Page 163
Appendix A: European Union Directives (CE)
Basic EMC Installation Guidelines
A The simplest way to meet the safety requirements of the Machinery and Low Voltage B Directives is to house all control equipment in an industry standard lockable steel enclosure. This normally has an added benefit because it will also help ensure that the EMC characteristics are well within the requirements of the EMC Directive. Although the RF 3 emissions from the PLC equipment, when measured in the open air, are well below the EMC Directive limits, certain configurations can increase emission levels. Holes in the enclosure, D for the passage of cables or to mount operator interfaces, will often increase emissions. 5 H 7 10 I 10 11 12 13 Electrostatic Discharge (ESD) 14 We specify in all declarations of conformity that our products are installed inside an industrial enclosure using metallic conduit for external wire runs; therefore, we test the products in a A typical enclosure. However, we would like to point out that although our products operate normally in the presence of ESD, this is only the case when mounted within an enclosed industrial control cabinet. When the cabinet is open during installation or maintenance, the B equipment and or programs may be at risk of damage from ESD carried by personnel. We therefore recommend that all personnel take necessary precautions to avoid the risk of C transferring static electricity to components inside the control cabinet. If necessary, clear warnings and instructions should be provided on the cabinet exterior, such as recommending D the use of earth straps of similar devices, or the powering off of equipment inside the Enclosures
Mains Fuse/ Isolation Transformer
Lockout switch for communication
*Toroid for communication cables
Conduit for communication cables
T1H-DM1E
T1K-16TR
I/O
ERR
T1F-08AD-1
TERM
RUN
RUN
STOP
USB TX
RX
USB PGM PORT
2" (50mm) minimum clearance all sides
*Separate conduit and toroid coils for DC signals AC signals, and analog signals
*Mains filter
Metallic conduit required
Transient voltage suppressor
Pressure-sensitive switch for power
I/O common ground
*May be required for CE compliance (see Declaration of Conformity for specific product requirements).
enclosure.
Do-more T1H Series PLC User Manual, 1st Edition, Rev. A - T1H-DM-M
A-5
Page 164
Appendix A: European Union Directives (CE)
AC Mains Filters
A B 3 D 5 H 7 10 I 10 11 12 13 14 A B C D
The AC powered base power supplies require extra mains filtering to comply with the EMC Directive on conducted RF emissions. All PLC equipment has been tested with filters from Schaffner, which reduce emissions levels if the filters are properly grounded (earth ground). A filter with a current rating suitable to supply all PLC power supplies and AC input modules should be selected. We suggest the FN2080 for Do-more systems.
L
N
Fused Terminals
Earth Terminal
Filter
Schaffner FN2010
Transient Suppressor
To AC Input Circuitry
NOTE: Very few mains filters can reduce problem emissions to negligible levels. In some cases, filters may increase conducted emissions if not properly matched to the problem emissions.
Suppression and Fusing In order to comply with the fire risk requirements of the Low Voltage and Machinery Directive electrical standards (EN 61010–1 and EN 60204–1), by limiting the power into “unlimited” mains circuits with power leads reversed, it is necessary to fuse both AC and DC supply inputs. You should also install a transient voltage suppressor across the power input connections of the PLC. Choose a suppressor such as a metal oxide varistor, with a rating of 275VAC working voltage for 230V nominal supplies (150VAC working voltage for 115V supplies) and high energy capacity (eg. 140 joules). Transient suppressors must be protected by fuses and the capacity of the transient suppressor must be greater than the blow characteristics of the fuses or circuit breakers to avoid a fire risk. A recommended AC supply input arrangement for Koyo PLCs is to use twin 3 amp TT fused terminals with fuse blown indication, such as DINnectors DN–F10L terminals, or twin circuit breakers, wired to a Schaffner FN2010 filter or equivalent, with high energy transient suppressor soldered directly across the output terminals of the filter. PLC system inputs should also be protected from voltage impulses by deriving their power from the same fused, filtered, and surge-suppressed supply.
