Page 143
Chapter 8: Installation and Wiring
Jumper Selection
External Power
Equivalent Input Circuit MODULE
Sink Module External Power
SOURCE
INT
SINK
EXT
MODULE
Source Module External Power
SOURCE
INT
SINK
EXT
Internal Power
MODULE
SINK
MODULE
INT
SOURCE
EXT
SINK
SOURCE
V0
INT EXT
V0 V1
V1 Source Module Internal Power
Internal Module Circuitry
Sink Module Internal Power
Internal Module Circuitry
Using Internal 24VDC Base Power The diagram below shows DC input devices using internally bussed 24VDC for power. If the module is set to “sink” current, +24VDC power is supplied to the input module base “COM” terminals and 0VDC is supplied to the module base “V” terminals. If the module is set to “source” current, +24VDC is supplied to the input module base ”V” terminals and 0VDC is supplied to the module base “COM” terminals.
Using Internally Bussed 24VDC (T1K-08ND3, T1K-16ND3 only) T1H-DM1E RUN
RUN
USB
I/O
TERM STOP
TX
ERR
RX
USB PGM PORT
2 and 3-wire input field devices
Do-more T1H Series PLC User Manual, 1st Edition, Rev. A - T1H-DM-M
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
8-21
Page 144
Chapter 8: Installation and Wiring
External 24VDC Wiring Options
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 8-22
DC output and analog I/O modules do not have direct access to the internally bussed 24VDC. External user supplied 24VDC power, or auxiliary 24VDC from the T1K-01AC, can be applied directly to one end of the DC I/O module base terminal (V and COM) rows and jumpered across each base as needed in a system. This creates a “bus” (row) of 24VDC and a bus of 0VDC power. Be sure not to exceed the supply’s power budget. WARNING: The T1H Series PLC does not support any Hot-Swap features.
Using T1K-01AC for External 24VDC Power T1H-DM1E RUN
RUN
TERM
USB
I/O
STOP
TX
ERR
RX
USB PGM PORT
Use T1K-01AC external 24VDC to create a power bus for DC modules.
Place wire jumpers from one DC I/O module base to another as necessary to continue the external 24VDC power bus.
Using an External 24VDC Power Supply T1H-DM1E RUN
RUN
USB
I/O
TERM STOP
TX
ERR
RX
USB PGM PORT
Use an external 24VDC power supply to create a power bus for the DC modules.
Place wire jumpers from one DC I/O module base to another as necessary to continue the external 24VDC power bus.
Do-more T1H Series PLC User Manual, 1st Edition, Rev. A - T1H-DM-M
Page 145
Chapter 8: Installation and Wiring
I/O Wiring Checklist Use the following guidelines when wiring the base terminals in your system.
1 2. Always use a continuous length of wire, do not combine wires to attain a needed length. 2 3. Use the shortest possible wire length. 3 4. Use wire trays for routing where possible. 5. Avoid running wires near high-energy wiring. 4 6. Avoid running input wiring close to output wiring where possible. 7. To minimize voltage drops when wires must run a long distance, consider using multiple wires for the return line. 5 8. Avoid running DC wiring in close proximity to AC wiring where possible. 9. Avoid creating sharp bends in the wires. 6 10. To reduce the risk of having a module with a blown fuse, we suggest you add external fuses to your I/O wiring. A fast blow fuse, with a lower current rating than the I/O module fuse can be 7 added to each common, or a fuse with a rating of slightly less than the maximum current per output point can be added to each output. 8 Output Module Fusing All Terminator I/O discrete output modules have internal user–replaceable fuses. For fuse 9 specifications and part numbers for a specific output module, refer to the output module specifications in Chapter 5. Be sure to remove system power before attempting to remove the I/O module from its base. 10 Fuses located under top cover of output modules 11 12 13 Replaceable Fuses 14 A B C D 1. is a limit to the size of wire the terminals can accept. The table on page 8-20 lists the suggested nominal AWG for each terminal base type.
Note: A blown fuse indicator illuminates only when a fuse is blown and associated output point is turned ON by the program.
