Page 133

Chapter 8: Installation and Wiring

Multiple Power Supplies / Local Expansion Configurations

1 2 3 4 5 6 7 Overview of I/O Expansion Configurations There are several expansion I/O system configurations that can be created by using the local 8 expansion cables. There are some restrictions on where power supplies can be placed in the system when using the T1K-05CBL-RR-1 expansion base cable. 9 10 11 12 13 14 A B C D Multiple Power Supply Configuration

It is possible to have multiple power supplies in a single slave (node) system to meet power budget requirements. One power supply is required in the leftmost component position followed by the CPU. Additional power supplies should be added between I/O modules as necessary to meet power budget requirements. There are some restrictions on where power supplies can be placed in the system when using the T1K-05CBL-RR(-1) expansion base cable. Each power supply powers the modules to its right, but is interrupted by the next power supply. Each slave (node) system can be divided into one row of base I/O plus two rows of local expansion I/O up to a total of 16 I/O modules. Expansion cables are available in two configurations: one that allows 24VDC base power to pass and one that does not (both cables pass the 5VDC base power). The (“-1”) version of the expansion cables pass 24VDC on an isolated wire. Any local expansion DC input modules configured for “internal power” (current sourcing) must either have a power supply preceding it on the same base or have a (“-1”) version cable pass 24VDC from a power supply on the preceding base.

One expansion cable each; T1K-10CBL-1 and T1K-10CBL T1H-DM1E

T1H-DM1E

TERM

RUN

I/O

STAT

One expansion cable each; T1K-05CBL-RR-1 and T1K-05CBL-LL

RUN

STOP

TERM

RUN

USB

I/O

TX

STAT

RX

RUN

STOP

USB TX

RX

USB PGM PORT

USB PGM PORT

I/O Addressing

I/O Addressing

I/O Addressing

I/O Addressing

I/O Addressing

I/O Addressing

Do-more T1H Series PLC User Manual, 1st Edition, Rev. A - T1H-DM-M

8-11

Page 134

Chapter 8: Installation and Wiring One expansion cable each; T1K-10CBL-1 and T1K-05CBL-RR

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 8-12

T1H-DM1E

I/O

T1H-DM1E

TERM

RUN

STAT

RUN

T1K-05CBL-RR-1 Expansion Cable

STOP

TERM

RUN

USB TX

I/O

RX

STAT

RUN

STOP

USB TX RX

USB PGM PORT

USB PGM PORT

I/O Addressing

I/O Addressing

I/O Addressing

I/O Addressing

I/O Addressing

NOTE: When an expansion cable connects the right side of two units together (RR in the cable part number), note that the I/O addressing of the downstream I/O is numbered right to left instead of left to right. However, the CPU detects modules in sequence from the nearest to the furthest and is unaware of the presence of expansion cables and extra power supplies. The display in Do-more Designer will reflect that. Do-more Designer only shows units left to right, in order (see below). The display in Do-more Designer is not intended to represent the physical layout, just the layout as the I/O is addressed.

Physical Layout Slot 0

Slot 1

Slot 2 Slot 3

T1H-DM1E TERM

RUN I/O STAT

RUN

STOP

USB TX RX

USB PGM PORT

I/O Addressing Slot 6

Layout represented in Do-more Designer Slot 5

Slot 4

I/O Addressing Slot 7

Slot 8

Slot 9

I/O Addressing

Do-more T1H Series PLC User Manual, 1st Edition, Rev. A - T1H-DM-M

Page 135

Chapter 8: Installation and Wiring

Example Using T1K-10CBL-1 and T1K-10CBL Expansion Cables

1 2 Power Supply #1 3 Power Supply #2 4 5 6 7 Power Supply #3 8 9 10 11 System shown above: The first power supply powers the CPU and the two I/O modules to its right. The second power supply powers the two modules to its right and the three I/O modules on the first local expansion base. Power Supply #3 powers the three I/O modules to 12 its right on the second local expansion base. This is only an example and the power budget requirements vary depending on the I/O modules used. 13 14 A B C D CPU

T1H-DM1E

TERM

RUN

I/O

STAT

RUN

STOP

USB TX

RX

USB PGM PORT

(a power supply must be the left most component in a system followed by the CPU)

Local Base I/O

I/O Addressing

T1K-10CBL-1

I/O Addressing

1st Local Expansion I/O T1K-10CBL

2nd Local Expansion I/O

I/O Addressing

Do-more T1H Series PLC User Manual, 1st Edition, Rev. A - T1H-DM-M

8-13

Page 136

Chapter 8: Installation and Wiring

Example Using T1K-05CBL-RR-1 and T1K-05CBL-LL Expansion Cables

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

Power Supply #1

(a power supply must be the left most component in a system followed by the CPU)

CPU

T1H-DM1E TERM

RUN I/O STAT

RUN

STOP

USB TX RX

USB PGM PORT

Do not connect a T1K-05CBL-LL to the left side of the local I/O base.