Internal Enclosure Grounding A heavy-duty star earth terminal block should be provided in every cubicle for the connection of all earth ground straps, protective earth ground connections, mains filter earth ground wires, and mechanical assembly earth ground connections. This should be installed to comply with safety and EMC requirements, local standards, and the requirements found in IEC 1000–5–2. The Machinery Directive also requires that the common terminals of PLC input modules, and common supply side of loads driven from PLC output modules should be connected to the protective earth ground terminal.
A-6
Do-more T1H Series PLC User Manual, 1st Edition, Rev. A - T1H-DM-M
Page 165
Appendix A: European Union Directives (CE)
Equi–potential Grounding
A B 3 D Serial Communication Cable Key Equi-potential Bond 5 Adequate site earth grounding must be provided for equipment containing modern electronic circuitry. The use of isolated earth electrodes for electronic systems is forbidden H in some countries. Make sure you check any requirements for your particular destination. IEC 1000–5–2 covers equipotential bonding of earth grids adequately, but special attention 7 should be given to apparatus and control cubicles that contain I/O devices, remote I/O racks, or have inter-system communications with the primary PLC system enclosure. An 10 equipotential bond wire must be provided alongside all serial communications cables, and to any separate items of the plant which contain I/O devices connected to the PLC. The diagram shows an example of four physical locations connected by a communications cable. I 10 11 12 13 14 A Communications and Shielded Cables Good quality 24AWG minimum twisted-pair shielded cables, with overall foil and braid B shields are recommended for analog cabling and communications cabling outside of the PLC enclosure. To date it has been a common practice to only provide an earth ground for one C end of the cable shield in order to minimize the risk of noise caused by earth ground loop currents between apparatus. The procedure of only grounding one end, which primarily originated as a result of trying to reduce hum in audio systems, is no longer applicable to the D complex industrial environment. Shielded cables are also efficient emitters of RF noise from Screened Cable
Conductive Adapter
Serial I/O
To Earth Block
Equi-potential Bond
Control Cubicle the PLC system, and can interact in a parasitic manner in networks and between multiple sources of interference. Do-more T1H Series PLC User Manual, 1st Edition, Rev. A - T1H-DM-M
A-7
Page 166
Appendix A: European Union Directives (CE)
A B 3 D 5 H 7 10 I 10 11 12 13 14 A B C D
The recommendation is to use shielded cables as electrostatic “pipes” between apparatus and systems, and to run heavy gauge equipotential bond wires alongside all shielded cables. When a shielded cable runs through the metallic wall of an enclosure or machine, it is recommended in IEC 1000–5–2 that the shield should be connected over its full perimeter to the wall, preferably using a conducting adapter, and not via a pigtail wire connection to an earth ground bolt. Shields must be connected to every enclosure wall or machine cover that they pass through.
Analog and RS232 Cables Providing an earth ground for both ends of the shield for analog circuits provides the perfect electrical environment for the twisted pair cable as the loop consists of signal and return, in a perfectly balanced circuit arrangement, with connection to the common of the input circuitry made at the module terminals. RS232 cables are handled in the same way.
Multi-drop Cables RS422 twin twisted pair, and RS485 single twisted pair cables also require a 0V link, which has often been provided in the past by the cable shield. It is now recommended that you use triple twisted pair cabling for RS422 links, and twin twisted pair cable for RS485 links. This is because the extra pair can be used as the 0V inter-system link. With loop DC power supplies earth grounded in both systems, earth loops are created in this manner via the intersystem 0v link. The installation guides encourage earth loops, which are maintained at a low impedance by using heavy equipotential bond wires. To account for non–European installations using single-end earth grounds, and sites with far from ideal earth ground characteristics, we recommend the addition of 100 ohm resistors at each 0V link connection in network and communications cables. Last Slave
100
Master
Slave n
TXD 0V RXD + – + –
TXD 0V RXD + – + –
RXD 0V TXD + – + –
100 100 Termination
Termination
Shielded Cables within Enclosures When you run cables between PLC items within an enclosure which also contains susceptible electronic equipment from other manufacturers, remember that these cables may be a source of RF emissions. There are ways to minimize this risk. Standard data cables connecting PLCs and/or operator interfaces should be routed well away from other equipment and their associated cabling. You can make special serial cables where the cable shield is connected to the enclosure’s earth ground at both ends, the same way as external cables are connected.
