Page 133
Chapter 8: Installation and Wiring
Multiple Power Supplies / Local Expansion Configurations
1 2 3 4 5 6 7 Overview of I/O Expansion Configurations There are several expansion I/O system configurations that can be created by using the local 8 expansion cables. There are some restrictions on where power supplies can be placed in the system when using the T1K-05CBL-RR-1 expansion base cable. 9 10 11 12 13 14 A B C D Multiple Power Supply Configuration
It is possible to have multiple power supplies in a single slave (node) system to meet power budget requirements. One power supply is required in the leftmost component position followed by the CPU. Additional power supplies should be added between I/O modules as necessary to meet power budget requirements. There are some restrictions on where power supplies can be placed in the system when using the T1K-05CBL-RR(-1) expansion base cable. Each power supply powers the modules to its right, but is interrupted by the next power supply. Each slave (node) system can be divided into one row of base I/O plus two rows of local expansion I/O up to a total of 16 I/O modules. Expansion cables are available in two configurations: one that allows 24VDC base power to pass and one that does not (both cables pass the 5VDC base power). The (“-1”) version of the expansion cables pass 24VDC on an isolated wire. Any local expansion DC input modules configured for “internal power” (current sourcing) must either have a power supply preceding it on the same base or have a (“-1”) version cable pass 24VDC from a power supply on the preceding base.
One expansion cable each; T1K-10CBL-1 and T1K-10CBL T1H-DM1E
T1H-DM1E
TERM
RUN
I/O
STAT
One expansion cable each; T1K-05CBL-RR-1 and T1K-05CBL-LL
RUN
STOP
TERM
RUN
USB
I/O
TX
STAT
RX
RUN
STOP
USB TX
RX
USB PGM PORT
USB PGM PORT
I/O Addressing
I/O Addressing
I/O Addressing
I/O Addressing
I/O Addressing
I/O Addressing
Do-more T1H Series PLC User Manual, 1st Edition, Rev. A - T1H-DM-M
8-11
Page 134
Chapter 8: Installation and Wiring One expansion cable each; T1K-10CBL-1 and T1K-05CBL-RR
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 8-12
T1H-DM1E
I/O
T1H-DM1E
TERM
RUN
STAT
RUN
T1K-05CBL-RR-1 Expansion Cable
STOP
TERM
RUN
USB TX
I/O
RX
STAT
RUN
STOP
USB TX RX
USB PGM PORT
USB PGM PORT
I/O Addressing
I/O Addressing
I/O Addressing
I/O Addressing
I/O Addressing
NOTE: When an expansion cable connects the right side of two units together (RR in the cable part number), note that the I/O addressing of the downstream I/O is numbered right to left instead of left to right. However, the CPU detects modules in sequence from the nearest to the furthest and is unaware of the presence of expansion cables and extra power supplies. The display in Do-more Designer will reflect that. Do-more Designer only shows units left to right, in order (see below). The display in Do-more Designer is not intended to represent the physical layout, just the layout as the I/O is addressed.
Physical Layout Slot 0
Slot 1
Slot 2 Slot 3
T1H-DM1E TERM
RUN I/O STAT
RUN
STOP
USB TX RX
USB PGM PORT
I/O Addressing Slot 6
Layout represented in Do-more Designer Slot 5
Slot 4
I/O Addressing Slot 7
Slot 8
Slot 9
I/O Addressing
Do-more T1H Series PLC User Manual, 1st Edition, Rev. A - T1H-DM-M
Page 135
Chapter 8: Installation and Wiring
Example Using T1K-10CBL-1 and T1K-10CBL Expansion Cables
1 2 Power Supply #1 3 Power Supply #2 4 5 6 7 Power Supply #3 8 9 10 11 System shown above: The first power supply powers the CPU and the two I/O modules to its right. The second power supply powers the two modules to its right and the three I/O modules on the first local expansion base. Power Supply #3 powers the three I/O modules to 12 its right on the second local expansion base. This is only an example and the power budget requirements vary depending on the I/O modules used. 13 14 A B C D CPU
T1H-DM1E
TERM
RUN
I/O
STAT
RUN
STOP
USB TX
RX
USB PGM PORT
(a power supply must be the left most component in a system followed by the CPU)
Local Base I/O
I/O Addressing
T1K-10CBL-1
I/O Addressing
1st Local Expansion I/O T1K-10CBL
2nd Local Expansion I/O
I/O Addressing
Do-more T1H Series PLC User Manual, 1st Edition, Rev. A - T1H-DM-M
8-13
Page 136
Chapter 8: Installation and Wiring
Example Using T1K-05CBL-RR-1 and T1K-05CBL-LL Expansion Cables
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
Power Supply #1
(a power supply must be the left most component in a system followed by the CPU)
CPU
T1H-DM1E TERM
RUN I/O STAT
RUN
STOP
USB TX RX
USB PGM PORT
Do not connect a T1K-05CBL-LL to the left side of the local I/O base.
