Page 29

Chapter 1: Getting Started Only with the New Online option does the Do-more T1H Series PLC assume that you are creating a new project from scratch. With any other method, such as PLC > Connect, the software will compare the project in the controller with the offline version you have open. If there are any differences, this warning window will appear detailing the options available for continuing:

1 2 1. Online and view the DISK project - This option will go online with the PLC but display the project 3 from disk. Status displays may show incorrect information. If the memory configuration in the disk4 based project contains elements that are incompatible with the memory configuration currently in the Do-more PLC the message box seen here will be 5 displayed. 2. Online and view the PLC project - The project 6 from the PLC will be opened by Do-more Designer. 3. and return to Offline - This option will cancel the connection attempt and return to the offline project. 7 4. Programs... - If you are unsure as to why the two projects are different, then this option will do a comparison of the projects and detail the differences found. An example comparison is 8 seen below. 9 10 11 12 13 14 A B C D In this example, the PLC project titled My_DM was compared with a project stored on the PC. The report window shown above illustrates the differences found between the two.

Do-more T1H Series PLC Hardware User Manual, 1st Edition, Rev. A - T1H-DM-M

1–17

Page 30

Chapter 1: Getting Started

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 1–18

According to the report, the PLC project was different in two areas. First, a new code-block was found only in the PLC project. This new code-block is titled MyNewProgram and is highlighted in green. The green color represents items that exist only in the Current Project (project in PLC) and not in the Other (project in PC). Also, the comparison noted that a normally open contact (STR) was changed to a normally closed contact (STRN) at $Main@0. This item is highlighted in blue which represents items that are different between the PLC Project and the project in the PC. Other colors used in the comparison are red, which denotes items that exist only in the project on the PC and not in the PLC and black which highlights items that are identical in both projects. There are also numerous checkbox and radio button options available to help you analyze the differences between projects.

Once you have connected to the CPU either by using the New Online option or using PLC > Connect for offline projects, you may encounter the initialization windows shown here.

The Set PLC Clock option (above) allows you to set the internal, realtime clock of the PLC. The Set PLC Clock window (right) has options for Timezones and Daylight Savings Adjustments. The Setup System Configuration option (left) allows you to configure the parameters of the Do-more T1H Series PLC. I/O module configuration, CPU ports, and I/O mapping profiles are a few of the parameters available in the System Configuration window. Refer to the following section for Hardware Configuration options.

Do-more T1H Series PLC Hardware User Manual, 1st Edition, Rev. A - T1H-DM-M

Page 31

Chapter 1: Getting Started Once all parameters have been configured, the following programming window will open with the online toolbar active.

1 2 3 4 5 6 7 8 9 Notice that the status bar indications show PLC type, memory usage, communication status, PLC errors, PLC mode, etc. Hovering your mouse over the status bar will highlight the items 10 that are selectable. If you select one of these items, a new window will open with real-time 11 data and options that are available for that selection. As an example, the System Information window seen here appears after selecting the Memory Usage indication from the status bar. 12 13 14 A B C D Do-more T1H Series PLC Hardware User Manual, 1st Edition, Rev. A - T1H-DM-M

1–19

Page 32

Chapter 1: Getting Started

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

Step 6: Verify Hardware Configuration

1–20

Next, you will need to verify the hardware configuration for accuracy. The Do-more T1H Series PLC has an auto discover feature that will automatically detect the I/O modules installed. You can see the results of this search by selecting PLC > System Configuration, double clicking the CPU link under the Configuration tab in the Project Browser, or by clicking the XY Configure icon in the Project Toolbar.

On the left side of the System Configuration window is an index of topics titled Configuration Entries. Click the I/O Configuration tab and you should see an overview of the modules that the software located, similar to the following.

From here you can verify that the software has detected all of the I/O modules that are installed.

Do-more T1H Series PLC Hardware User Manual, 1st Edition, Rev. A - T1H-DM-M

Page 33

Chapter 1: Getting Started The Do-more T1H Series PLC allows the I/O to be manually configured as well. In order to do so, you must first set the I/O Configuration Mode to manual. Select the Terminator Local I/O Master tab found under the I/O Configuration tab in the Configuration Entries index. The Terminator Local I/O Master Configuration window shown here will appear. From here select Manual to configure the I/O modules that are installed in the system yourself. It is important to remember that the PLC will compare what you configure with what is installed and they must match for the PLC to work properly.

1 2 3 4 5 6 7 NOTE: If the manually configured I/O modules do not match the installed I/O modules, the PLC will not go into Run Mode. 8 After you have set the configuration mode to Manual, select the Terminator Base tab in the Configuration Entries index. This will take you to the following set up window. 9 10 11 12 13 14 A B C Notice that from this window, you can perform a Manual Scan. When initiated, this scan D will poll the available modules connected to the PC and display the I/O found. The results can then be altered as you choose.

Do-more T1H Series PLC Hardware User Manual, 1st Edition, Rev. A - T1H-DM-M

1–21

Page 34

Chapter 1: Getting Started

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D 1–22

To manually enter your I/O modules into the configuration, right click on the slot the module will reside in, select Add Module and then choose the module from the drop down list. Once you have selected the module, it will appear in the slot that was chosen. In order to

Insert a module manually between two existing modules in the System Configuration Window, you would follow the same steps as mentioned above but instead of selecting ‘Add Module’ the selection will be ‘Insert Module’ as seen below.

Do-more T1H Series PLC Hardware User Manual, 1st Edition, Rev. A - T1H-DM-M

Page 35

Chapter 1: Getting Started After the hardware configuration has been verified select the I/O Mappings tab in the Configuration Entries index. This option will display the assigned addresses for the configured modules as seen below.

1 2 3 4 5 6 7 8 9 10 11 These X (discrete input), Y (discrete output), WX (analog input) and WY (analog output) addresses are automatically assigned by Do-more Designer. You have the option to manually 12 configure these addresses by selecting Manual in the Mapping Mode section at the bottom of the window. 13 The Manual Mode Instructions section, also found at the bottom of the window, details the various color indications associated with this mode. 14 A B C D Do-more T1H Series PLC Hardware User Manual, 1st Edition, Rev. A - T1H-DM-M

1–23

Page 36

Chapter 1: Getting Started

1 2 3 4 5 6 7 8 9 10 11 12 13 14 A B C D

Step 7: Create a Ladder Logic Program

1–24

To create a ladder logic program, you must first place the software in Edit Mode. Click the Edit Mode button found in the Project Toolbar or Ladder Palette Bar or use the shortcut Ctrl+E.

When in Edit Mode, all of the Ladder Palette Bar’s options will become active and the cursor in Ladder View will fill in blue. Now, you are ready to begin entering the example ladder logic below.

Rung #1 Place the box cursor in the NOP position on Rung #1. If the Instruction Palette is not open, then click Instructions from the Ladder Palette Bar and select the TMR (Timer) or type a “T” and select TMR from the drop down menu, then press Enter. Once TMR is selected, a Timer dialog box appears. 1. the Timer Struct to T1. 2. 03 into the Preset Constant Value for the seconds (s) preset. 3. the checkmark in the upper left corner to accept.

After clicking the checkmark, Rung #1 should show the T1 timer (TMR) instruction with a preset of 3.000 seconds. A user variable can be assigned to the preset value if needed.