8-14

Local Base I/O I/O Addressing

Power Supply #2

T1K-05CBL-RR-1

1st Local Expansion I/O I/O Addressing A power supply cannot be used on a base that is connected to a system by a T1K-05CBL-RR-1.

T1K-05CBL-LL

2nd Local Expansion I/O I/O Addressing

Power Supply #3

System shown above: The first power supply powers the CPU and the two I/O modules to its right. The second power supply powers the two modules to its right and the three I/O modules on the first local expansion base. When a T1K-05CBL-RR-1 is used, the expansion I/O assignments are from right to left (reversed). A power supply cannot be used on a base that is connected to a system by a T1K-05CBL-RR-1. Power Supply #3 powers the three I/O modules to its right on the second local expansion base. This is only an example and the power budget requirements vary depending on the I/O modules used.

Do-more T1H Series PLC User Manual, 1st Edition, Rev. A - T1H-DM-M

Page 137

Chapter 8: Installation and Wiring

Example Using T1K-10CBL and T1K-05CBL-RR-1 Expansion Cables

1 Power Supply #1 2 3 Power Supply #2 4 5 6 7 Power Supply #3 8 9 10 11 System shown above: The first power supply powers the CPU and the two I/O modules 12 to its right. The second power supply powers the two modules to its right. Power Supply #3 powers the three I/O modules to its right on the first local expansion base and the three I/O modules on the second local expansion base. When a T1K-05CBL-RR-1 is used, the 13 expansion I/O assignments are from right to left (reversed). A power supply cannot be used on a base that is connected to a system by a T1K-05CBL-RR-1. This is only an example and 14 the power budget requirements vary depending on the I/O modules used. A B C D CPU

T1H-DM1E

(a power supply must be the left most component in a system followed by the CPU)

TERM

RUN

I/O

STAT

RUN

STOP

USB TX

RX

USB PGM PORT

Local Base I/O

I/O Addressing

T1K-10CBL

1st Local Expansion I/O

I/O Addressing

T1K-05CBL-RR-1

A power supply cannot be used on a base that is connected to a system by a T1K-05CBL-RR-1.

2nd Local Expansion I/O

I/O Addressing

Do-more T1H Series PLC User Manual, 1st Edition, Rev. A - T1H-DM-M

8-15

Page 138

Chapter 8: Installation and Wiring

Example Using T1K-05CBL-RR-1 Expansion Cables

1 2 3 4 Power Supply #1 Power Supply #2 5 6 7 8 9 10 System shown above: The first power supply powers the CPU and the two I/O modules to its right. The second power supply powers the two modules to its right and the five I/O 11 modules on the first local expansion base. When a T1K-05CBL-RR-1 is used, the expansion I/O assignments are from right to left (reversed). A power supply cannot be used on a base 12 that is connected to a system by a T1K-05CBL-RR-1. This is only an example and the power budget requirements vary depending on the I/O modules used. 13 14 A B C D CPU

T1H-DM1E

TERM

RUN

I/O

STAT

RUN

STOP

USB TX

RX

USB PGM PORT

(a power supply must be the left most component in a system followed by the CPU)

Local Base I/O

I/O Addressing

T1K-05CBL-RR-1

I/O Addressing

8-16

1st Local Expansion I/O

A power supply cannot be used on a base that is connected to a system by a T1K-05CBL-RR-1.