8-14
Local Base I/O I/O Addressing
Power Supply #2
T1K-05CBL-RR-1
1st Local Expansion I/O I/O Addressing A power supply cannot be used on a base that is connected to a system by a T1K-05CBL-RR-1.
T1K-05CBL-LL
2nd Local Expansion I/O I/O Addressing
Power Supply #3
System shown above: The first power supply powers the CPU and the two I/O modules to its right. The second power supply powers the two modules to its right and the three I/O modules on the first local expansion base. When a T1K-05CBL-RR-1 is used, the expansion I/O assignments are from right to left (reversed). A power supply cannot be used on a base that is connected to a system by a T1K-05CBL-RR-1. Power Supply #3 powers the three I/O modules to its right on the second local expansion base. This is only an example and the power budget requirements vary depending on the I/O modules used.
Do-more T1H Series PLC User Manual, 1st Edition, Rev. A - T1H-DM-M
Page 137
Chapter 8: Installation and Wiring
Example Using T1K-10CBL and T1K-05CBL-RR-1 Expansion Cables
1 Power Supply #1 2 3 Power Supply #2 4 5 6 7 Power Supply #3 8 9 10 11 System shown above: The first power supply powers the CPU and the two I/O modules 12 to its right. The second power supply powers the two modules to its right. Power Supply #3 powers the three I/O modules to its right on the first local expansion base and the three I/O modules on the second local expansion base. When a T1K-05CBL-RR-1 is used, the 13 expansion I/O assignments are from right to left (reversed). A power supply cannot be used on a base that is connected to a system by a T1K-05CBL-RR-1. This is only an example and 14 the power budget requirements vary depending on the I/O modules used. A B C D CPU
T1H-DM1E
(a power supply must be the left most component in a system followed by the CPU)
TERM
RUN
I/O
STAT
RUN
STOP
USB TX
RX
USB PGM PORT
Local Base I/O
I/O Addressing
T1K-10CBL
1st Local Expansion I/O
I/O Addressing
T1K-05CBL-RR-1
A power supply cannot be used on a base that is connected to a system by a T1K-05CBL-RR-1.
2nd Local Expansion I/O
I/O Addressing
Do-more T1H Series PLC User Manual, 1st Edition, Rev. A - T1H-DM-M
8-15
Page 138
Chapter 8: Installation and Wiring
Example Using T1K-05CBL-RR-1 Expansion Cables
1 2 3 4 Power Supply #1 Power Supply #2 5 6 7 8 9 10 System shown above: The first power supply powers the CPU and the two I/O modules to its right. The second power supply powers the two modules to its right and the five I/O 11 modules on the first local expansion base. When a T1K-05CBL-RR-1 is used, the expansion I/O assignments are from right to left (reversed). A power supply cannot be used on a base 12 that is connected to a system by a T1K-05CBL-RR-1. This is only an example and the power budget requirements vary depending on the I/O modules used. 13 14 A B C D CPU
T1H-DM1E
TERM
RUN
I/O
STAT
RUN
STOP
USB TX
RX
USB PGM PORT
(a power supply must be the left most component in a system followed by the CPU)
Local Base I/O
I/O Addressing
T1K-05CBL-RR-1
I/O Addressing
8-16
1st Local Expansion I/O
A power supply cannot be used on a base that is connected to a system by a T1K-05CBL-RR-1.
