Chapter 8: Installation and Wiring
Relay Output Guidelines Several output modules in the Terminator I/O family feature relay outputs: T1K-08TR, T1K-16TR, and T1K-08TRS. Relays are best for the following applications:
1 • Loads that require higher currents than the solid-state outputs can deliver 2 • Cost-sensitive applications • Some output channels need isolation from other outputs (such as when some loads require different voltages than other loads) 3 Some applications in which NOT to use relays: • Loads that require currents under 10mA 4 • Loads which must be switched at high speed or heavy duty cycle Relay output module contacts are available in 5 Form A type, or SPST (single pole, single throw) Relay with Form A contacts normally open. 6 Some relay output module’s share common relay terminals, which connect to the wiper contact in 7 each relay of the bank. Other relay modules have relays which are completely isolated from each other. In all cases, the module drives the relay coil 8 when the corresponding output point is on. 9 Relay Outputs - Transient Suppression for Inductive Loads in a Control System 10 The following pages are intended to give a quick overview of the negative effects of transient voltages on a control system and provide some simple advice on how to effectively minimize them. The need for transient suppression is often not apparent to the newcomers in the 11 automation world. Many mysterious errors that can afflict an installation can be traced back to a lack of transient suppression. 12 What is a Transient Voltage and Why is it Bad? Inductive loads (devices with a coil) generate transient voltages as they transition from being 13 energized to being de-energized. If not suppressed, the transient can be many times greater than the voltage applied to the coil. These transient voltages can damage PLC outputs or 14 other electronic devices connected to the circuit, and cause unreliable operation of other electronics in the general area. Transients must be managed with suppressors for long component life and reliable operation of the control system. A This example shows a simple circuit with a small 24V/ 125mA/ 3W relay. As you can see, when the switch is opened, thereby de-energizing the coil, the transient voltage generated B across the switch contacts peaks at 140V. C D Do-more T1H Series PLC User Manual, 1st Edition, Rev. A - T1H-DM-M
8-31
Page 154
Chapter 8: Installation and Wiring Example: Circuit with no Suppression
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 8-32
Oscilloscope
Volts 160 140 120
24VDC
100
+ -
80
Relay Coil (24V/ 125mA/ 3W, AutomationDirect part no. 750-2C-24D)
60 40 20 0 -20
In the same circuit, replacing the relay with a larger 24V/ 290mA/ 7W relay will generate a transient voltage exceeding 800V (not shown). Transient voltages like this can cause many problems, including: • contacts driving the coil may experience arcing, which can pit the contacts and reduce the relay’s lifespan. • state (transistor) outputs driving the coil can be damaged if the transient voltage exceeds the transistor’s ratings. In extreme cases, complete failure of the output can occur the very first time a coil is de-energized. • circuits, which might be connected to monitor the coil or the output driver, can also be damaged by the transient voltage.
A very destructive side-effect of the arcing across relay contacts is the electromagnetic interference (EMI) it can cause. This occurs because the arcing causes a current surge, which releases RF energy. The entire length of wire between the relay contacts, the coil, and the power source carries the current surge and becomes an antenna that radiates the RF energy. It will readily couple into parallel wiring and may disrupt the PLC and other electronics in the area. This EMI can make an otherwise stable control system behave unpredictably at times. PLC’s Integrated Transient Suppressors Although the PLC’s outputs typically have integrated suppressors to protect against transients, they are not capable of handling them all. It is usually necessary to have some additional transient suppression for an inductive load. The next example uses the same 24V/125mA/3W relay used earlier. This example measures the PNP transistor output of a D0-06DD2 PLC, which incorporates an integrated Zener diode for transient suppression. Instead of the 140V peak in the first example, the transient voltage here is limited to about 40V by the Zener diode. While the PLC will probably tolerate repeated transients in this range for some time, the 40V is still beyond the module’s peak output voltage rating of 30V.
Do-more T1H Series PLC User Manual, 1st Edition, Rev. A - T1H-DM-M
Page 155
Chapter 8: Installation and Wiring Example: Small Inductive Load with Only Integrated Suppression 2VFLOORVFRSH
9ROWV
9'&
&RLO
The next example uses the same circuit as above, but with a larger 24V/ 290mA/ 7W relay, thereby creating a larger inductive load. As you can see, the transient voltage generated is much worse, peaking at over 50V. Driving an inductive load of this size without additional transient suppression is very likely to permanently damage the PLC output. Example: Larger Inductive Load with Only Integrated Suppression 2VFLOORVFRSH
9ROWV
9'&
&RLO
Additional transient suppression should be used in both these examples. If you are unable to measure the transients generated by the connected loads of your control system, using additional transient suppression on all inductive loads would be the safest practice.
