PLC User Manual, 1st Edition, Rev. A - T1H-DM-M
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
80mm (3.15in)
8-5
Page 128
Chapter 8: Installation and Wiring
Panel Mounting and Layout
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
It is important to design your panel properly to help ensure that the Terminator products operate within their environmental and electrical limits. The system installation should comply with all appropriate electrical codes and standards. It is important that the system also conforms to the operating standards for the application to insure proper performance.
1.
OK
K
Airflow
Airflow
Only mount the unit horizontally as shown to provide proper ventilation.
2. you place more than one unit in a cabinet, there should be a minimum of 7.2” (183 mm) between them. 3. a minimum clearance of 2” (50mm) between the units and all sides of the cabinet. There should also be at least 1.2” (30mm) of clearance between the base and any wiring ducts.
Temperature Probe
2” 50mm min T1H-DM1E RUN I/O
ERR
Power Source
TERM STOP
3” 76mm min
7.2” 183mm min
2” 50mm min
3” 76mm min
2” 50mm min
Ground braid copper lugs
Panel Ground Terminal
Panel
Star Washers
8-6
RUN
USB TX RX
USB PGM PORT
Star Washers
Panel or single point ground
Earth Ground
Do-more T1H Series PLC User Manual, 1st Edition, Rev. A - T1H-DM-M
Page 129
Chapter 8: Installation and Wiring 4. must be a minimum of 2” (50mm) clearance between the panel door and the nearest Terminator component.
1 2 3 6. must be a single point ground (i.e. copper bus bar) for all devices in the panel requiring an earth ground return. The single point of ground must be connected to the panel ground 4 termination. The panel ground termination must be connected to earth ground. For this connection you should use 12AWG stranded copper wire as a minimum. Minimum wire sizes, color coding, and general safety practices should comply with appropriate electrical codes and 5 standards for your region. A good common ground reference (earth ground) is essential for proper operation of the Terminator system. There are several methods of providing an adequate common ground reference, including: a) Installing a ground rod as close to the panel as possible. 6 b) Connection to incoming power system ground. 7. evaluate any installation where the ambient temperature may approach the lower or 7 upper limits of the specifications. Place a temperature probe in the panel, close the door and operate the system until the ambient temperature has stabilized. If the ambient temperature is not within the operating specification for the Terminator system, measure points in the panel in 8 consideration for installing a cooling/heating source to provide the ambient temperature to meet the Terminator I/O operating specifications. 9 8. mounting bolts and ground braid termination bolts should be #10 copper bolts or equivalent. Tapped holes instead of nut-bolt arrangements should be used whenever possible. To assure good contact on termination areas impediments such as, paint, other coating or 10 corrosion should be removed in the area of contact. 9. system is designed to be powered by 110/220 VAC or 24VDC normally available throughout an industrial environment. Isolation transformers and noise suppression devices are 11 not normally necessary, but may be helpful in eliminating/reducing suspect power problems. 12 Enclosures Your selection of a proper enclosure is important to ensure safe and proper operation of your Terminator system. Applications of Terminator systems vary and may require additional 13 features. The minimum considerations for enclosures include: 14 • Conformance to electrical standards • Protection from the elements in an industrial environment • Common ground reference A • Maintenance of specified ambient temperature • Access to equipment • Security or restricted access B • Sufficient space for proper installation and maintenance of equipment C D 5. ground terminal on the Terminator power supply must be connected to a single point ground. Use copper stranded wire to achieve a low impedance. Copper eye lugs should be crimped and soldered to the ends of the stranded wire to ensure good surface contact. Remove anodized finishes and use copper lugs and star washers at termination points. A general rule is to achieve a 0.1 ohm of DC resistance between the Terminator I/O slave and the single point ground.