Do-more T1H Series PLC User Manual, 1st Edition, Rev. A - T1H-DM-M
Page 139
Chapter 8: Installation and Wiring
T1K-10CBL, T1K-10CBL-1 Expansion Cable Specifications Specifications Specification
T1K-10CBL
Cable Length Cable Diameter Shielding Temperature Range Jacket Material
Auxiliary 24VDC Cable
Cable Diameter Insulation Voltage
T1K-10CBL-1
100cm (3.28 ft.) 8.5 mm None -25!C to 80!C (-13!F to 176!F) PVC N/A 2 cables used: 1.42 mm each N/A 2000VAC / 1 minute
T1K-10CBL(-1)
T1K-10CBL-1 has 24 VDC cable attached here
Cable Length: 100cm Cable Diameter: 8.5mm
T1K-5CBL-LL(-1) Expansion Cable Specifications Specifications Specification
T1K-05CBL-LL
T1K-05CBL-1-LL-1
Cable Description
Left-to-left Side Expansion Cable
Cable Length Cable Diameter Shielding Temperature Range Jacket Material
50cm (1.64 ft.) 8.5 mm None -25!C to 80!C (-13!F to 176!F) PVC Two 1.42 mm cables N/A used in a 6mm sheath N/A 2000VAC / 1 minute
Auxiliary 24VDC Cable
Cable Diameter Insulation Voltage
Do-more T1H Series PLC User Manual, 1st Edition, Rev. A - T1H-DM-M
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 8-17
Page 140
Chapter 8: Installation and Wiring
T1K-5CBL-RR(-1) Expansion Cable Specifications
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 8-18
Specifications Specification
T1K-05CBL-RR
Cable Description Cable Length Cable Diameter Shielding Temperature Range Jacket Material
Auxiliary 24VDC Cable
Cable Diameter Insulation Voltage
T1K-5CBL-LL(-1)
T1K-05CBL-LL-1 has 24 VDC cable attached here
Cable Length: 50cm
T1K-05CBL-1-RR-1
Right-to-right Side Expansion Cable 50cm (1.64 ft.) 8.5 mm None -25!C to 80!C (-13!F to 176!F) PVC Two 1.42 mm cables used in a 6mm sheath 2000VAC / 1 minute
T1K-5CBL-RR(-1)
Cable Length: 50cm
T1K-05CBL-RR-1 has 24 VDC cable attached here
Do-more T1H Series PLC User Manual, 1st Edition, Rev. A - T1H-DM-M
Page 141
Chapter 8: Installation and Wiring
Wiring Guidelines
1 The diagram below shows the terminal connections located on the Terminator AC and DC power supplies. The table below shows the wire size and recommended torque for the power 2 supply screw terminals. 3 4 5 6 7 8 9 110/220 VAC Terminal Strip 12/24 VDC Terminal Strip 10 110/220 VAC Terminal Strip 12/24 VDC Terminal Strip 11 12 13 14 A B Power Supply T1K-01AC T1K-01DC Wire Size C Recommended Torque D
Power Wiring
Solid: 24–12 AWG Stranded: 24–12 AWG 4.43–5.31 lb·in (0.5–0.6 N·m)
Solid: 24–12 AWG Stranded: 24–12 AWG 4.43–5.31 lb·in (0.5–0.6 N·m)
Do-more T1H Series PLC User Manual, 1st Edition, Rev. A - T1H-DM-M
8-19
Page 142
Chapter 8: Installation and Wiring
Wiring the I/O Module Bases
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 8-20
There are two types of terminal bases for the Terminator I/O modules: screw clamp and spring clamp connectors. The recessed screw heads help minimize the risk of someone accidentally touching active wiring. WARNING: For some modules, field device power may still be present on the terminal block even though the Terminator I/O system power is turned off. To minimize the risk of electrical shock, check all field device power before you remove a wire.
Terminal Type
Screw Type
Spring Clamp
Recommended Torque
1.77–3.54 lb·in (0.2–0.4 N·m)
N/A
Recommended Screwdriver Blade Size Wire Gauge
Push in on clamp using screwdriver blade size: (0.016 x 0.079 to 0.032 x 0.16) in. (0.4 x 2 to 0 .8 x 4) mm Solid conductor: 24–14 AWG Solid conductor: 24–12 AWG Stranded conductor: 24–14 AWG Stranded conductor: 24–12 AWG (Twist stranded conductors before inserting into gate) 0.02 in. x 0.125 in. (0.5 mm x 3mm)
Selecting Internal 24 VDC Power Supply The DC input field devices can be powered from the integrated 24VDC power supply from the power supply bus. The T1K-08ND3 and T1K-16ND3 DC input modules have jumpers for selecting internal 24VDC power supply available for 2 and 3-wire field devices. The analog I/O and DC output modules do not have direct access to the internal bussed 24VDC. Jumpers located under top cover of T1K-08ND3 and T1K-16ND3 Position jumper to set the module to sink or source current.
Position jumper to set the module to provide internally bussed 24VDC or if external power is to be supplied.
Do-more T1H Series PLC User Manual, 1st Edition, Rev. A - T1H-DM-M