Do-more T1H Series PLC User Manual, 1st Edition, Rev. A - T1H-DM-M
8-23
Page 146
Chapter 8: Installation and Wiring
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
I/O Wiring Strategies
8-24
Terminator System Isolation Boundaries The Terminator system is very flexible and will work in many different wiring configurations. By studying this section before actual installation, you can probably find the best wiring strategy for your application. This will help to lower system cost, wiring errors, and avoid safety problems. Terminator system circuitry is divided into three main regions separated by isolation boundaries, shown in the drawing below. Electrical isolation provides safety, so that a fault in one area does not damage another. A transformer in the power supply provides magnetic isolation between the primary and secondary sides. Opto-couplers provide optical isolation in Input and Output circuits. This isolates logic circuitry from the field side, where factory machinery connects. Note the discrete inputs are isolated from the discrete outputs, because each is isolated from the logic side. Isolation boundaries protect the operator interface (and the operator) from power input faults or field wiring faults. When wiring a Terminator I/O system, it is extremely important to avoid making external connections that connect logic side circuits to any other. Primary Side
Secondary, or Logic side
Do-more T1H PLC Main Power Supply
Power Input
Isolation Boundary
Slave CPU
Field Side
(backplane)
Input Module
Inputs
(backplane)
Output Module
Outputs
Programming Device, Operator Interface, or Network
Isolation Boundary
The next figure shows the physical layout of a Terminator system, as viewed from the front. In addition to the basic circuits covered above, AC-powered bases include an auxiliary +24VDC power supply with its own isolation boundary. Since the supply output is isolated from the other three circuits, it can power input and/or output circuits! Primary Side Power Input
+24 VDC Out
Main Power Supply
Auxiliary +24 VDC Supply
Do-more T1H PLC System Slave Internal
CPU
Secondary, or Logic side Backplane
Comm.
Input Module
Output Module
Operator Interface
Inputs Commons
Outputs Commons
Field Side
Supply for Output Circuit
Do-more T1H Series PLC User Manual, 1st Edition, Rev. A - T1H-DM-M
Page 147
Chapter 8: Installation and Wiring In some cases, using the built-in auxiliary +24VDC supply can result in a cost savings for your control system. It can power combined loads up to 500mA if power budget allows. Be careful not to exceed the current rating of the supply. If you are the system designer for your application, you may be able to select and design in field devices which can use the +24VDC auxiliary supply.
1 2 Powering I/O Circuits with the Auxiliary Supply All AC power supplies feature an internal auxiliary supply. If input devices AND output 3 loads need +24VDC power, the auxiliary supply may be able to power both circuits as shown in the following diagram. 4 AC Power 5 Power Input 6 Auxiliary Input Module Output Module +24 VDC 7 Inputs Com. Outputs Com. Supply 8 – + Loads 9 10 DC-powered units are designed for application environments in which low-voltage DC 11 power is more readily available than AC. These include a wide range of battery-powered applications, such as remotely-located control, in vehicles, portable machines, etc. For this type of application, all input devices and output loads typically use the same DC power 12 source. Typical wiring for DC-powered applications is shown in the following diagram. 13 + 14 – A Input Module Output Module B Inputs Com. Outputs Com. C D +
DC Power
–
Power Input
Loads
Do-more T1H Series PLC User Manual, 1st Edition, Rev. A - T1H-DM-M
8-25
Page 148
Chapter 8: Installation and Wiring
Powering I/O Circuits Using Separate Supplies
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 8-26
In most applications it will be necessary to power the input devices from one power source, and to power output loads from another source. Loads often require high-energy AC power, while input sensors use low-energy DC. If a machine operator is likely to come in close contact with input wiring, then safety reasons also require isolation from high-energy output circuits. It is most convenient if the loads can use the same power source as the Terminator I/O system, and the input sensors can use the auxiliary supply, as shown to the left in the figure below. If the loads cannot be powered from the system supply, then a separate supply must be used as shown to the right in the figure below. AC Power
AC Power
Power Input
Auxiliary +24 VDC Supply
+
Power Input
Input Module
Output Module
Inputs
Outputs Com.
Com.
–
Auxiliary +24 VDC Supply
+
Input Module
Output Module
Inputs
Outputs Com.