Do-more T1H Series PLC User Manual, 1st Edition, Rev. A - T1H-DM-M
8-7
Page 130
Chapter 8: Installation and Wiring
Environmental Specifications
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 8-8
The following table lists the environmental specifications that apply to the Terminator modules. Be sure to check the specifications of the controller you are using. Also refer to the appropriate I/O module specifications, mentioned in earlier chapters, for the temperature derating curves for the specific module. Specification Storage temperature Ambient operating temperature Ambient humidity* Vibration resistance Shock resistance Noise Immunity Atmosphere
Rating -4°F to 158°F (-20°C to 70°C) 32°F to 131°F (0°C to 55°C) 5%–95% relative humidity (non-condensing) MIL STD 810C, Method 514.2 MIL STD 810C, Method 516.2 NEMA (ICS3-304) Impulse noise 1µs, 1000V FCC class A RFI (144MHz, 430MHz 10W, 10cm) No corrosive gases. The level for the environmental pollution = 2. (UL840)
will operate at low humidity. However, static electricity problems occur much more frequently at lower humidity levels. Make sure you take adequate precautions when you touch the equipment. Consider using ground straps, anti-static floor coverings, etc. if you use the equipment in low humidity environments.
Power The power source must be capable of supplying voltage and current complying with the base power supply specifications. Specification Part Number
AC Power Supply
DC Power Supply
T1K-01AC T1K-01DC 110/220 VAC (85–264 VAC) 12/24 VDC (10.8–26.4 VDC) with Input Voltage Range 50/60 Hz (47–63 Hz) less than 10% ripple 20A 10A Maximum Inrush Current 50VA 20W Maximum Power Voltage Withstand (dielectric) 1 minute @ 1500VAC between primary, secondary, field ground >10Mq at 500VDC Insulation Resistance
Auxiliary 24 VDC Output
20–28 VDC, 10% ripple max. 300mA. A max. of 500mA @ 24VDC can be achieved if the 5VDC power budget None rating of 2000mA is reduced to 1500mA. See power budget section.
Agency Approvals Some applications require agency approvals. Typical agency approvals which your application may require are: • • • •
UL (Underwriters’ Laboratories, Inc.) CSA (Canadian Standards Association) FM (Factory Mutual Research Corporation) CUL (Canadian Underwriters’ Laboratories, Inc.)
Do-more T1H Series PLC User Manual, 1st Edition, Rev. A - T1H-DM-M
Page 131
Chapter 8: Installation and Wiring
Assembling the Components Assembling the I/O Modules and Bases
1
3
INSERT MODULE INTO BASE 1. Pull base arm back to allow space for module to enter base. 2. Align module slides with base track. 3. Press module firmly into base.
2
Mounting the Components on DIN Rail
2
3
1
NOTE: Do not force the module on the DIN rail. Due to slight size variations in different manufacturers’ DIN rail, it may be necessary to first unlatch the locking tab, rotate the module into place, then latch the locking tab.
INSTALL ON DIN RAIL 1. Make sure the locking tab is in the latched position (pushed in). 2. Hook upper tab over upper flange of DIN rail. 3. Tilt the unit toward DIN rail until it snaps securely to DIN rail.
Do-more T1H Series PLC User Manual, 1st Edition, Rev. A - T1H-DM-M
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 8-9
Page 132
Chapter 8: Installation and Wiring
Connecting the Components on the DIN Rail
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 8-10
SLIDE ASSEMBLY INTO POSITION ON THE DIN RAIL
T1H-DM1E TERM
RUN I/O STAT
RUN
STOP
USB TX RX
USB PGM PORT
Slide the module assembly on the DIN rail until the clip arm attaches securely to the adjacent module. NOTE: One power supply is required in the leftmost component position followed by the CPU. Additional power supplies should be added between I/O modules as necessary to meet power budget requirements. Each power supply powers the modules to its right, but is interrupted by the next power supply.
Removing I/O Modules from the Base To remove a module from the base, grip the center of the base arm and rotate outward releasing the module. Lift the module from the base.
T1H-DM1E TERM
RUN I/O STAT
RUN
STOP
USB TX RX
USB PGM PORT
To remove a module assembly from the DIN rail, lift the clip arm up and slide the module assembly away from the adjacent module. Pull the locking tab down (out) and lift the assembly off the DIN rail. WARNING: The T1H Series PLC does not support any Hot-Swap features.