Do-more T1H Series PLC User Manual, 1st Edition, Rev. A - T1H-DM-M
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
8-33
Page 156
Chapter 8: Installation and Wiring Types of Additional Transient Protection
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 8-34
DC Coils: The most effective protection against transients from a DC coil is a flyback diode. A flyback diode can reduce the transient to roughly 1V over the supply voltage, as shown in this example. DC Flyback Circuit
Volts
Oscilloscope
30 25 20
+ 24 VDC _
15 10 5 0 -5
Sinking
Sourcing
Many AutomationDirect socketed relays and motor starters have add-on flyback diodes that plug or screw into the base, such as the AD-ASMD-250 protection diode module and 784-4C-SKT-1 socket module shown below. If an add-on flyback diode is not available for your inductive load, an easy way to add one is to use an AutomationDirect DN-D10DR-A diode terminal block, a 600VDC power diode mounted in a slim DIN rail housing.
AD-ASMD-250 Protection Diode Module
784-4C-SKT-1 Relay Socket
DN-D10DR-A Diode Terminal Block
Do-more T1H Series PLC User Manual, 1st Edition, Rev. A - T1H-DM-M
Page 157
Chapter 8: Installation and Wiring Two more common options for DC coils are Metal Oxide Varistors (MOV) or TVS diodes. These devices should be connected across the driver (PLC output) for best protection as shown below. The optimum voltage rating for the suppressor is the lowest rated voltage available that will NOT conduct at the supply voltage, while allowing a safe margin. An AutomationDirect ZL-TSD8-24 transorb module is a good choice for 24VDC circuits. It is a bank of 8 uni-directional 30V TVS diodes. Since they are uni-directional, be sure to observe the polarity during installation. MOVs or bi-directional TVS diodes would install at the same location, but have no polarity concerns.
1 2 3 DC MOV or TVS Diode Circuit 4 5 6 7 AC Coils: 8 Two options for AC coils are MOVs or bi-directional TVS diodes. These devices are most effective at protecting the driver from a transient voltage when connected across the driver (PLC output) but are also commonly connected across the coil. The optimum voltage rating for the suppressor 9 is the lowest rated voltage available that will NOT conduct at the supply voltage, while allowing a safe margin. 10 11 12 13 An AutomationDirect ZL-TSD8-120 transorb module is a good choice for 120VAC circuits. It is 14 a bank of eight bi-directional 180V TVS diodes. A NOTE: Manufacturers of devices with coils frequently offer MOV or TVS diode suppressors as an addon option which mount conveniently across the coil. Before using them, carefully check the suppressor B ratings. Just because the suppressor is made specifically for that part does not mean it will reduce the transient voltages to an acceptable level. For example, a MOV or TVS diode rated for use on 24–48 VDC coils would need to have a high C enough voltage rating to NOT conduct at 48V. That suppressor might typically start conducting at roughly 60VDC. If it were mounted across a 24V coil, transients of roughly 84V (if sinking D +
24 VDC _
Sinking
Sourcing
AC MOV or Bi-Directional Diode Circuit
VAC output) or -60V (if sourcing output) could reach the PLC output. Many semiconductor PLC outputs cannot tolerate such levels. Do-more T1H Series PLC User Manual, 1st Edition, Rev. A - T1H-DM-M
8-35
Page 158
Chapter 8: Installation and Wiring
1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D
Notes:
8-36
Do-more T1H Series PLC User Manual, 1st Edition, Rev. A - T1H-DM-M
Page 159
European Union Directives (CE)
Appendix
A
In This Appendix... European Union (EU) Directives. .......................................................................... A-2 Basic EMC Installation Guidelines......................................................................... A-5
Page 160
Appendix A: European Union Directives (CE)
European Union (EU) Directives
A B 3 D 5 H 7 10 I 10 11 12 13 14 A B C D
NOTE: The information contained in this section is intended as a guideline and is based on our interpretation of the various standards and requirements. Since the actual standards are issued by other parties, and in some cases governmental agencies, the requirements can change over time without advance warning or notice. Changes or additions to the standards can possibly invalidate any part of the information provided in this section.
This area of certification and approval is absolutely vital to anyone who wants to do business in Europe. One of the key tasks that faced the EU member countries and the European Economic Area (EEA) was the requirement to bring several similar yet distinct standards together into one common standard for all members. The primary purpose of a single standard was to make it easier to sell and transport goods between the various countries and to maintain a safe working and living environment. The Directives that resulted from this merging of standards are now legal requirements for doing business in Europe. Products that meet these Directives are required to have a CE mark to signify compliance.
Member Countries As of January 1, 2015, the members of the EU are Austria, Belgium, Bulgaria, Croatia, Republic of Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, and United Kingdom. Iceland, Liechtenstein, and Norway together with the EU members make up the European Economic Area (EEA) and all are covered by the Directives.