Com.
–
Loads
Loads
Load Supply
Some applications will use the external power source to also power the input circuit. This typically occurs on DC-powered systems, as shown in the drawing below to the left. The inputs share the system power source supply, while the outputs have their own separate supply. A worse-case scenario, from a cost and complexity view-point, is an application which requires separate power sources for the Terminator I/O system, input devices, and output loads. The example wiring diagram below on the right shows how this can work, but also the auxiliary supply output is an unused resource. You will want to avoid this situation if possible. +
+
–
–
DC Power
AC Power Power Input
Power Input
Input Module
Output Module
Inputs
Outputs Com.
Com.
Auxiliary +24 VDC Supply
+ Loads
Load Supply
Input Module
Output Module
Inputs
Com.
Outputs Com.
Input Supply
Loads
–
Do-more T1H Series PLC User Manual, 1st Edition, Rev. A - T1H-DM-M
Load Supply
Page 149
Chapter 8: Installation and Wiring
Sinking / Sourcing Concepts Before going further in the study of wiring strategies, you must have a solid understanding of “sinking” and “sourcing” concepts. Use of these terms occurs frequently in input or output circuit discussions. It is the goal of this section to make these concepts easy to understand, further ensuring your success in installation. First the following short definitions are provided, followed by practical applications. Sinking = provides a path to supply ground (-) Sourcing = provides a path to supply source (+) First you will notice these are only associated with DC circuits and not AC, because of the reference to (+) and (-) polarities. Therefore, sinking and sourcing terminology only applies to DC input and output circuits. Input and output points that are sinking or sourcing only can conduct current in only one direction. This means it is possible to connect the external supply and field device to the I/O point with current trying to flow in the wrong direction, and the circuit will not operate. However, you can successfully connect the supply and field device every time by understanding “sourcing” and “sinking”. For example, the figure to the right depicts a “sinking” input. To properly connect the external supply, you will have to connect it so the input provides a path to ground (-). Start at the Terminator I/O system input terminal, Input follow through the input sensing circuit, exit at (sinking) the common terminal, and connect the supply + (-) to the common terminal. By adding the Input Sensing switch, between the supply (+) and the input, the – circuit has been completed. Current flows in the Common direction of the arrow when the switch is closed. By applying the circuit principle above to the four possible combinations of input/output sinking/ sourcing types as shown below. The I/O module specifications at the end of this chapter list the input or output type. Sinking Input
Sinking Output Input
+ –
Common
Output Input Sensing
Sourcing Input
Output Switch
–
Input
+ –
Common
Sourcing Output
Common +
Load
Common Input Sensing
Output Switch
+ Output
Load
–
Do-more T1H Series PLC User Manual, 1st Edition, Rev. A - T1H-DM-M
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
8-27
Page 150
Chapter 8: Installation and Wiring
I/O “Common” Terminal Concepts
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
In order for an I/O circuit to operate, current must enter at one terminal and exit at another. Therefore, at least two terminals are associated with every I/O point. In the figure to the right, the Input or Output terminal is the main path for the current. One additional terminal must provide the return path to the power supply.. If there was unlimited space and budget for I/O terminals, every I/O point could have two dedicated terminals as the figure above shows. However, providing this level of flexibility is not practical or even necessary for most applications. So, most Input or Output points are in groups which share the return path (called commons). The figure to the right shows a group (or bank) of 4 input points which share a common return path. In this way, the four inputs require only five terminals instead of eight.
Field Device
Main Path (I/O Point)
+ – Return Path
Input 1
Input Sensing
Input 2 Input 3 Input 4 + –
Common
NOTE: In the circuit above, the current in the common path is 4 times any channel’s input current when all inputs are energized. This is especially important in output circuits, where heavier gauge wire is sometimes necessary on commons.