A-8
Do-more T1H Series PLC User Manual, 1st Edition, Rev. A - T1H-DM-M
Page 167
Appendix A: European Union Directives (CE)
Analog Modules and RF Interference All AutomationDirect products are tested to withstand field strength levels up to 10V/m, which is the maximum required by the relevant EU standards. While all products pass this test, analog modules will typically exhibit deviations of their readings. This is quite normal, however, systems designers should be aware of this and plan accordingly. When assembling a control system using analog modules, these issues must be adhered to and should be integrated into the system design. This is the responsibility of the system builder/ commissioner.
A B 3 Network Isolation D For safety reasons, it is a specific requirement of the Machinery Directive that a keyswitch must be provided that isolates any network input signal during maintenance, so that remote 5 commands cannot be received that could result in the operation of the machinery. The FA–ISOCON does not have a keyswitch! Use a keylock and switch on your enclosure which H when open removes power from the FA–ISOCON. To avoid the introduction of noise into the system, any keyswitch assembly should be housed in its own earth grounded steel box and the integrity of the shielded cable must be maintained. 7 Again, for further information on EU directives we recommend that you get a copy of our EU Installation Manual (DA–EU–M). Also, if you are connected to the World Wide Web, 10 you can check the EU Commission’s official site at: http://ec.europa.eu/index_en.htm. DC Powered Versions I Due to slightly higher emissions radiated by the DC powered versions of the Do-more T1H Series PLC, and the differing emissions performance for different DC supply voltages, the 10 following stipulations must be met: • The PLC must be housed within a metallic enclosure with a minimum amount of orifices. 11 • and communications cabling exiting the cabinet must be contained within metallic conduit/ trunking. 12 13 14 A B C D Do-more T1H Series PLC User Manual, 1st Edition, Rev. A - T1H-DM-M
A-9
Page 168
Appendix A: European Union Directives (CE)
Items Specific to the Do-more T1H Series PLC
A B 3 D 5 H 7 10 I 10 11 12 13 14 A B C D A-10
• rating between all circuits in this product are rated as basic insulation only, as appropriate for single fault conditions. • There is no isolation offered between the PLC and the analog inputs of this product. • is the responsibility of the system designer to earth one side of all control and power circuits, and to earth the braid of screened cables. • equipment must be properly installed while adhering to the guidelines of the installation manual DA–EU–M (available for download at AutomationDirect Technical Support Manuals), and the installation standards IEC 1000–5–1, IEC 1000–5–2 and IEC 1131–4. • is a requirement that all PLC equipment must be housed in a protective steel enclosure, which limits access to operators by a lock and power breaker. If access is required by operators or untrained personnel, the equipment must be installed inside an internal cover or secondary enclosure. A warning label must be used on the front door of the installation cabinet as follows: Warning: Exposed terminals and hazardous voltages inside. • should be noted that the safety requirements of the machinery directive standard EN60204–1 state that all equipment power circuits must be wired through isolation transformers or isolating power supplies, and that one side of all AC or DC control circuits must be earthed. • power input connections to the PLC must be separately fused using 3 amp T-type anti–surge fuses, and a transient suppressor fitted to limit supply overvoltages. • the user is made aware by notice in the documentation that if the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
Do-more T1H Series PLC User Manual, 1st Edition, Rev. A - T1H-DM-M