Applicable Directives There are several Directives that apply to our products. Directives may be amended, or added, as required. • Compatibility Directive (EMC), this Directive attempts to ensure that devices, equipment, and systems have the ability to function satisfactorily in an electromagnetic environment without introducing intolerable electromagnetic disturbance to anything in that environment. • Safety Directive, this Directive covers the safety aspects of the equipment, installation, etc. There are several areas involved, including testing standards covering both electrical noise immunity and noise generation. •L ow Voltage Directive (LVD), this Directive is also safety related and covers electrical equipment that has voltage ranges of 50–1000VAC and/or 75–1500VDC. •B attery Directive, this Directive covers the production, recycling, and disposal of batteries.
Compliance Certain standards within each Directive already require mandatory compliance. The EMC Directive, which has gained the most attention, became mandatory as of January 1, 1996. The Low Voltage Directive became mandatory as of January 1, 1997. Ultimately, we are all responsible for our various pieces of the puzzle. As manufacturers, we must test our products and document any test results and/or installation procedures that are necessary to comply with the Directives. As an end user, you are responsible for installing the products applying “good engineering practices” and in a manner which will ensure compliance is maintained.
A-2
Do-more T1H Series PLC User Manual, 1st Edition, Rev. A - T1H-DM-M
Page 161
Appendix A: European Union Directives (CE) You are also responsible for testing any combinations of products that may (or may not) comply with the Directives when used together. The end user of the products must comply with any Directives that may cover maintenance, disposal, etc. of equipment or various components. Although we strive to provide the best assistance available, it is impossible for us to test all possible configurations of our products with respect to any specific Directive. Because of this, it is ultimately your responsibility to ensure that your machinery (as a whole) complies with these Directives and to keep up with applicable Directives and/or practices that are required for compliance. PLC systems manufactured by Koyo Electronics Industries, FACTS Engineering or HOST Engineering, when properly installed and used, conform to the Electromagnetic Compatibility (EMC), Low Voltage Directive, and Machinery Directive requirements of the following standards.
A B 3 D 5 •E MC Directive Standards Relevant to PLCs EN50081–1 Generic emission standard for residential, commercial, and light industry EN50081–2 Generic emission standard for industrial environment. H EN50082–1 Generic immunity standard for residential, commercial, and light industry EN50082–2 Generic immunity standard for industrial environment. 7 • Voltage Directive Standards Applicable to PLCs EN61010–1 Safety requirements for electrical equipment for measurement, control, and laboratory use. 10 • Specific Standard for PLCs EN61131–2 Programmable controllers, equipment requirements and tests. This standard replaces I the above generic standards for immunity and safety. However, the generic emissions standards must still be used in conjunction with the following standards: -EN 61000-3-2 Harmonics 10 -EN 61000-3-2 Fluctuations • on Electrostatic Discharge (ESD) 11 We recommend that all personnel take necessary precautions to avoid the risk of transferring static charges to inside the control cabinet, and clear warnings and instructions should be provided on the cabinet exterior. Such precautions may include, the use of earth straps, similar 12 devices or the powering off of the equipment inside the enclosure before the door is opened. • on Radio Interference (RFI) 13 This is a class A product. In a domestic environment this product may cause radio interference in which case the user may be required to take adequate measures. 14 General Safety • External switches, circuit breaker or external fusing, are required for these devices. A • switch or circuit breaker should be mounted near the PLC equipment. AutomationDirect is currently in the process of changing their testing procedures from the B generic standards to the product specific standards. C D Do-more T1H Series PLC User Manual, 1st Edition, Rev. A - T1H-DM-M
A-3
Page 162
Appendix A: European Union Directives (CE)
Special Installation Manual The installation requirements to comply with the requirements of the Machinery Directive, EMC Directive and Low Voltage Directive are slightly more complex than the normal installation requirements found in the United States. To help with this, we have published a special manual which you can order or download from our website:
A B 3 D 5 H 7 10 I 10 11 12 13 14 A B C D
• – EU Installation Manual that covers special installation requirements to meet the EU Directive requirements. Order this manual to obtain the most up-to-date information.
Other Sources of Information Although the EMC Directive gets the most attention, other basic Directives, such as the Machinery Directive and the Low Voltage Directive, also place restrictions on the control panel builder. Because of these additional requirements it is recommended that the following publications be purchased and used as guidelines: • publication BS TH 42073: November 2000 – covers the safety and electrical aspects of the Machinery Directive • 60204–1:2006 – Safety of Machinery; General electrical requirements for machinery, including Low Voltage and EMC considerations • IEC 61000–5–2: EMC earthing and cabling requirements • IEC 61000–5–1: EMC general considerations
It may be possible for you to obtain this information locally; however, the official source of applicable Directives and related standards is: Publications Office 2, rue Mercier 2985 Luxembourg LUXEMBOURG Quickest contact is via the web at: http://ec.europa.eu/growth/single-market/european-standards/harmonised-standards. Another source is the British Standards Institution at: British Standards Institution – Sales Department, Linford Wood: Milton Keynes, MK14 6LE, United Kingdom. The quickest contact is via the web at www.bsigroup.com
A-4
Do-more T1H Series PLC User Manual, 1st Edition, Rev. A - T1H-DM-M