Most Terminator I/O input and output modules group their I/O points into banks that share a common return path. The best indication of I/O common grouping is on the wiring label, such as the one shown to the right. The miniature schematic shows two banks of circuits with four output points in each. The common terminal for each is labeled COM 0 and COM 1, respectively. In this wiring label example, the positive terminal of a DC supply connects to the common terminals. Some symbols you will see on the wiring labels, and their meanings are: AC supply
DC supply –
Input Switch
AC or DC supply
+
Output Load L
8-28
I/O Circuit
Do-more T1H Series PLC User Manual, 1st Edition, Rev. A - T1H-DM-M
Page 151
Chapter 8: Installation and Wiring
Connecting DC I/O to Solid State Field Devices In the previous section on Sourcing and Sinking concepts, the DC I/O circuits were explained to only allow current to flow one way. This is also true for many of the field devices which have solid-state (transistor) interfaces. In other words, field devices can also be sourcing or sinking. When connecting two devices in a series DC circuit, one must be wired as sourcing and the other as sinking:
1 2 3 Solid State Input Sensors Terminator I/O DC input modules are flexible because they detect current flow in either direction, so they can be wired as either sourcing or sinking. In the following circuit, a field 4 device has an open-collector NPN transistor output. It sinks current from the input point, which sources current. The power supply can be the +24V auxiliary supply or another supply 5 (+12VDC or +24VDC), as long as the input specifications are met. 6 7 8 In the next circuit, a field device has an open-emitter PNP transistor output. It sources current to the input point, which sinks the current back to ground. Since the field device is sourcing 9 current, no additional power supply is required. 10 11 12 Solid State Output Loads 13 Sometimes an application requires connecting an output point to a solid state input on a device. This type of connection is usually made to carry a low-level control signal, not to send DC 14 power to an actuator. Several of the Terminator I/O DC output modules are the sinking type. This means that each DC output provides a path to ground when it is energized. In the following circuit, the output A point sinks current to the output common when energized. It is connected to a sourcing input of a field device input. B C D Field Device
Do-more T1H PLC System DC Input Input (sourcing)
Output (sinking)
Supply
Ground
–
+
Common
Field Device +V
Do-more T1H PLC System DC Input Input
(sinking)
Output (sourcing) Ground
Common
Do-more T1H PLC System DC Sinking Output Power +DC pwr Output
(sinking)
+
Common
–
Field Device
+V
Input (sourcing) 10–30 VDC Ground
Do-more T1H Series PLC User Manual, 1st Edition, Rev. A - T1H-DM-M
8-29
Page 152
Chapter 8: Installation and Wiring
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 8-30
In the next example a sinking DC output point is connected to the sinking input of a field device. This is a little tricky, because both the Terminator I/O system output and field device input are sinking type. Since the circuit must have one sourcing and one sinking device, a sourcing capability needs to be added to the Terminator I/O system output by using a pull-up resistor. In the circuit below, an Rpull-up is connected from the output to the DC power input circuit. Do-more T1H PLC System DC Output Power +DC pwr Field Device
R pull-up
(sourcing)
(sinking)
Output
Input (sinking)
+ Common
Supply
–
R input
Ground
NOTE 1: DO NOT attempt to drive a heavy load (>25mA) with this pull-up method. NOTE 2: Using the pull-up resistor to implement a sourcing output has the effect of inverting the output point logic. In other words, the field device input is energized when the Terminator I/O system output is OFF, from a ladder logic point-of-view. Your ladder program must comprehend this and generate an inverted output. Or, you may choose to cancel the effect of the inversion elsewhere, such as in the field device.
It is important to choose the correct value of R pull-up. In order to do so, you need to know the nominal input current to the field device (I input) when the input is energized. If this value is not known, it can be calculated as shown (a typical value is 15 mA). Then use I input and the voltage of the external supply to compute Rpull-up. Then calculate the power Ppull-up (in watts), in order to size Rpull-up properly. V input (turn–on) I input = R input 2 V supply V supply – 0.7 R pull-up = P pull-up = – R input R pullup I input Of course, the easiest way to drive a sinking input field device as shown below is to use a DC sourcing output module. The Darlington NPN stage will have about 1.5 V ON-state saturation, but this is not a problem with low-current solid-state loads. Do-more T1H PLC DC Sourcing Output +DC pwr
Common Field Device Output (sourcing) Supply
+
Input (sinking)
–
Ground
R input
Do-more T1H Series PLC User Manual, 1st Edition, Rev. A - T1H-DM-M