Do-more T1H Series PLC User Manual, 1st Edition, Rev. A - T1H-DM-M

Page 139

Chapter 8: Installation and Wiring

T1K-10CBL, T1K-10CBL-1 Expansion Cable Specifications Specifications Specification

T1K-10CBL

Cable Length Cable Diameter Shielding Temperature Range Jacket Material

Auxiliary 24VDC Cable

Cable Diameter Insulation Voltage

T1K-10CBL-1

100cm (3.28 ft.) 8.5 mm None -25!C to 80!C (-13!F to 176!F) PVC N/A 2 cables used: 1.42 mm each N/A 2000VAC / 1 minute

T1K-10CBL(-1)

T1K-10CBL-1 has 24 VDC cable attached here

Cable Length: 100cm Cable Diameter: 8.5mm

T1K-5CBL-LL(-1) Expansion Cable Specifications Specifications Specification

T1K-05CBL-LL

T1K-05CBL-1-LL-1

Cable Description

Left-to-left Side Expansion Cable

Cable Length Cable Diameter Shielding Temperature Range Jacket Material

50cm (1.64 ft.) 8.5 mm None -25!C to 80!C (-13!F to 176!F) PVC Two 1.42 mm cables N/A used in a 6mm sheath N/A 2000VAC / 1 minute

Auxiliary 24VDC Cable

Cable Diameter Insulation Voltage

Do-more T1H Series PLC User Manual, 1st Edition, Rev. A - T1H-DM-M

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 8-17

Page 140

Chapter 8: Installation and Wiring

T1K-5CBL-RR(-1) Expansion Cable Specifications

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 8-18

Specifications Specification

T1K-05CBL-RR

Cable Description Cable Length Cable Diameter Shielding Temperature Range Jacket Material

Auxiliary 24VDC Cable

Cable Diameter Insulation Voltage

T1K-5CBL-LL(-1)

T1K-05CBL-LL-1 has 24 VDC cable attached here

Cable Length: 50cm

T1K-05CBL-1-RR-1

Right-to-right Side Expansion Cable 50cm (1.64 ft.) 8.5 mm None -25!C to 80!C (-13!F to 176!F) PVC Two 1.42 mm cables used in a 6mm sheath 2000VAC / 1 minute

T1K-5CBL-RR(-1)

Cable Length: 50cm

T1K-05CBL-RR-1 has 24 VDC cable attached here

Do-more T1H Series PLC User Manual, 1st Edition, Rev. A - T1H-DM-M

Page 141

Chapter 8: Installation and Wiring

Wiring Guidelines

1 The diagram below shows the terminal connections located on the Terminator AC and DC power supplies. The table below shows the wire size and recommended torque for the power 2 supply screw terminals. 3 4 5 6 7 8 9 110/220 VAC Terminal Strip 12/24 VDC Terminal Strip 10 110/220 VAC Terminal Strip 12/24 VDC Terminal Strip 11 12 13 14 A B Power Supply T1K-01AC T1K-01DC Wire Size C Recommended Torque D

Power Wiring

Solid: 24–12 AWG Stranded: 24–12 AWG 4.43–5.31 lb·in (0.5–0.6 N·m)

Solid: 24–12 AWG Stranded: 24–12 AWG 4.43–5.31 lb·in (0.5–0.6 N·m)

Do-more T1H Series PLC User Manual, 1st Edition, Rev. A - T1H-DM-M

8-19

Page 142

Chapter 8: Installation and Wiring

Wiring the I/O Module Bases

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 8-20

There are two types of terminal bases for the Terminator I/O modules: screw clamp and spring clamp connectors. The recessed screw heads help minimize the risk of someone accidentally touching active wiring. WARNING: For some modules, field device power may still be present on the terminal block even though the Terminator I/O system power is turned off. To minimize the risk of electrical shock, check all field device power before you remove a wire.

Terminal Type

Screw Type

Spring Clamp

Recommended Torque

1.77–3.54 lb·in (0.2–0.4 N·m)

N/A

Recommended Screwdriver Blade Size Wire Gauge

Push in on clamp using screwdriver blade size: (0.016 x 0.079 to 0.032 x 0.16) in. (0.4 x 2 to 0 .8 x 4) mm Solid conductor: 24–14 AWG Solid conductor: 24–12 AWG Stranded conductor: 24–14 AWG Stranded conductor: 24–12 AWG (Twist stranded conductors before inserting into gate) 0.02 in. x 0.125 in. (0.5 mm x 3mm)

Selecting Internal 24 VDC Power Supply The DC input field devices can be powered from the integrated 24VDC power supply from the power supply bus. The T1K-08ND3 and T1K-16ND3 DC input modules have jumpers for selecting internal 24VDC power supply available for 2 and 3-wire field devices. The analog I/O and DC output modules do not have direct access to the internal bussed 24VDC. Jumpers located under top cover of T1K-08ND3 and T1K-16ND3 Position jumper to set the module to sink or source current.

Position jumper to set the module to provide internally bussed 24VDC or if external power is to be supplied.

Do-more T1H Series PLC User Manual, 1st Edition, Rev. A - T1H-DM-M